Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
dummy [2026/05/16 22:03] mexleadmindummy [2026/05/26 13:48] (current) – removed mexleadmin
Line 1: Line 1:
-====== Block 09/10 — Transformers and Magnetic Coupling ====== 
  
-===== Learning objectives ===== 
-<callout> 
-After this 90-minute block, you can 
- 
-  * explain how two coils can exchange energy by a common magnetic flux \(\Phi\). 
-  * use the ideal transformer equations 
-\[ 
-\begin{align*} 
-\frac{\underline{U}_1}{\underline{U}_2}=\frac{N_1}{N_2}=n, 
-\qquad 
-\frac{\underline{I}_1}{\underline{I}_2}=-\frac{1}{n} 
-\end{align*} 
-\] 
-with a clear sign convention. 
-  * explain mutual inductance \(M\) using flux linkage and magnetic reluctance \(R_{\rm m}\). 
-  * distinguish **main flux**, **leakage flux**, **copper losses**, and **iron losses** in a real transformer. 
-  * refer secondary-side quantities to the primary side using \( \underline{U}'_2=n\underline{U}_2\), \( \underline{I}'_2=\frac{1}{n}\underline{I}_2\), \(R'_2=n^2R_2\), and \(X'_{2\sigma}=n^2X_{2\sigma}\). 
-  * interpret the no-load test and short-circuit test using the reduced equivalent circuit. 
-  * calculate short-circuit voltage \(u_{\rm k}\), continuous short-circuit current \(I_{\rm 1k}\), and an estimated initial peak short-circuit current. 
-  * connect transformer parameters to engineering applications in mechatronics and robotics, such as isolated power supplies, motor current measurement, welding transformers, and safety transformers. 
-</callout> 
- 
-===== Preparation at Home ===== 
- 
-Well, again 
- 
-  * read through the present chapter and write down anything you did not understand. 
-  * Repeat the EEE1 ideas of [[:electrical_engineering_1:block18|magnetic flux and induction]], [[:electrical_engineering_1:block19|magnetic circuits]], and [[:electrical_engineering_1:block20|inductance and magnetic energy]]. 
-  * Repeat from EEE2 the use of [[block03|sinusoidal quantities]], [[block04|complex calculation]], and [[block06|complex power]]. 
-  * For a deeper field-theory view, see also [[:electrical_engineering_2:magnetic_circuits#mutual_induction_and_coupling|Mutual Induction and Coupling]]. 
- 
-For checking your understanding please do the quick checks in the exercise section. 
- 
-===== 90-minute plan ===== 
- 
-  * **Warm-up (10 min):** 
-    * Where do transformers occur in robots and automation systems? 
-    * Recall: Faraday induction from EEE1 — a changing magnetic flux induces a voltage. 
-    * Recall: in AC analysis we use RMS phasors \(\underline{U}\), \(\underline{I}\), and impedances \(j\omega L\). 
- 
-  * **Core concepts and derivations (55 min):** 
-    * Ideal transformer: common flux, voltage ratio, current ratio, power balance. 
-    * Mutual inductance: how flux from one coil links another coil. 
-    * Magnetic coupling with reluctance \(R_{\rm m}\). 
-    * Real transformer: winding resistances, leakage inductances, iron-loss resistance. 
-    * Reduced equivalent circuit: refer secondary quantities to the primary side. 
-    * No-load and short-circuit operation: what can be measured, what can be neglected. 
- 
-  * **Practice (20 min):** 
-    * Quick ratio calculations for step-up and step-down transformers. 
-    * Unit checks for \(j\omega L\), \(j\omega N\Phi\), and \(u_{\rm k}\). 
-    * Short-circuit current calculation for a transformer used in an actuator supply. 
- 
-  * **Wrap-up (5 min):** 
-    * Summary box: ideal transformer, mutual inductance, real transformer, reduced circuit, short-circuit parameters. 
-    * Common pitfalls checklist. 
- 
-===== Conceptual overview ===== 
-<callout icon="fa fa-lightbulb-o" color="blue"> 
-  * A transformer is **not** a DC component. It needs a changing magnetic flux. In normal operation this is usually a sinusoidal flux created by AC voltage. 
-  * The transformer does not “create power”. Ideally, it trades voltage for current: 
-\[ 
-\begin{align*} 
-\text{higher voltage} \quad \Longleftrightarrow \quad \text{lower current} 
-\end{align*} 
-\] 
-  * The link between the two windings is the magnetic field in the iron core. This continues directly from EEE1: 
-    * [[:electrical_engineering_1:block18|induction]] explains why a changing flux induces voltage. 
-    * [[:electrical_engineering_1:block19|magnetic circuits]] explains why the iron core guides the flux. 
-    * [[:electrical_engineering_1:block20|inductance]] explains how flux linkage and current are connected. 
-  * Mutual inductance \(M\) measures how strongly one coil “notices” the changing current in another coil. 
-  * A real transformer is almost ideal, but not quite: 
-    * \(R_1, R_2\): copper losses in the windings. 
-    * \(L_{1\sigma}, L_{2\sigma}\): leakage flux that does not couple both windings. 
-    * \(R_{\rm Fe}\): iron losses in the core. 
-    * \(L_{\rm H}\): main magnetizing inductance needed to create the main flux. 
-  * In engineering, transformer data such as \(u_{\rm k}\) are not abstract: they determine voltage drop, fault current, thermal stress, and protection design. 
-</callout> 
- 
-~~PAGEBREAK~~ ~~CLEARFIX~~ 
- 
-===== Core content ===== 
- 
-==== From EEE1 induction to an AC transformer ==== 
- 
-<panel type="info" title="Transition from EEE1 to EEE2"> 
-In EEE1 we considered magnetic flux \(\Phi\), flux linkage \(\Psi\), and induction.   
-For one coil with \(N\) turns the flux linkage is 
- 
-\[ 
-\begin{align*} 
-\Psi = N\Phi . 
-\end{align*} 
-\] 
- 
-Faraday's law gives 
- 
-\[ 
-\begin{align*} 
-u(t)=\frac{{\rm d}\Psi}{{\rm d}t}=N\frac{{\rm d}\Phi}{{\rm d}t}. 
-\end{align*} 
-\] 
- 
-In sinusoidal steady state this becomes the phasor equation 
- 
-\[ 
-\begin{align*} 
-\underline{U}=j\omega\underline{\Psi}=j\omega N\underline{\Phi}. 
-\end{align*} 
-\] 
- 
-This is the starting point for the transformer. 
-</panel> 
- 
-<WRAP> 
-<panel type="default"> 
-<imgcaption fig_transformer_principle|Idealized single-phase transformer with primary winding, secondary winding, iron core, and common main flux \(\Phi\).></imgcaption> 
-{{drawio>block09_transformer_principle.svg}} 
-</panel> 
-</WRAP> 
- 
-<callout type="info" icon="true"> 
-**Unit check for induced voltage** 
- 
-\[ 
-\begin{align*} 
-\underline{U}=j\omega N\underline{\Phi} 
-\end{align*} 
-\] 
- 
-with 
- 
-\[ 
-\begin{align*} 
-[\omega\Phi]={\rm s}^{-1}\cdot {\rm Wb} 
-={\rm s}^{-1}\cdot {\rm V\,s} 
-={\rm V}. 
-\end{align*} 
-\] 
- 
-The number of turns \(N\) is dimensionless. 
-</callout> 
- 
-==== Mutual induction: the key idea before the transformer ==== 
- 
-Before we look at the transformer, we need one important idea: 
- 
-<callout icon="fa fa-lightbulb-o" color="blue"> 
-A changing current in coil \(1\) creates a changing magnetic flux.   
