Unterschiede
Hier werden die Unterschiede zwischen zwei Versionen angezeigt.
Beide Seiten der vorigen Revision Vorhergehende Überarbeitung Nächste Überarbeitung | Vorhergehende Überarbeitung | ||
electrical_engineering_2:polyphase_networks [2025/06/24 00:27] – mexleadmin | electrical_engineering_2:polyphase_networks [2025/06/24 00:40] (aktuell) – mexleadmin | ||
---|---|---|---|
Zeile 362: | Zeile 362: | ||
==== 7.2.2 Three-Phase System ==== | ==== 7.2.2 Three-Phase System ==== | ||
- | See also: __ BROKEN-LINK: | + | See also: __ BROKEN-LINK: |
The most commonly used polyphase system is the three-phase system. The three-phase system has advantages over a DC system or single-phase AC system: | The most commonly used polyphase system is the three-phase system. The three-phase system has advantages over a DC system or single-phase AC system: | ||
Zeile 1355: | Zeile 1355: | ||
A three-phase heater with given resistors is connected to the $230~\rm V$/$400~\rm V$ three-phase system. The heater shows purely ohmic behavior and can be configured in wye or delta configuration. \\ | A three-phase heater with given resistors is connected to the $230~\rm V$/$400~\rm V$ three-phase system. The heater shows purely ohmic behavior and can be configured in wye or delta configuration. \\ | ||
- | - The heater is configured in a delta configuration and provides a constant heating power of $6 ~\rm kW$. | + | 1. The heater is configured in a delta configuration and provides a constant heating power of $6 ~\rm kW$. \\ |
- | | + | 1.a Calculate the resistor value of a single string in the heater. \\ |
- | | + | 1.b Calculate the RMS values of the string currents and phase currents. |
- | - The heater with the same resistors as in 1. is now configured in a wye configuration. | + | |
- | | + | # |
- | | + | ===== 1. Delta configuration ===== |
+ | The line-to-line (string) voltage in delta is the system line voltage | ||
+ | \[ | ||
+ | U_{\mathrm s, | ||
+ | \] | ||
+ | |||
+ | **(a) Resistor of one string** | ||
+ | |||
+ | Purely ohmic, total power in delta | ||
+ | \[ | ||
+ | P_\Delta = 3\; | ||
+ | \] | ||
+ | |||
+ | Solve for \(R\): | ||
+ | \begin{align*} | ||
+ | R &= 3\frac{U_{\mathrm s, | ||
+ | | ||
+ | | ||
+ | \end{align*} | ||
+ | |||
+ | **(b) Currents** | ||
+ | |||
+ | String (coil) current | ||
+ | \[ | ||
+ | I_{\mathrm s,\Delta}= \frac{U_{\mathrm s, | ||
+ | = \frac{400}{80}=5.00~\mathrm{A}. | ||
+ | \] | ||
+ | |||
+ | In delta the **phase current equals the string current**: | ||
+ | \[ | ||
+ | I_{\mathrm{ph}, | ||
+ | \] | ||
+ | |||
+ | (The line current would be \(I_{\mathrm L,\Delta}= \sqrt3\, | ||
+ | # | ||
+ | |||
+ | # | ||
+ | * resistor of one string \(R = 80~\Omega\) | ||
+ | * string current \(I_{\mathrm s, | ||
+ | * phase current \(I_{\mathrm{ph}, | ||
+ | # | ||
+ | |||
+ | 2. The heater with the same resistors as in 1. is now configured in a wye configuration. | ||
+ | 2.a Calculate the RMS values of the string currents and phase currents. | ||
+ | 2.b Compare the heating power in delta configuration (1.) and wye configuration (2.) \\ | ||
+ | |||
+ | # | ||
+ | ===== 2. Wye configuration (same resistors \(R=80~\Omega\)) ===== | ||
+ | The string (phase-to-neutral) voltage is the system phase voltage | ||
+ | \[ | ||
+ | U_{\mathrm s,\mathrm Y}=U_{\mathrm{PN}}=230~\mathrm{V}. | ||
+ | \] | ||
+ | |||
+ | **(a) Currents** | ||
+ | |||
+ | String current | ||
+ | \[ | ||
+ | I_{\mathrm s,\mathrm Y}= \frac{U_{\mathrm s,\mathrm Y}}{R} | ||
+ | = \frac{230}{80}=2.875~\mathrm{A}. | ||
+ | \] | ||
+ | |||
+ | In wye the **phase current equals the string current**: | ||
+ | \[ | ||
+ | I_{\mathrm{ph}, | ||
+ | \] | ||
+ | |||
+ | **(b) Heating power in wye** | ||
+ | |||
+ | Pure ohmic load: | ||
+ | \begin{align*} | ||
+ | P_{\mathrm Y} &= 3\; | ||
+ | = 3\; | ||
+ | \approx 1.984~\mathrm{kW}. | ||
+ | \end{align*} | ||
+ | |||
+ | --- | ||
+ | |||
+ | ===== Comparison ===== | ||
+ | \[ | ||
+ | \frac{P_{\mathrm Y}}{P_\Delta} = \frac{1.984~\mathrm{kW}}{6.000~\mathrm{kW}} | ||
+ | | ||
+ | \] | ||
+ | |||
+ | The heater delivers only about **33 %** of the delta power when re-wired in wye. | ||
+ | # | ||
+ | |||
+ | # | ||
+ | * string current \(I_{\mathrm s,\mathrm Y}=2.88~\mathrm{A}\) | ||
+ | * phase current \(I_{\mathrm{ph}, | ||
+ | * heating power \(P_{\mathrm Y}\approx1.98~\mathrm{kW}\) | ||
+ | * comparison: \(P_{\mathrm Y} \approx 0.33\, | ||
+ | # | ||
+ | |||
# | # | ||