Unterschiede
Hier werden die Unterschiede zwischen zwei Versionen angezeigt.
| Beide Seiten der vorigen Revision Vorhergehende Überarbeitung Nächste Überarbeitung | Vorhergehende Überarbeitung | ||
| electrical_engineering_2:polyphase_networks [2024/06/18 01:06] – mexleadmin | electrical_engineering_2:polyphase_networks [2025/06/24 00:40] (aktuell) – mexleadmin | ||
|---|---|---|---|
| Zeile 362: | Zeile 362: | ||
| ==== 7.2.2 Three-Phase System ==== | ==== 7.2.2 Three-Phase System ==== | ||
| - | See also: [[https:// | + | See also: __ BROKEN-LINK: |
| The most commonly used polyphase system is the three-phase system. The three-phase system has advantages over a DC system or single-phase AC system: | The most commonly used polyphase system is the three-phase system. The three-phase system has advantages over a DC system or single-phase AC system: | ||
| * Simple three-phase machines can be used for generation. | * Simple three-phase machines can be used for generation. | ||
| - | * Rotary field machines (e.g. synchronous | + | * Rotary field machines (e.g., synchronous or induction motors) can also be simply connected to a load, converting electrical energy into mechanical energy. |
| * When a symmetrical load can be assumed, the energy flow is constant in time. | * When a symmetrical load can be assumed, the energy flow is constant in time. | ||
| * For energy transport, the voltage can be up-transformed and thus the AC current, as well as the associated power loss (= waste heat), can be reduced. | * For energy transport, the voltage can be up-transformed and thus the AC current, as well as the associated power loss (= waste heat), can be reduced. | ||
| Zeile 383: | Zeile 383: | ||
| === Three-phase generator === | === Three-phase generator === | ||
| - | * The windings of a three-phase generator are called $\rm U$, $\rm V$, $\rm W$; the winding connections are correspondingly called: $\rm U1$, $\rm U2$, $\rm V1$, $\rm V2$, $\rm W1$, $\rm W2$ (see <imgref imageNo10> | + | * The windings of a three-phase generator are called $\rm U$, $\rm V$, $\rm W$. \\ Often they are also colour-coded as red, yellow and blue - and consecutively sometimes also called $\rm R$, $\rm Y$, $\rm B$. |
| + | * The winding connections are correspondingly called: $\rm U1$, $\rm U2$, $\rm V1$, $\rm V2$, $\rm W1$, $\rm W2$ (see <imgref imageNo10> | ||
| < | < | ||
| - | * The typical **winding connections** | + | * The typical **winding connections** |
| < | < | ||
| * The **phase voltages** | * The **phase voltages** | ||
| Zeile 540: | Zeile 541: | ||
| In the case of a symmetric load, the situation and the formulas get much simpler: | In the case of a symmetric load, the situation and the formulas get much simpler: | ||
| - | - The **phase-voltages** $U_\rm L$ and star-voltages $U_{\rm Y} = U_{\rm S}$ are equal to the asymmetric load: $U_{\rm L} = \sqrt{3}\cdot U_{\rm S}$. | + | - The **phase-voltages** $U_\rm L$ and star-voltages $U_{\rm Y} = U_{\rm S}$ are related by: $U_{\rm L} = \sqrt{3}\cdot U_{\rm S}$ (equal to the asymmetric load). |
| - For equal impedances the absolute value of all **phase currents** $I_x$ are the same: $|\underline{I}_x|= |\underline{I}_{\rm S}| = \left|{{\underline{U}_{\rm S}}\over{\underline{Z}_{\rm S}^\phantom{O}}} \right|$. \\ Since the phase currents have the same absolute value and have the same $\varphi$, they will add up to zero. Therefore there is no current on the neutral line: $I_{\rm N} =0$ | - For equal impedances the absolute value of all **phase currents** $I_x$ are the same: $|\underline{I}_x|= |\underline{I}_{\rm S}| = \left|{{\underline{U}_{\rm S}}\over{\underline{Z}_{\rm S}^\phantom{O}}} \right|$. \\ Since the phase currents have the same absolute value and have the same $\varphi$, they will add up to zero. Therefore there is no current on the neutral line: $I_{\rm N} =0$ | ||