-If part of this flux passes through coil \(2\), a voltage is induced in coil \(2\).   
-This is called **mutual induction**. 
-</callout> 
- 
-<WRAP> 
-<panel type="default"> 
-<imgcaption fig_mutual_induction_two_coils|Mutual induction of two coils: only part of the flux created by coil \(1\) links coil \(2\).></imgcaption> 
-{{:electrical_engineering_2:mutualinductiontwocoils1.svg?650}} 
-</panel> 
-</WRAP> 
- 
-The flux created by coil \(1\) can be split into 
- 
-\[ 
-\begin{align*} 
-\Phi_{11} 
-= 
-{\color{blue}{\Phi_{21}}} 
-+ 
-{\color{orange}{\Phi_{\rm S1}}}. 
-\end{align*} 
-\] 
- 
-  * \(\Phi_{11}\): total flux created by coil \(1\). 
-  * \({\color{blue}{\Phi_{21}}}\): part of this flux that also links coil \(2\). 
-  * \({\color{orange}{\Phi_{\rm S1}}}\): stray or leakage flux that does **not** link coil \(2\). 
- 
-The voltage induced in coil \(2\) is 
- 
-\[ 
-\begin{align*} 
-u_{{\rm ind},2}(t) 
-= 
--N_2\frac{{\rm d}{\color{blue}{\Phi_{21}}}}{{\rm d}t}. 
-\end{align*} 
-\] 
- 
-<panel type="info" title="Analogy: two pendulums connected by a spring"> 
-Imagine two pendulums connected by a weak spring. 
- 
-  * If pendulum \(1\) moves, the spring can make pendulum \(2\) move as well. 
-  * A strong spring transfers the motion strongly. 
-  * A weak spring transfers the motion only weakly. 
-  * If the spring is missing, pendulum \(2\) does not react. 
- 
-For coupled coils: 
- 
-  * the changing motion corresponds to changing current, 
-  * the spring corresponds to the magnetic coupling, 
-  * the motion transferred to the second pendulum corresponds to the induced voltage, 
-  * weak coupling means that only a small part of the magnetic flux links both coils. 
-</panel> 
- 
-<panel type="info" title="Analogy: a leaky magnetic pipe"> 
-The magnetic core can be imagined as a pipe guiding magnetic flux. 
- 
-  * A good iron core is like a wide, low-resistance pipe: most flux reaches the second coil. 
-  * A large air gap is like a narrow, difficult path: less flux reaches the second coil. 
-  * Leakage flux is like flow escaping through side paths: it belongs to the first coil but does not help the second coil. 
- 
-This image is helpful for transformers, wireless charging coils, and current sensors. 
-</panel> 
- 
-<panel type="info" title="Engineering examples"> 
-  * **Transformer:** very strong coupling because the iron core guides most of the flux through both windings. 
-  * **Wireless charger:** weaker coupling because the flux must cross an air gap and the coils may be misaligned. 
-  * **Current transformer:** the measured conductor acts like a one-turn primary winding; the secondary winding detects the changing magnetic field. 
-  * **Relay coil near signal wiring:** unwanted coupling can induce noise voltages in nearby loops. 
-</panel> 
- 
-==== Linked fluxes and mutual inductance ==== 
- 
-For a single coil we already know 
- 
-\[ 
-\begin{align*} 
-\Psi=L i . 
-\end{align*} 
-\] 
- 
-For two coupled coils, each flux linkage can depend on both currents. 
- 
-<panel type="info" title="Color scheme for coupled coils"> 
-In the following formulas: 
- 
-  * green terms: self-linkage of a coil by its own current, 
-  * blue terms: mutual linkage between both coils, 
-  * orange terms: leakage or stray flux that does not help energy transfer. 
-</panel> 
- 
-\[ 
-\begin{align*} 
-\Psi_1 
-&= 
-\underbrace{{\color{green}{L_{11}i_1}}}_{\text{self-linkage of coil 1}} 
-+ 
-\underbrace{{\color{blue}{M_{12}i_2}}}_{\text{mutual linkage from coil 2}}, 
-\\[4pt] 
-\Psi_2 
-&= 
-\underbrace{{\color{blue}{M_{21}i_1}}}_{\text{mutual linkage from coil 1}} 
-+ 
-\underbrace{{\color{green}{L_{22}i_2}}}_{\text{self-linkage of coil 2}}. 
-\end{align*} 
-\] 
- 
-For most transformer calculations we use the symmetric case 
- 
-\[ 
-\begin{align*} 
-M_{12}=M_{21}=M. 
-\end{align*} 
-\] 
- 
-Then 
- 
-\[ 
-\begin{align*} 
-\boxed{ 
-\begin{pmatrix} 
-\Psi_1\\ 
-\Psi_2 
-\end{pmatrix} 
-= 
-\begin{pmatrix} 
-{\color{green}{L_{11}}} & {\color{blue}{M}}\\ 
-{\color{blue}{M}} & {\color{green}{L_{22}}} 
-\end{pmatrix} 
-\begin{pmatrix} 
-i_1\\ 
-i_2 
-\end{pmatrix} 
-} 
-\end{align*} 
-\] 
- 
-and 
- 
-\[ 
-\begin{align*} 
-M=k\sqrt{L_{11}L_{22}}. 
-\end{align*} 
-\] 
- 
-Here \(k\) is the coupling coefficient. 
- 
-<tabcaption tab_coupling_coefficient|Meaning of the coupling coefficient \(k\)> 
- 
-^ Coupling coefficient ^ Interpretation ^ Typical example ^ 
-| \(k=0\) | no useful flux from one coil links the other coil | coils far apart | 
-| \(0<k<1\) | partial coupling | wireless charger with air gap or misalignment | 
-| \(k\approx 1\) | almost all useful flux links both coils | transformer with iron core | 
-| sign of \(k\) | depends on winding direction and reference arrows | dot convention | 
- 
-<panel type="info" title="How to read \(M\)"> 
-Mutual inductance \(M\) answers the question: 
- 
-> How much flux linkage appears in coil \(2\) when the current in coil \(1\) changes? 
- 
-A large \(M\) means strong interaction.   
-A small \(M\) means weak interaction. 
-</panel> 
- 
-==== Polarity and the dot convention ==== 
- 
-The sign of the mutual term depends on the winding direction and on the chosen current reference arrows. 
- 
-<WRAP> 
-<panel type="default"> 
-<imgcaption fig_direction_of_coupling|Dot convention: the dots indicate corresponding winding ends.></imgcaption> 
-{{:electrical_engineering_2:directionofcoupling.svg?650}} 
-</panel> 
-</WRAP> 
- 
-<callout> 
-**Rule of thumb** 
- 
-  * If both currents enter dotted terminals, the mutual fluxes support each other. 
-  * If one current enters a dotted terminal and the other current leaves a dotted terminal, the mutual fluxes oppose each other. 
-</callout> 
- 
-<WRAP group> 
-<WRAP column half> 
-<panel type="default"> 
-<imgcaption fig_positive_coupling|Positive coupling: currents enter corresponding dotted terminals.></imgcaption> 
-{{:electrical_engineering_2:poscoupling.svg?500}} 
-</panel> 
-</WRAP> 
- 
-<WRAP column half> 
-<panel type="default"> 
-<imgcaption fig_negative_coupling|Negative coupling: only one current enters a dotted terminal.></imgcaption> 
-{{:electrical_engineering_2:negcoupling.svg?500}} 
-</panel> 
-</WRAP> 
-</WRAP> 
- 
-For positive coupling: 
- 
-\[ 
-\begin{align*} 
-u_1 
-&= 
-{\color{green}{L_{11}\frac{{\rm d}i_1}{{\rm d}t}}} 
-+ 
-{\color{blue}{M\frac{{\rm d}i_2}{{\rm d}t}}}, 
-\\[4pt] 
-u_2 
-&= 
-{\color{blue}{M\frac{{\rm d}i_1}{{\rm d}t}}} 
-+ 
-{\color{green}{L_{22}\frac{{\rm d}i_2}{{\rm d}t}}}. 
