Zeile 864: | Zeile 864: | ||
The power supply line to a consumer has to be replaced. Due to the application, | The power supply line to a consumer has to be replaced. Due to the application, | ||
- | * The old aluminium supply cable had a specific conductivity $\kappa_{Al}=33\cdot 10^6 ~{\rm {S}\over{m}}$ and a cross-section $A_{Al}=115~{\rm mm}^2$. | + | * The old aluminium supply cable had a specific conductivity $\kappa_{\rm Al}=33\cdot 10^6 ~{\rm {S}\over{m}}$ and a cross-section $A_{\rm Al}=115~{\rm mm}^2$. |
- | * The new copper supply cable has a specific conductivity $\kappa_{Cu}=56\cdot 10^6 ~{\rm {S}\over{m}}$ | + | * The new copper supply cable has a specific conductivity $\kappa_{\rm Cu}=56\cdot 10^6 ~{\rm {S}\over{m}}$ |
- | Which wire cross-section $A_{Cu}$ must be selected? | + | Which wire cross-section $A_{\rm Cu}$ must be selected? |
</ | </ | ||