| - The **true power** is three times the true power of a single phase: $P = 3 \cdot U_{\rm S} I_{\rm S} \cdot \cos \varphi$. \\ Based on the line voltages $U_{\rm L}$, the formula is $P = \sqrt{3} \cdot U_{\rm L} I_{\rm S} \cdot \cos \varphi$ | - The **true power** is three times the true power of a single phase: $P = 3 \cdot U_{\rm S} I_{\rm S} \cdot \cos \varphi$. \\ Based on the line voltages $U_{\rm L}$, the formula is $P = \sqrt{3} \cdot U_{\rm L} I_{\rm S} \cdot \cos \varphi$ | ||
| - The **(collective) apparent power** - given the formula above - is: $S_\Sigma = \sqrt{3}\cdot U_{\rm S} \cdot \sqrt{3\cdot I_{\rm S}^2} = 3 \cdot U_{\rm S} I_{\rm S}$. \\ This corresponds to three times the apparent power of a single phase. | - The **(collective) apparent power** - given the formula above - is: $S_\Sigma = \sqrt{3}\cdot U_{\rm S} \cdot \sqrt{3\cdot I_{\rm S}^2} = 3 \cdot U_{\rm S} I_{\rm S}$. \\ This corresponds to three times the apparent power of a single phase. | ||
| - | - The **reactive power** leads to: $Q_\Sigma = \sqrt{S_\Sigma^2 - P^2} = 3 \cdot U_{\rm S} I_{\rm S} \cdot \sin (\varphi)$. | + | - The **reactive power** leads to: $Q_\Sigma = \sqrt{S_\Sigma^2 - P^2} = 3 \cdot U_{\rm S} I_{\rm S} \cdot \sin \varphi$. |
| </ | </ | ||
| Zeile 851: | Zeile 852: | ||
| A passive component is fed by a sinusoidal AC voltage with the RMS value $U=230~\rm V$ and $f=50.0~\rm Hz$. The RMS current on this component is $I=5.00~\rm A$ with a phase angle of $\varphi=+60°$. | A passive component is fed by a sinusoidal AC voltage with the RMS value $U=230~\rm V$ and $f=50.0~\rm Hz$. The RMS current on this component is $I=5.00~\rm A$ with a phase angle of $\varphi=+60°$. | ||
| - | 1. Draw the equivalent circuits based on a series and on a parallel circuit. \\ | + | 1. Draw the equivalent circuits based on a series and a parallel circuit |
| # | # | ||
| Zeile 988: | Zeile 989: | ||
| A magnetic coil shows at a frequency of $f=50.0 {~\rm Hz}$ the voltage of $U=115{~\rm V}$ and the current $I=2.60{~\rm A}$ with a power factor of $\cos \varphi = 0.30$ | A magnetic coil shows at a frequency of $f=50.0 {~\rm Hz}$ the voltage of $U=115{~\rm V}$ and the current $I=2.60{~\rm A}$ with a power factor of $\cos \varphi = 0.30$ | ||
| - | - Calculate the real power, the reactive power, and the apparent power . | + | - Calculate the real power, the reactive power, and the apparent power. |
| - Draw the equivalent parallel circuit. Calculate the active and reactive part of the current. | - Draw the equivalent parallel circuit. Calculate the active and reactive part of the current. | ||
| - Draw the equivalent series circuit. Calculate the ohmic and inductive impedance and the value of the inductivity. | - Draw the equivalent series circuit. Calculate the ohmic and inductive impedance and the value of the inductivity. | ||
| Zeile 1255: | Zeile 1256: | ||
| </ | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | A three-phase motor is connected to an artificial three-phase system and can be configured in wye or delta configuration. | ||
| + | * The voltage measured on a single coil shall always be $230 ~\rm V$. | ||
| + | * The current measured on a single coil shall always be $10 ~\rm A$. | ||
| + | * The phase shift for every string is $25°$ | ||
| + | |||
| + | 1. The motor shall be in wye configuration. \\ | ||
| + | Write down the string voltage, phase voltage, string current, phase current, and active power | ||
| + | |||
| + | # | ||
| + | |||
| + | * The **string voltage** \( U_\rm s \) is always the voltage measured on a single coil ($230 ~\rm V$). | ||
| + | * The **string current** \( I_\rm s \) is always the current measured on a single coil ($10 ~\rm A$). | ||
| + | |||