-\end{align*} 
-\] 
- 
-For negative coupling, the sign of the \(M\)-term changes in the chosen equation system. 
- 
-<panel type="info" title="Engineering example: wireless charging"> 
-In wireless charging, the transmitter coil and receiver coil are separated by an air gap.   
-The coupling coefficient \(k\) is much smaller than in a transformer with an iron core. 
- 
-If the receiver is misaligned, less flux from the transmitter passes through it.   
-Then \(M\) decreases, the induced voltage decreases, and the transmitted power decreases. 
-</panel> 
- 
-~~PAGEBREAK~~ ~~CLEARFIX~~ 
- 
-==== Magnetic coupling with reluctance ==== 
- 
-We now use the magnetic circuit model from EEE1. 
- 
-The magnetic voltage, also called magnetomotive force, is 
- 
-\[ 
-\begin{align*} 
-\Theta=N i . 
-\end{align*} 
-\] 
- 
-For a magnetic path with reluctance \(R_{\rm m}\), Hopkinson's law is 
- 
-\[ 
-\begin{align*} 
-\Theta=R_{\rm m}\Phi 
-\qquad \Longleftrightarrow \qquad 
-\Phi=\frac{\Theta}{R_{\rm m}}. 
-\end{align*} 
-\] 
- 
-<panel type="info" title="Analogy to an electric circuit"> 
-\[ 
-\begin{align*} 
-\text{electric:}\quad U=R I 
-\qquad 
-\text{magnetic:}\quad \Theta=R_{\rm m}\Phi 
-\end{align*} 
-\] 
- 
-  * Electric voltage \(U\) pushes electric current \(I\) through resistance \(R\). 
-  * Magnetic voltage \(\Theta=N i\) pushes magnetic flux \(\Phi\) through reluctance \(R_{\rm m}\). 
-</panel> 
- 
-For two windings on the same main magnetic path, the total magnetic voltage is 
- 
-\[ 
-\begin{align*} 
-\Theta 
-= 
-N_1\underline{I}_1 
-+ 
-N_2\underline{I}_2. 
-\end{align*} 
-\] 
- 
-The main flux is 
- 
-\[ 
-\begin{align*} 
-\underline{\Phi} 
-= 
-\frac{\Theta}{R_{\rm mH}} 
-= 
-\frac{N_1\underline{I}_1+N_2\underline{I}_2}{R_{\rm mH}}. 
-\end{align*} 
-\] 
- 
-The flux linkages are 
- 
-\[ 
-\begin{align*} 
-\underline{\Psi}_1 
-&= 
-N_1\underline{\Phi} 
-= 
-{\color{green}{\frac{N_1^2}{R_{\rm mH}}\underline{I}_1}} 
-+ 
-{\color{blue}{\frac{N_1N_2}{R_{\rm mH}}\underline{I}_2}}, 
-\\[4pt] 
-\underline{\Psi}_2 
-&= 
-N_2\underline{\Phi} 
-= 
-{\color{blue}{\frac{N_1N_2}{R_{\rm mH}}\underline{I}_1}} 
-+ 
-{\color{green}{\frac{N_2^2}{R_{\rm mH}}\underline{I}_2}}. 
-\end{align*} 
-\] 
- 
-Therefore 
- 
-\[ 
-\begin{align*} 
-\boxed{ 
-{\color{green}{L_{1{\rm H}}=\frac{N_1^2}{R_{\rm mH}}}} 
-} 
-\qquad 
-\boxed{ 
-{\color{green}{L_{2{\rm H}}=\frac{N_2^2}{R_{\rm mH}}}} 
-} 
-\qquad 
-\boxed{ 
-{\color{blue}{M=\frac{N_1N_2}{R_{\rm mH}}}} 
-} 
-\end{align*} 
-\] 
- 
-for an ideal common magnetic path. 
- 
-<callout type="info" icon="true"> 
-**Unit check for mutual inductance** 
- 
-\[ 
-\begin{align*} 
-M=\frac{N_1N_2}{R_{\rm mH}} 
-\end{align*} 
-\] 
- 
-with 
- 
-\[ 
-\begin{align*} 
-[R_{\rm mH}] 
-= 
-\frac{{\rm A}}{{\rm Vs}} 
-= 
-\frac{1}{{\rm H}}. 
-\end{align*} 
-\] 
- 
-Thus 
- 
-\[ 
-\begin{align*} 
-[M]=\frac{1}{1/{\rm H}}={\rm H}. 
-\end{align*} 
-\] 
-</callout> 
- 
-<panel type="info" title="Example: why iron cores improve coupling"> 
-Air has a high magnetic reluctance. Iron has a much lower magnetic reluctance. 
- 
-If the magnetic path has a lower reluctance \(R_{\rm mH}\), then 
- 
-\[ 
-\begin{align*} 
-M=\frac{N_1N_2}{R_{\rm mH}} 
-\end{align*} 
-\] 
- 
-becomes larger.   
-A larger \(M\) means that a changing current in one winding induces a stronger voltage in the other winding. 
-</panel> 
- 
-==== Ideal single-phase transformer ==== 
- 
-For an ideal transformer we assume: 
- 
-  * both windings are linked by the same magnetic flux \(\Phi\), 
-  * there is no leakage flux, 
-  * there are no winding resistances, 
-  * there are no iron losses, 
-  * the transformer stores no net energy over one period. 
- 
-Let \(N_1\) be the number of turns of the primary winding and \(N_2\) the number of turns of the secondary winding. 
- 
-\[ 
-\begin{align*} 
-\underline{\Psi}_1 &= N_1\underline{\Phi}, 
-& 
-\underline{U}_1 &= j\omega\underline{\Psi}_1 
-= j\omega N_1\underline{\Phi}, 
-\\ 
-\underline{\Psi}_2 &= N_2\underline{\Phi}, 
-& 
-\underline{U}_2 &= j\omega\underline{\Psi}_2 
-= j\omega N_2\underline{\Phi}. 
-\end{align*} 
-\] 
- 
-Dividing the two voltage equations gives the **turns ratio** 
- 
-\[ 
-\begin{align*} 
-\boxed{ 
-\frac{\underline{U}_1}{\underline{U}_2} 
-= 
-\frac{N_1}{N_2} 
-= 
-n 
-} 
-\end{align*} 
-\] 
- 
-with 
- 
-\[ 
-\begin{align*} 
-n=\frac{N_1}{N_2}. 
-\end{align*} 
-\] 
- 
-<WRAP column 100%> 
-<panel type="danger" title="Remember: ideal transformer ratios"> 
-With the indicated reference arrows and a lossless transformer: 
- 
-\[ 
-\begin{align*} 
-\underline{U}_1\underline{I}_1+\underline{U}_2\underline{I}_2=0 
-\end{align*} 
-\] 
- 
-and therefore 
- 
-\[ 
-\begin{align*} 
-\boxed{ 
-\frac{\underline{I}_1}{\underline{I}_2} 
-= 
--\frac{\underline{U}_2}{\underline{U}_1} 
-= 
--\frac{N_2}{N_1} 
-= 
--\frac{1}{n} 
-} 
-\end{align*} 
-\] 
- 
-The minus sign is not a “loss”. It is caused by the chosen current arrows. The primary side absorbs power while the secondary side delivers power to the load. 
-</panel> 
-</WRAP> 
- 
-<panel type="info" title="Analogy: gearbox for voltage and current"> 
-An ideal transformer behaves like a lossless gearbox: 
- 
-  * a gearbox can trade speed for torque, 
-  * a transformer can trade voltage for current. 
- 
-For a step-down transformer: 
- 
-\[ 
-\begin{align*} 
-\text{lower voltage} \quad \Longleftrightarrow \quad \text{higher current}. 
-\end{align*} 
-\] 
- 
-The power is ideally conserved, just as mechanical power is ideally conserved in a lossless gearbox. 
-</panel> 
- 
-<panel type="info" title="Physical interpretation"> 
-  * If \(N_2<N_1\), the transformer steps the voltage down: \(U_2<U_1\). 
-  * At the same time, the secondary current can be higher: \(I_2>I_1\). 
-  * This is useful in robotics power supplies: a mains-side transformer or isolated converter stage may reduce voltage while increasing available current for actuators. 
-</panel> 
- 
-==== Example: step-down transformer for a robot controller ==== 
- 
-A transformer has \(N_1=800\) turns and \(N_2=80\) turns.   
-The primary RMS voltage is \(U_1=230~{\rm V}\). 
- 
-\[ 
-\begin{align*} 
-n &= \frac{N_1}{N_2} 
-= \frac{800}{80} 
-=10, 
-\\ 
-U_2 &= \frac{U_1}{n} 
-= \frac{230~{\rm V}}{10} 
-=23~{\rm V}. 
-\end{align*} 
-\] 
- 
-If the secondary side supplies \(I_2=4~{\rm A}\), the ideal primary current magnitude is 
- 
-\[ 
-\begin{align*} 
-I_1 &= \frac{I_2}{n} 
-= \frac{4~{\rm A}}{10} 
-=0.4~{\rm A}. 
-\end{align*} 
-\] 
- 
-The apparent power is equal on both sides: 
- 
-\[ 
-\begin{align*} 
-S_1 &= U_1I_1=230~{\rm V}\cdot 0.4~{\rm A}=92~{\rm VA}, 
-\\ 
-S_2 &= U_2I_2=23~{\rm V}\cdot 4~{\rm A}=92~{\rm VA}. 
-\end{align*} 
-\] 
- 
-~~PAGEBREAK~~ ~~CLEARFIX~~ 
- 
-==== Real transformer: leakage and losses ==== 
- 
-In a real transformer, not all flux links both windings. 
- 
-  * The **main flux** \(\Phi_{\rm H}\) links primary and secondary winding. 
-  * The **primary leakage flux** \(\Phi_{1\sigma}\) mainly links only the primary winding. 
-  * The **secondary leakage flux** \(\Phi_{2\sigma}\) mainly links only the secondary winding. 
- 
-<WRAP> 
-<panel type="default"> 
-<imgcaption fig_main_and_leakage_flux|Main flux and leakage fluxes in a real transformer.></imgcaption> 
-{{drawio>block09_main_and_leakage_flux.svg}} 
-</panel> 
-</WRAP> 
- 
-The real flux linkage equations become 
- 
-\[ 
-\begin{align*} 
-\underline{\Psi}_1 
-&= 
-\underbrace{{\color{blue}{L_{1{\rm H}}\underline{I}_1+M\underline{I}_2}}}_{\text{main magnetic path}} 
-+ 
-\underbrace{{\color{orange}{L_{1\sigma}\underline{I}_1}}}_{\text{primary leakage}}, 
-\\[4pt] 
-\underline{\Psi}_2 
-&= 
-\underbrace{{\color{blue}{L_{2{\rm H}}\underline{I}_2+M\underline{I}_1}}}_{\text{main magnetic path}} 
-+ 
-\underbrace{{\color{orange}{L_{2\sigma}\underline{I}_2}}}_{\text{secondary leakage}}. 
-\end{align*} 
-\] 
- 
-Equivalently, 
- 
-\[ 
-\begin{align*} 
-\underline{\Psi}_1 
-&= 
-L_1\underline{I}_1+M\underline{I}_2, 
-& 
-L_1&=L_{1{\rm H}}+L_{1\sigma}, 
-\\ 
-\underline{\Psi}_2 
-&= 
-L_2\underline{I}_2+M\underline{I}_1, 
-& 
-L_2&=L_{2{\rm H}}+L_{2\sigma}. 
-\end{align*} 
-\] 
- 
-The winding resistances \(R_1\) and \(R_2\) cause copper losses: 
- 
-\[ 
-\begin{align*} 
-P_{\rm Cu,1}=R_1I_1^2, 
-\qquad 
-P_{\rm Cu,2}=R_2I_2^2. 
-\end{align*} 
-\] 
- 
-<panel type="info" title="Color scheme for the equivalent equations"> 
-In the following formulas: 
- 
-  * blue terms: useful main magnetic coupling, 
-  * orange terms: leakage flux, 
-  * red terms: winding resistance and copper loss. 
-</panel> 
- 
-\[ 
-\begin{align*} 
-\underline{U}_1 
-&= 
-\underbrace{{\color{red}{R_1\underline{I}_1}}}_{\text{primary copper drop}} 
-+ 
-\underbrace{{\color{orange}{j\omega L_{1\sigma}\underline{I}_1}}}_{\text{primary leakage drop}} 
-+ 
-\underbrace{{\color{blue}{j\omega L_{1{\rm H}}\underline{I}_1+j\omega M\underline{I}_2}}}_{\text{main magnetic coupling}}, 
-\\[6pt] 
-\underline{U}_2 
-&= 
-\underbrace{{\color{red}{R_2\underline{I}_2}}}_{\text{secondary copper drop}} 
-+ 
-\underbrace{{\color{orange}{j\omega L_{2\sigma}\underline{I}_2}}}_{\text{secondary leakage drop}} 
-+ 
-\underbrace{{\color{blue}{j\omega L_{2{\rm H}}\underline{I}_2+j\omega M\underline{I}_1}}}_{\text{main magnetic coupling}}. 
-\end{align*} 
-\] 
- 
-<callout> 
-The blue terms are responsible for transformer action.   
-The orange terms are unwanted but unavoidable.   
-The red terms convert electrical energy into heat. 
-</callout> 
- 
-With the leakage reactances 
- 
-\[ 
-\begin{align*} 
-X_{1\sigma}=\omega L_{1\sigma}, 
-\qquad 
-X_{2\sigma}=\omega L_{2\sigma}, 
-\qquad 
-X_{\rm M}=\omega M 
-\end{align*} 
-\] 
- 
-these equations can be represented by an equivalent circuit. 
- 
-<callout type="info" icon="true"> 
-**Unit check for leakage reactance** 
- 
-\[ 
-\begin{align*} 
-X_{1\sigma}=\omega L_{1\sigma} 
-\end{align*} 
-\] 
- 
-with 
- 
-\[ 
-\begin{align*} 
-[\omega L]={\rm s}^{-1}\cdot{\rm H} 
-= 
-{\rm s}^{-1}\cdot \frac{{\rm V\,s}}{{\rm A}} 
-= 
-\Omega . 
-\end{align*} 
-\] 
- 
-So \(jX_{1\sigma}\) is an impedance. 