| + | In a **wye** configuration: | ||
| + | * The **phase voltage** \( U_{\rm ph} = U_{\rm 12} = U_{\rm 23} = U_{\rm 31} \) is the **string voltage** \( U_\rm s \) times \( \sqrt{3} \) | ||
| + | * The **phase current** \( I_{\rm ph} \) is just the **string current** \( I_\rm s \) | ||
| + | |||
| + | So, we can compute: | ||
| + | * **Phase voltage** \( U_{\rm ph} = \sqrt{3} \cdot U_{\rm s} = \sqrt{3} \cdot 230 ~\rm V \approx 398.37 ~\rm V \) | ||
| + | * **Active power**: | ||
| + | |||
| + | \begin{align*} | ||
| + | P &= \sqrt{3} \cdot U_{\rm s} \cdot I_{\rm ph} \cdot \cos(\phi) \\ | ||
| + | &= \sqrt{3} \cdot 398.37 \cdot 10 \cdot \cos(25^\circ) \\ | ||
| + | &= 1.732 \cdot 398.37 \cdot 10 \cdot 0.9063 \, \text{W} \\ | ||
| + | & | ||
| + | \end{align*} | ||
| + | |||
| + | # | ||
| + | |||
| + | # | ||
| + | |||
| + | - string voltage \( U_{\rm s} = 230\, \text{V} \) | ||
| + | - phase voltage \( U_{\rm ph} = 398\, \text{V} \) | ||
| + | - string current \( I_{\rm s} = 10\, \text{A} \) | ||
| + | - phase current \( I_{\rm ph} = 10\, \text{A} \) | ||
| + | - and active power \( P = 6254.79\, \text{W} \) | ||
| + | |||
| + | # | ||
| + | |||
| + | 2. The motor shall be in delta configuration. \\ | ||
| + | Write down the string voltage, phase voltage, string current, phase current, and active power | ||
| + | |||
| + | # | ||
| + | |||
| + | * The **string voltage** \( U_\rm s \) is always the voltage measured on a single coil ($230 ~\rm V$). | ||
| + | * The **string current** \( I_\rm s \) is always the current measured on a single coil ($10 ~\rm A$). | ||
| + | |||
| + | In a **delta** configuration: | ||
| + | * The **phase voltage** \( U_{\rm ph} = U_{\rm 12} = U_{\rm 23} = U_{\rm 31} \) is just the **string voltage** \( U_\rm s \) \) | ||
| + | * The **phase current** \( I_{\rm ph} \) is the **string current** \( I_\rm s \) times \( \sqrt{3} | ||
| + | |||
| + | So, we can compute: | ||
| + | * **Phase current** \( I_{\rm ph} = \sqrt{3} \cdot I_{\rm s} = \sqrt{3} \cdot 10 ~\rm V \approx 17.32 ~\rm A \) | ||
| + | * **Active power**: | ||
| + | |||
| + | \begin{align*} | ||
| + | P &= \sqrt{3} \cdot U_{\rm s} \cdot I_{\rm ph} \cdot \cos(\phi) \\ | ||
| + | &= \sqrt{3} \cdot 200 \cdot 17.32 \cdot \cos(25^\circ) \\ | ||
| + | &= 1.732 \cdot 200 \cdot 17.32 \cdot 0.9063 \, \text{W} \\ | ||
| + | & | ||
| + | \end{align*} | ||
| + | |||
| + | # | ||
| + | |||
| + | # | ||
| + | |||
| + | - string voltage \( U_{\rm s} = 230\, \text{V} \) | ||
| + | - phase voltage \( U_{\rm ph} = 230\, \text{V} \) | ||
| + | - string current \( I_{\rm s} = 10\, \text{A} \) | ||
| + | - phase current \( I_{\rm ph} = 17.32\, \text{A} \) | ||
| + | - and active power \( P = 6254.79\, \text{W} \) | ||
| + | |||
| + | # | ||
| + | |||
| + | 3. Compare the results | ||
| + | |||
| + | # | ||
| + | |||
| + | ^ Configuration ^ String Voltage (V) ^ Phase Voltage (V) ^ Line Voltage (V) ^ String Current (A) ^ Phase Current (A) ^ Line Current (A) ^ Power (W) | | ||
| + | | Wye | 230 | 230 | 398.37 | ||
| + | | Delta | 230 | 230 | 230 | 10 | 10 | 17.32 | 6254.79 | ||
| + | |||
| + | **Conclusion: | ||
| + | Both configurations deliver the same active power to the motor. However: | ||
| + | * In **wye**, voltage across each phase is lower, resulting in lower current per line. | ||
| + | * In **delta**, current per line is higher, even though voltage across each phase equals line voltage. | ||
| + | |||
| + | # | ||
| + | |||
| + | # | ||
| + | |||
| + | # | ||
| + | |||
| + | A three-phase heater with given resistors is connected to the $230~\rm V$/$400~\rm V$ three-phase system. The heater shows purely ohmic behavior and can be configured in wye or delta configuration. \\ | ||
| + | |||
| + | 1. The heater is configured in a delta configuration and provides a constant heating power of $6 ~\rm kW$. \\ | ||