-</callout> 
- 
-==== Why leakage flux matters in engineering ==== 
- 
-<panel type="info" title="Mechatronics example: motor start-up"> 
-A robot axis may draw a high current during acceleration.   
-This high current produces a voltage drop at the leakage reactance and winding resistance of the transformer. 
- 
-Possible effects: 
- 
-  * the secondary voltage decreases, 
-  * a DC link after a rectifier may sag, 
-  * controllers may reset due to undervoltage, 
-  * cables and protective devices must withstand the fault current. 
- 
-So leakage is not only a “field theory detail”. It directly affects the electrical behavior of the machine. 
-</panel> 
- 
-<panel type="info" title="Analogy: useful road and side roads"> 
-Think of the main flux as traffic on the useful road between two cities.   
-Traffic on side roads still exists, but it does not help transport goods between the two cities. 
- 
-  * main flux: useful road between primary and secondary winding, 
-  * leakage flux: side roads that return locally, 
-  * winding resistance: friction that turns useful energy into heat. 
-</panel> 
- 
-~~PAGEBREAK~~ ~~CLEARFIX~~ 
- 
-==== Reduced equivalent circuit referred to the primary side ==== 
- 
-For calculations it is convenient to move all secondary-side quantities to the primary side. This is called **referring** or **transforming** the secondary side to the primary side. 
- 
-\[ 
-\begin{align*} 
-\boxed{ 
-\underline{U}'_2=n\underline{U}_2 
-} 
-\qquad 
-\boxed{ 
-\underline{I}'_2=\frac{1}{n}\underline{I}_2 
-} 
-\end{align*} 
-\] 
- 
-The secondary resistance and leakage reactance are transformed by \(n^2\): 
- 
-\[ 
-\begin{align*} 
-\boxed{ 
-R'_2=n^2R_2 
-} 
-\qquad 
-\boxed{ 
-X'_{2\sigma}=n^2X_{2\sigma} 
-} 
-\end{align*} 
-\] 
- 
-<callout type="info" icon="true"> 
-**Unit check for referred resistance** 
- 
-The turns ratio \(n\) is dimensionless. Therefore 
- 
-\[ 
-\begin{align*} 
-[R'_2]=[n^2R_2]=\Omega . 
-\end{align*} 
-\] 
- 
-The value changes, but the unit does not. 
-</callout> 
- 
-<WRAP> 
-<panel type="default"> 
-<imgcaption fig_reduced_equivalent_circuit|Reduced transformer equivalent circuit with secondary quantities referred to the primary side.></imgcaption> 
-{{drawio>block09_reduced_transformer_equivalent_circuit.svg}} 
-</panel> 
-</WRAP> 
- 
-In the reduced equivalent circuit: 
- 
-  * \(R_1\) and \(R'_2\) model copper losses. 
-  * \(jX_{1\sigma}\) and \(jX'_{2\sigma}\) model leakage flux. 
-  * \(jX_{1{\rm H}}\) models the magnetizing branch. 
-  * \(R_{\rm Fe}\) is placed parallel to \(jX_{1{\rm H}}\) to model iron losses. 
- 
-<panel type="info" title="Why the reduced circuit is useful"> 
-Once all quantities are referred to one side, the transformer can be calculated like an AC network with impedances.   
-This uses the same method as [[block04|complex network calculation]]: replace components by impedances and apply Kirchhoff's laws. 
-</panel> 
- 
-==== No-load operation of the real transformer ==== 
- 
-No-load operation means that the secondary side is open: 
- 
-\[ 
-\begin{align*} 
-\underline{I}_2=0. 
-\end{align*} 
-\] 
- 
-The primary side still draws a small no-load current \(\underline{I}_{10}\). This current has two parts: 
- 
-\[ 
-\begin{align*} 
-\underline{I}_{10} 
-= 
-\underline{I}_{\rm Fe} 
-+ 
-\underline{I}_{\rm m}. 
-\end{align*} 
-\] 
- 
-  * \(\underline{I}_{\rm Fe}\): current through \(R_{\rm Fe}\), in phase with voltage, represents iron losses. 
-  * \(\underline{I}_{\rm m}\): magnetizing current through \(jX_{1{\rm H}}\), approximately \(90^\circ\) lagging. 
- 
-<WRAP> 
-<panel type="default"> 
-<imgcaption fig_no_load_phasor|No-load phasor diagram: the no-load current is the sum of iron-loss current and magnetizing current.></imgcaption> 
-{{drawio>block09_no_load_phasor_diagram.svg}} 
-</panel> 
-</WRAP> 
- 
-The technical voltage ratio is often defined from the no-load voltages. Here it is denoted by \(\ddot{u}\): 
- 
-\[ 
-\begin{align*} 
-\ddot{u} 
-= 
-\frac{\text{higher voltage}}{\text{lower voltage}} 
-\bigg|_{\rm no~load}. 
-\end{align*} 
-\] 
- 
-For a step-down transformer: 
- 
-\[ 
-\begin{align*} 
-\ddot{u} 
-= 
-\frac{U_{1{\rm N}}}{U_{20}}. 
-\end{align*} 
-\] 
- 
-Here \(U_{1{\rm N}}\) is the rated primary voltage and \(U_{20}\) is the open-circuit secondary voltage. 
- 
-<callout> 
-Because of real voltage drops and magnetizing effects, 
- 
-\[ 
-\begin{align*} 
-\ddot{u}\neq n, 
-\end{align*} 
-\] 
- 
-but for many practical transformers 
- 
-\[ 
-\begin{align*} 
-\ddot{u}\approx n. 
-\end{align*} 
-\] 
-</callout> 
- 
-==== Short-circuit operation of the real transformer ==== 
- 
-In the short-circuit test, the secondary side is shorted: 
- 
-\[ 
-\begin{align*} 
-\underline{U}_2=0. 
-\end{align*} 
-\] 
- 
-Because the required primary voltage is small, the magnetizing branch is often neglected: 
- 
-\[ 
-\begin{align*} 
-X_{1{\rm H}},\;R_{\rm Fe} 
-\gg 
-X'_{2\sigma},\;R'_2. 
-\end{align*} 
-\] 
- 
-This gives the short-circuit equivalent circuit with 
- 
-\[ 
-\begin{align*} 
-\boxed{ 
-R_{\rm k}=R_1+R'_2 
-} 
-\qquad 
-\boxed{ 
-X_{\rm k}=X_{1\sigma}+X'_{2\sigma} 
-} 
-\end{align*} 
-\] 
- 
-and 
- 
-\[ 
-\begin{align*} 
-\underline{Z}_{\rm k} 
-= 
-R_{\rm k}+jX_{\rm k}. 
-\end{align*} 
-\] 
- 
-<WRAP> 
-<panel type="default"> 
-<imgcaption fig_short_circuit_equivalent|Short-circuit equivalent circuit of a real transformer.></imgcaption> 
-{{drawio>block09_short_circuit_equivalent_circuit.svg}} 
-</panel> 
-</WRAP> 
- 
-<panel type="info" title="Definition: rated short-circuit voltage"> 
-The **rated short-circuit voltage** \(U_{1{\rm k}}\) is the primary voltage that must be applied while the secondary side is shorted so that rated primary current \(I_{1{\rm N}}\) flows. 
- 
-As a relative value: 
- 
-\[ 
-\begin{align*} 
-\boxed{ 
-u_{\rm k} 
-= 
-\frac{U_{1{\rm k}}}{U_{1{\rm N}}}\cdot 100~\% 
-} 
-\end{align*} 
-\] 
- 
-Small \(u_{\rm k}\) means: small internal impedance and high possible fault current.   
-Large \(u_{\rm k}\) means: stronger current limitation and larger voltage drop under load. 
-</panel> 
- 
-The continuous short-circuit current for rated primary voltage is 
- 
-\[ 
-\begin{align*} 
-\boxed{ 
-I_{1{\rm k}} 
-= 
-\frac{U_{1{\rm N}}}{U_{1{\rm k}}}\cdot I_{1{\rm N}} 
-= 
-I_{1{\rm N}}\cdot \frac{100~\%}{u_{\rm k}} 
-} 
-\end{align*} 
-\] 
- 
-where \(u_{\rm k}\) is inserted as a percentage value. 
- 
-<callout type="info" icon="true"> 
-**Unit check for \(u_{\rm k}\)** 
- 
-\[ 
-\begin{align*} 
-u_{\rm k} 
-= 
-\frac{U_{1{\rm k}}}{U_{1{\rm N}}}\cdot 100~\% 
-\end{align*} 
-\] 
- 
-is dimensionless. It is usually stated in percent. 
-</callout> 
- 
-==== Why the first short-circuit peak can be about \(2.54 I_{1{\rm k}}\) ==== 
- 
-The RMS short-circuit current \(I_{1{\rm k}}\) does not describe the highest instantaneous current. 
- 
-When a short circuit starts, the current can contain 
- 
-  * a sinusoidal AC component, and 
-  * a decaying DC offset. 
- 
-The worst case occurs when the fault starts at an unfavorable phase angle. Then the first current peak is larger than the normal sinusoidal peak \(\sqrt{2}I_{1{\rm k}}\). 
- 
-A common engineering form is 
- 
-\[ 
-\begin{align*} 
-i_{\rm p} 
-= 
-\kappa\sqrt{2}\,I''_{\rm k}. 
-\end{align*} 
-\] 
- 
-Here 
- 
-  * \(i_{\rm p}\) is the instantaneous peak short-circuit current, 
-  * \(I''_{\rm k}\) is the initial symmetrical RMS short-circuit current, 
-  * \(\kappa\) is a peak factor depending mainly on the \(R/X\) ratio of the short-circuit impedance. 
- 
-For a strongly inductive transformer short circuit, a practical approximation is 
- 
-\[ 
-\begin{align*} 
-\kappa\approx 1.8. 
-\end{align*} 
-\] 
- 
-Then 
- 
-\[ 
-\begin{align*} 
-i_{\rm p} 
-\approx 
-1.8\cdot\sqrt{2}\cdot I_{1{\rm k}} 
-= 
-2.55\,I_{1{\rm k}} 
-\approx 
-2.54\,I_{1{\rm k}}. 
-\end{align*} 
-\] 
- 
-<WRAP column 100%> 
-<panel type="danger" title="Do not overinterpret the factor 2.54"> 
-The factor \(2.54\) is an engineering approximation for the first peak current.   
-It is **not** a universal transformer law. 
- 
-For real protection design, use the applicable standard, manufacturer data, and the actual \(R/X\) ratio of the installation. 
-</panel> 
-</WRAP> 
- 
-~~PAGEBREAK~~ ~~CLEARFIX~~ 
- 
-==== Real transformer under load ==== 
- 
-Under load, the short-circuit equivalent circuit is often sufficient for engineering estimates. 
- 
-\[ 
-\begin{align*} 
-\underline{U}_{\rm k} 
-= 
-\left(R_{\rm k}+jX_{\rm k}\right)\underline{I}_1. 
-\end{align*} 
-\] 
- 
-This voltage drop is subtracted vectorially from the primary-side voltage relation. Therefore the secondary voltage depends on 
- 
-  * load current magnitude, 
-  * load power factor, 
-  * winding resistance, 
-  * leakage reactance. 
- 
-<WRAP> 
-<panel type="default"> 
-<imgcaption fig_kapp_triangle|Kapp triangle: approximate voltage drop under load using \(R_{\rm k}I\) and \(X_{\rm k}I\).></imgcaption> 
-{{drawio>block09_kapp_triangle.svg}} 
-</panel> 
-</WRAP> 
- 
-<panel type="info" title="Engineering use: voltage regulation"> 
-In a robot with motors, the supply transformer may show a lower output voltage during high acceleration because the motor currents increase.   
-The Kapp triangle helps estimate this voltage drop. This is important for: 
- 
-  * selecting transformer size, 
-  * checking whether the DC link after a rectifier remains high enough, 
-  * designing fuses and protective devices, 
-  * avoiding undervoltage resets in control electronics. 
-</panel> 
- 
-==== Construction types and cooling ==== 
- 
-Transformer behavior is influenced by construction. 
- 
-<WRAP group> 
-<WRAP column half> 
-<panel type="default"> 
-<imgcaption fig_core_transformer|Core-type transformer: usually smaller short-circuit voltage \(u_{\rm k}\).></imgcaption> 
-{{drawio>block09_core_type_transformer.svg}} 
-</panel> 
-</WRAP> 
- 
-<WRAP column half> 
-<panel type="default"> 
-<imgcaption fig_shell_transformer|Shell-type transformer: usually larger short-circuit voltage \(u_{\rm k}\).></imgcaption> 
-{{drawio>block09_shell_type_transformer.svg}} 
-</panel> 
-</WRAP> 
-</WRAP> 
- 
-Cooling types: 
- 
-  * **Dry-type transformer:** air cooling, often used inside machines or buildings at lower and medium power. 
-  * **Oil transformer:** oil provides insulation and heat transfer, typical for higher power. 
- 
-<panel type="info" title="Mechatronics examples"> 
-  * **Isolating transformer:** safe diagnostic supply for laboratory setups. 
-  * **Control transformer:** supplies \(24~{\rm V}\) or similar low-voltage control circuits. 
-  * **Current transformer:** measures large motor currents with galvanic isolation. 
-  * **Welding transformer:** intentionally high short-circuit voltage and current limitation for welding processes. 
-</panel> 
- 
-==== Typical technical transformer data ==== 
- 
-<tabcaption tab_transformer_types|Typical transformer types, short-circuit voltage, and secondary voltage> 
- 
-^ Name / use ^ Typical \(u_{\rm k}\) ^ Secondary voltage \(U_2\) ^ Important note ^ 
-| Power transformer | \(4\ldots 12~\%\) | application-dependent | low voltage drop, high fault currents possible | 
-| Isolating transformer | \(\approx 10~\%\) | max. \(250~{\rm V}\) | galvanic isolation for safety and measurement | 
-| Toy transformer | \(\approx 20~\%\) | max. \(24~{\rm V}\) | current limitation is desired | 
-| Doorbell transformer | \(\approx 40~\%\) | max. \(12~{\rm V}\), often several taps | simple robust low-voltage supply | 
-| Ignition transformer | \(\approx 100~\%\) | \(\leq 14~{\rm kV}\) | high voltage, limited current | 
-| Welding transformer | \(\approx 100~\%\) | max. \(70~{\rm V}\) | large current, strong current limitation | 
-| Voltage transformer | \(<1~\%\) | \(100~{\rm V}\) | operate with high load resistance, approximately no-load | 
-| Current transformer | \(100~\%\) | \(0~{\rm V}\) ideal secondary voltage | operate with low burden, approximately short-circuit | 
- 
-<WRAP column 100%> 
-<panel type="danger" title="Important safety note: current transformers"> 
-A current transformer secondary must not be opened while primary current flows.   
-If the secondary circuit is open, the transformer tries to maintain the magnetic balance and can generate dangerous high voltages. 