| + | 1.a Calculate the resistor value of a single string in the heater. \\ | ||
| + | 1.b Calculate the RMS values of the string currents and phase currents. \\ | ||
| + | |||
| + | # | ||
| + | ===== 1. Delta configuration ===== | ||
| + | The line-to-line (string) voltage in delta is the system line voltage | ||
| + | \[ | ||
| + | U_{\mathrm s, | ||
| + | \] | ||
| + | |||
| + | **(a) Resistor of one string** | ||
| + | |||
| + | Purely ohmic, total power in delta | ||
| + | \[ | ||
| + | P_\Delta = 3\; | ||
| + | \] | ||
| + | |||
| + | Solve for \(R\): | ||
| + | \begin{align*} | ||
| + | R &= 3\frac{U_{\mathrm s, | ||
| + | | ||
| + | | ||
| + | \end{align*} | ||
| + | |||
| + | **(b) Currents** | ||
| + | |||
| + | String (coil) current | ||
| + | \[ | ||
| + | I_{\mathrm s,\Delta}= \frac{U_{\mathrm s, | ||
| + | = \frac{400}{80}=5.00~\mathrm{A}. | ||
| + | \] | ||
| + | |||
| + | In delta the **phase current equals the string current**: | ||
| + | \[ | ||
| + | I_{\mathrm{ph}, | ||
| + | \] | ||
| + | |||
| + | (The line current would be \(I_{\mathrm L,\Delta}= \sqrt3\, | ||
| + | # | ||
| + | |||
| + | # | ||
| + | * resistor of one string \(R = 80~\Omega\) | ||
| + | * string current \(I_{\mathrm s, | ||
| + | * phase current \(I_{\mathrm{ph}, | ||
| + | # | ||
| + | |||
| + | 2. The heater with the same resistors as in 1. is now configured in a wye configuration. \\ | ||
| + | 2.a Calculate the RMS values of the string currents and phase currents. \\ | ||
| + | 2.b Compare the heating power in delta configuration (1.) and wye configuration (2.) \\ | ||
| + | |||
| + | # | ||
| + | ===== 2. Wye configuration (same resistors \(R=80~\Omega\)) ===== | ||
| + | The string (phase-to-neutral) voltage is the system phase voltage | ||
| + | \[ | ||
| + | U_{\mathrm s,\mathrm Y}=U_{\mathrm{PN}}=230~\mathrm{V}. | ||
| + | \] | ||
| + | |||
| + | **(a) Currents** | ||
| + | |||
| + | String current | ||
| + | \[ | ||
| + | I_{\mathrm s,\mathrm Y}= \frac{U_{\mathrm s,\mathrm Y}}{R} | ||
| + | = \frac{230}{80}=2.875~\mathrm{A}. | ||
| + | \] | ||
| + | |||
| + | In wye the **phase current equals the string current**: | ||
| + | \[ | ||
| + | I_{\mathrm{ph}, | ||
| + | \] | ||
| + | |||
| + | **(b) Heating power in wye** | ||
| + | |||
| + | Pure ohmic load: | ||
| + | \begin{align*} | ||
| + | P_{\mathrm Y} &= 3\; | ||
| + | = 3\; | ||
| + | \approx 1.984~\mathrm{kW}. | ||
| + | \end{align*} | ||
| + | |||
| + | --- | ||
| + | |||
| + | ===== Comparison ===== | ||
| + | \[ | ||
| + | \frac{P_{\mathrm Y}}{P_\Delta} = \frac{1.984~\mathrm{kW}}{6.000~\mathrm{kW}} | ||
| + | | ||
| + | \] | ||
| + | |||
| + | The heater delivers only about **33 %** of the delta power when re-wired in wye. | ||
| + | # | ||
| + | |||
| + | # | ||
| + | * string current \(I_{\mathrm s,\mathrm Y}=2.88~\mathrm{A}\) | ||
| + | * phase current \(I_{\mathrm{ph}, | ||
| + | * heating power \(P_{\mathrm Y}\approx1.98~\mathrm{kW}\) | ||
| + | * comparison: \(P_{\mathrm Y} \approx 0.33\, | ||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | |||
| + | # | ||
| + | |||
| + | A three-phase motor is connected to a three-phase system with a phase voltage of $400 ~\rm V$. The phase current is $16 ~\rm A$ and the power factor $0.9$. \\ | ||
| + | Calculate the active power, reactive power, and apparent power. | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | |||
| + | A symmetrical and balanced three-phase motor of a production line shall be configured in a star configuration and provide a power of $17~\rm kW$ with a power factor of $0.75$. The voltage on a single string is measured to be $135 ~\rm V$. \\ | ||
| + | Calculate the string current. | ||
| + | |||
| + | # | ||
| ==== Related Links ==== | ==== Related Links ==== | ||