-</panel> 
-</WRAP> 
- 
-===== Exercises ===== 
- 
-#@TaskTitle_HTML@##@Lvl_HTML@#~~#@ee2_taskctr#~~.1  Quick check: ideal transformer voltage and current ratio 
-#@TaskText_HTML@# 
- 
-A transformer has \(N_1=1200\) turns and \(N_2=300\) turns.   
-The primary RMS voltage is \(U_1=230~{\rm V}\).   
-The secondary side supplies a load current \(I_2=2.0~{\rm A}\). 
- 
-  * Calculate the turns ratio \(n\). 
-  * Calculate the ideal secondary voltage \(U_2\). 
-  * Calculate the magnitude of the ideal primary current \(I_1\). 
-  * State whether this is a step-up or step-down transformer. 
- 
-#@ResultBegin_HTML~Exercise1~@# 
- 
-\[ 
-\begin{align*} 
-n=\frac{N_1}{N_2} 
-= 
-\frac{1200}{300} 
-= 
-4. 
-\end{align*} 
-\] 
- 
-The secondary voltage is 
- 
-\[ 
-\begin{align*} 
-U_2 
-= 
-\frac{U_1}{n} 
-= 
-\frac{230~{\rm V}}{4} 
-= 
-57.5~{\rm V}. 
-\end{align*} 
-\] 
- 
-The primary current magnitude is 
- 
-\[ 
-\begin{align*} 
-I_1 
-= 
-\frac{I_2}{n} 
-= 
-\frac{2.0~{\rm A}}{4} 
-= 
-0.50~{\rm A}. 
-\end{align*} 
-\] 
- 
-Because \(U_2<U_1\), it is a step-down transformer. 
- 
-#@ResultEnd_HTML@# 
-#@TaskEnd_HTML@# 
- 
-#@TaskTitle_HTML@##@Lvl_HTML@#~~#@ee2_taskctr#~~.1  Quick check: mutual inductance from reluctance 
-#@TaskText_HTML@# 
- 
-Two coils are wound on the same ideal magnetic core.   
-The main magnetic reluctance is 
- 
-\[ 
-\begin{align*} 
-R_{\rm mH}=2.0\cdot 10^6~\frac{1}{\rm H}. 
-\end{align*} 
-\] 
- 
-The number of turns is \(N_1=500\) and \(N_2=100\). 
- 
-  * Calculate \(L_{1{\rm H}}\). 
-  * Calculate \(L_{2{\rm H}}\). 
-  * Calculate \(M\). 
-  * Check whether the units are correct. 
- 
-#@ResultBegin_HTML~Exercise2~@# 
- 
-\[ 
-\begin{align*} 
-L_{1{\rm H}} 
-= 
-\frac{N_1^2}{R_{\rm mH}} 
-= 
-\frac{500^2}{2.0\cdot 10^6~1/{\rm H}} 
-= 
-0.125~{\rm H}. 
-\end{align*} 
-\] 
- 
-\[ 
-\begin{align*} 
-L_{2{\rm H}} 
-= 
-\frac{N_2^2}{R_{\rm mH}} 
-= 
-\frac{100^2}{2.0\cdot 10^6~1/{\rm H}} 
-= 
-0.0050~{\rm H} 
-= 
-5.0~{\rm mH}. 
-\end{align*} 
-\] 
- 
-\[ 
-\begin{align*} 
-M 
-= 
-\frac{N_1N_2}{R_{\rm mH}} 
-= 
-\frac{500\cdot 100}{2.0\cdot 10^6~1/{\rm H}} 
-= 
-0.025~{\rm H} 
-= 
-25~{\rm mH}. 
-\end{align*} 
-\] 
- 
-The unit is correct because \(1/(1/{\rm H})={\rm H}\). 
- 
-#@ResultEnd_HTML@# 
-#@TaskEnd_HTML@# 
- 
-#@TaskTitle_HTML@##@Lvl_HTML@#~~#@ee2_taskctr#~~.1  Quick check: referring secondary quantities to the primary side 
-#@TaskText_HTML@# 
- 
-A transformer has \(n=5\).   
-The secondary winding resistance is \(R_2=0.20~\Omega\) and the secondary leakage reactance is \(X_{2\sigma}=0.35~\Omega\). 
- 
-Calculate the values \(R'_2\) and \(X'_{2\sigma}\) referred to the primary side. 
- 
-#@ResultBegin_HTML~Exercise3~@# 
- 
-\[ 
-\begin{align*} 
-R'_2 
-= 
-n^2R_2 
-= 
-5^2\cdot 0.20~\Omega 
-= 
-25\cdot 0.20~\Omega 
-= 
-5.0~\Omega. 
-\end{align*} 
-\] 
- 
-\[ 
-\begin{align*} 
-X'_{2\sigma} 
-= 
-n^2X_{2\sigma} 
-= 
-5^2\cdot 0.35~\Omega 
-= 
-25\cdot 0.35~\Omega 
-= 
-8.75~\Omega. 
-\end{align*} 
-\] 
- 
-The unit remains \(\Omega\), because \(n\) is dimensionless. 
- 
-#@ResultEnd_HTML@# 
-#@TaskEnd_HTML@# 
- 
-#@TaskTitle_HTML@##@Lvl_HTML@#~~#@ee2_taskctr#~~.1  Quick check: short-circuit voltage and fault current 
-#@TaskText_HTML@# 
- 
-A transformer has a rated primary current \(I_{1{\rm N}}=10~{\rm A}\) and a short-circuit voltage \(u_{\rm k}=5~\%\). 
- 
-  * Calculate the continuous short-circuit current \(I_{1{\rm k}}\) when rated primary voltage is applied. 
-  * Estimate the initial peak short-circuit current \(i_{\rm p}\) using \(i_{\rm p}\approx 2.54 I_{1{\rm k}}\). 
- 
-#@ResultBegin_HTML~Exercise4~@# 
- 
-\[ 
-\begin{align*} 
-I_{1{\rm k}} 
-= 
-I_{1{\rm N}}\cdot \frac{100~\%}{u_{\rm k}} 
-= 
-10~{\rm A}\cdot \frac{100~\%}{5~\%} 
-= 
-200~{\rm A}. 
-\end{align*} 
-\] 
- 
-\[ 
-\begin{align*} 
-i_{\rm p} 
-\approx 
-2.54\cdot I_{1{\rm k}} 
-= 
-2.54\cdot 200~{\rm A} 
-= 
-508~{\rm A}. 
-\end{align*} 
-\] 
- 
-The short-circuit current is much larger than the rated current. Protection devices must be selected accordingly. 
- 
-#@ResultEnd_HTML@# 
-#@TaskEnd_HTML@# 
- 
-#@TaskTitle_HTML@##@Lvl_HTML@#~~#@ee2_taskctr#~~.1  Longer exercise: transformer equivalent circuit for an actuator supply 
-#@TaskText_HTML@# 
- 
-A single-phase transformer supplies an actuator driver.   
-Rated data and equivalent circuit data are: 
- 
-\[ 
-\begin{align*} 
-U_{1{\rm N}}&=230~{\rm V}, 
-& 
-U_{2{\rm N}}&=23~{\rm V}, 
-& 
-I_{2{\rm N}}&=5.0~{\rm A}, 
-\\ 
-R_1&=1.2~\Omega, 
-& 
-X_{1\sigma}&=1.8~\Omega, 
-\\ 
-R_2&=0.012~\Omega, 
-& 
-X_{2\sigma}&=0.018~\Omega. 
-\end{align*} 
-\] 
- 
-Assume \(n=\frac{U_{1{\rm N}}}{U_{2{\rm N}}}\). The magnetizing branch is neglected for the loaded operating point. 
- 
-  * Calculate \(n\). 
-  * Refer \(R_2\) and \(X_{2\sigma}\) to the primary side. 
-  * Calculate \(R_{\rm k}\) and \(X_{\rm k}\). 
-  * Calculate the primary rated current magnitude \(I_{1{\rm N}}\) using the ideal current ratio. 
-  * Estimate the magnitude of the internal voltage drop \(U_{\rm k}\approx |\underline{Z}_{\rm k}|I_{1{\rm N}}\). 
- 
-#@ResultBegin_HTML~Exercise5~@# 
- 
-The turns ratio is 
- 
-\[ 
-\begin{align*} 
-n 
-= 
-\frac{U_{1{\rm N}}}{U_{2{\rm N}}} 
-= 
-\frac{230~{\rm V}}{23~{\rm V}} 
-= 
-10. 
-\end{align*} 
-\] 
- 
-The secondary quantities referred to the primary side are 
- 
-\[ 
-\begin{align*} 
-R'_2 
-&= 
-n^2R_2 
-= 
-10^2\cdot 0.012~\Omega 
-= 
-1.2~\Omega, 
-\\ 
-X'_{2\sigma} 
-&= 
-n^2X_{2\sigma} 
-= 
-10^2\cdot 0.018~\Omega 
-= 
-1.8~\Omega. 
-\end{align*} 
-\] 
- 
-Therefore 
- 
-\[ 
-\begin{align*} 
-R_{\rm k} 
-&= 
-R_1+R'_2 
-= 
-1.2~\Omega+1.2~\Omega 
-= 
-2.4~\Omega, 
-\\ 
-X_{\rm k} 
-&= 
-X_{1\sigma}+X'_{2\sigma} 
-= 
-1.8~\Omega+1.8~\Omega 
-= 
-3.6~\Omega. 
-\end{align*} 
-\] 
- 
-The primary current magnitude is 
- 
-\[ 
-\begin{align*} 
-I_{1{\rm N}} 
-= 
-\frac{I_{2{\rm N}}}{n} 
-= 
-\frac{5.0~{\rm A}}{10} 
-= 
-0.50~{\rm A}. 
-\end{align*} 
-\] 
- 
-The magnitude of the short-circuit impedance is 
- 
-\[ 
-\begin{align*} 
-|\underline{Z}_{\rm k}| 
-= 
-\sqrt{R_{\rm k}^2+X_{\rm k}^2} 
-= 
-\sqrt{(2.4~\Omega)^2+(3.6~\Omega)^2} 
-= 
-4.33~\Omega. 
-\end{align*} 
-\] 
- 
-Thus the internal voltage drop estimate is 
- 
-\[ 
-\begin{align*} 
-U_{\rm k} 
-\approx 
-|\underline{Z}_{\rm k}|I_{1{\rm N}} 
-= 
-4.33~\Omega\cdot 0.50~{\rm A} 
-= 
-2.17~{\rm V}. 
-\end{align*} 
-\] 
- 
-This is a primary-side voltage drop. On the secondary side it corresponds approximately to 
- 
-\[ 
-\begin{align*} 
-\frac{2.17~{\rm V}}{10}=0.217~{\rm V}. 
-\end{align*} 
-\] 
- 
-For a \(23~{\rm V}\) actuator supply this is small but not zero. 
- 
-#@ResultEnd_HTML@# 
-#@TaskEnd_HTML@# 
- 
-===== Common pitfalls ===== 
- 
-  * **Using a transformer with DC:** A transformer needs changing flux. With DC, after the switching transient, an ideal transformer no longer transfers voltage. A real transformer may overheat because the winding resistance limits the current only weakly. 
-  * **Forgetting the current ratio sign:** The minus sign in \(\frac{\underline{I}_1}{\underline{I}_2}=-\frac{1}{n}\) comes from reference arrows. Do not interpret it as negative power loss. 
-  * **Mixing peak values and RMS values:** In AC power and transformer ratings, \(U\) and \(I\) usually mean RMS values. Time functions are written \(u(t)\), \(i(t)\). Instantaneous short-circuit peaks are written here as \(i_{\rm p}\). 
-  * **Confusing reluctance and resistance:** Magnetic reluctance \(R_{\rm m}\) has the unit \(1/{\rm H}\), not \(\Omega\). 
-  * **Confusing \(n\) and the technical no-load voltage ratio \(\ddot{u}\):** The ideal ratio is \(n=\frac{N_1}{N_2}\). The measured no-load voltage ratio is close to \(n\), but not exactly equal for a real transformer. 
-  * **Forgetting the square when referring impedances:** Voltages transform with \(n\), currents with \(\frac{1}{n}\), but impedances transform with \(n^2\). 
-  * **Ignoring leakage reactance:** Leakage reactance is often the dominant part of short-circuit impedance. It strongly affects fault current and voltage drop. 
-  * **Treating \(u_{\rm k}\) as a voltage in volts:** \(u_{\rm k}\) is normally given in percent. Insert it consistently in formulas. 
-  * **Using \(2.54\) as a universal law:** The first short-circuit peak depends on the \(R/X\) ratio and on the switching instant. The factor \(2.54\) is an approximation. 
-  * **Opening a current transformer secondary:** This can create dangerous voltages. Current transformers are operated with a low burden, approximately as a short-circuit. 
-  * **Assuming ideal isolation at every frequency:** Real transformers have parasitic capacitances between windings. For high-frequency noise and EMC, the “isolated” sides can still be capacitively coupled. 
- 
-===== Embedded resources ===== 
- 
-<WRAP group> 
-<WRAP column half> 
-<panel type="info" title="PhET: Faraday's Law"> 
-Use this simulation to revisit the EEE1 idea that a changing magnetic flux induces voltage.   
-This is the physical basis of the transformer equations in this block. 
- 
-{{url>https://phet.colorado.edu/sims/html/faradays-law/latest/faradays-law_en.html 700,500 noborder}} 
-</panel> 
-</WRAP> 
- 
-<WRAP column half> 
-<panel type="info" title="Falstad / CircuitJS: transformer circuits"> 
-Use CircuitJS for qualitative experiments with coupled inductors and transformer circuits.   
-Suggested activity: search the example circuits for “transformer”, change the turns ratio, and observe voltage and current. 
- 
-{{url>https://www.falstad.com/circuit/circuitjs.html 700,500 noborder}} 
-</panel> 
-</WRAP> 
-</WRAP> 
- 
-<WRAP group> 
-<WRAP column half> 
-<panel type="info" title="Falstad / CircuitJS: coupled inductors"> 
-Suggested experiment: 
- 
-  * build two coupled inductors, 
-  * change the coupling coefficient, 
-  * observe how the secondary voltage changes. 
- 
-This is especially useful for understanding the difference between an iron-core transformer and loosely coupled wireless charging coils. 
-</panel> 
-</WRAP> 
- 
-<WRAP column half> 
-<panel type="info" title="Further reading in this wiki"> 
-Relevant continuity pages: 
- 
-  * [[:electrical_engineering_1:block18|EEE1: Induction]] 
-  * [[:electrical_engineering_1:block19|EEE1: Magnetic circuits]] 
-  * [[:electrical_engineering_1:block20|EEE1: Inductance]] 
-  * [[:electrical_engineering_2:magnetic_circuits#mutual_induction_and_coupling|Mutual Induction and Coupling]] 
-</panel> 
-</WRAP> 
-</WRAP> 
- 
-~~PAGEBREAK~~ ~~CLEARFIX~~