Differences
This shows you the differences between two versions of the page.
| Both sides previous revision Previous revision Next revision | Previous revision | ||
| electrical_engineering_and_electronics_2:block09 [2026/05/16 22:35] – mexleadmin | electrical_engineering_and_electronics_2:block09 [2026/05/19 02:55] (current) – mexleadmin | ||
|---|---|---|---|
| Line 9: | Line 9: | ||
| \[ | \[ | ||
| \begin{align*} | \begin{align*} | ||
| - | \frac{\underline{U}_1}{\underline{U}_2}=\frac{N_1}{N_2}=n, | + | \frac{\underline{U}_1^\phantom{O}}{\underline{U}_2^\phantom{O}}=\frac{N_1}{N_2}=n, |
| \qquad | \qquad | ||
| \frac{\underline{I}_1}{\underline{I}_2}=-\frac{1}{n} | \frac{\underline{I}_1}{\underline{I}_2}=-\frac{1}{n} | ||
| Line 19: | Line 19: | ||
| * refer secondary-side quantities to the primary side using \( \underline{U}' | * refer secondary-side quantities to the primary side using \( \underline{U}' | ||
| * interpret the no-load test and short-circuit test using the reduced equivalent circuit. | * interpret the no-load test and short-circuit test using the reduced equivalent circuit. | ||
| - | * calculate short-circuit voltage \(u_{\rm k}\), continuous short-circuit current \(I_{\rm 1k}\), and an estimated initial peak short-circuit current. | + | * calculate short-circuit voltage \(\rm u_k\), continuous short-circuit current \(I_{\rm 1k}\), and an estimated initial peak short-circuit current. |
| * connect transformer parameters to engineering applications in mechatronics and robotics, such as isolated power supplies, motor current measurement, | * connect transformer parameters to engineering applications in mechatronics and robotics, such as isolated power supplies, motor current measurement, | ||
| </ | </ | ||
| Line 50: | Line 50: | ||
| * **Practice (20 min):** | * **Practice (20 min):** | ||
| * Quick ratio calculations for step-up and step-down transformers. | * Quick ratio calculations for step-up and step-down transformers. | ||
| - | * Unit checks for \(j\omega L\), \(j\omega N\Phi\), and \(u_{\rm k}\). | ||
| * Short-circuit current calculation for a transformer used in an actuator supply. | * Short-circuit current calculation for a transformer used in an actuator supply. | ||
| Line 76: | Line 75: | ||
| * \(R_{\rm Fe}\): iron losses in the core. | * \(R_{\rm Fe}\): iron losses in the core. | ||
| * \(L_{\rm H}\): main magnetizing inductance needed to create the main flux. | * \(L_{\rm H}\): main magnetizing inductance needed to create the main flux. | ||
| - | * In engineering, | + | * In engineering, |
| </ | </ | ||
| Line 82: | Line 81: | ||
| ===== Core content ===== | ===== Core content ===== | ||
| - | |||
| - | ==== Mutual induction: the key idea before the transformer ==== | ||
| <panel type=" | <panel type=" | ||
| - | In EEE1 we considered magnetic flux \(\Phi\), flux linkage \(\Psi\), and induction. | + | In EEE1 we considered magnetic flux \(\Phi\), flux linkage |
| For one coil with \(N\) turns the flux linkage is | For one coil with \(N\) turns the flux linkage is | ||
| Line 103: | Line 100: | ||
| \] | \] | ||
| - | (Be aware of Lenz law, whenever you want to draw the votage arrows) \\ | + | (Be aware of Lenz law: Here u(t) is the terminal voltage according to the chosen voltage reference arrow. The induced voltage $u_{\rm ind}$ according |
| In sinusoidal steady state this becomes the phasor equation | In sinusoidal steady state this becomes the phasor equation | ||
| Line 115: | Line 112: | ||
| </ | </ | ||
| - | Now, we look onto the situation of two coils nearby each other and expand this formula for the induced voltage. \\ | + | ==== Polarity |
| - | For this, we see: | + | |
| - | <callout icon="fa fa-lightbulb-o" | + | Before we start with the transformer, |
| - | A changing current in coil \(1\) creates a changing magnetic flux. \\ | + | |
| - | If part of this flux passes through coil \(2\), a voltage is induced in coil \(2\). \\ | + | <WRAP> |
| - | This is called | + | <panel type="default"> |
| + | < | ||
| + | {{drawio> | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | < | ||
| + | **Rule of thumb** | ||
| + | |||
| + | * If both currents enter dotted terminals, the fluxes support each other. | ||
| + | * If one current enters a dotted terminal and the other current leaves a dotted terminal, the fluxes oppose each other. | ||
| </ | </ | ||
| + | |||
| + | |||
| + | ==== Ideal single-phase transformer ==== | ||
| + | |||
| + | {{drawio> | ||
| + | |||
| + | For an ideal transformer we assume: | ||
| + | |||
| + | * both windings are linked by the same magnetic flux \( \underline{\Phi} \), | ||
| + | * there is no leakage flux, | ||
| + | * there are no winding resistances, | ||
| + | * there are no iron losses, | ||
| + | * the transformer stores no net energy over one period. | ||
| + | |||
| + | Let \(N_1\) be the number of turns of the primary winding and \(N_2\) the number of turns of the secondary winding. | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{\Psi}_1 &= N_1\underline{\Phi}, | ||
| + | & | ||
| + | \underline{U}_1 &= j\omega\underline{\Psi}_1 | ||
| + | = j\omega N_1\underline{\Phi}, | ||
| + | \\ | ||
| + | \underline{\Psi}_2 &= N_2\underline{\Phi}, | ||
| + | & | ||
| + | \underline{U}_2 &= j\omega\underline{\Psi}_2 | ||
| + | = j\omega N_2\underline{\Phi}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | Dividing the two voltage equations gives the **turns ratio** | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | \frac{\underline{U}_1^\phantom{O}}{\underline{U}_2^\phantom{O}} | ||
| + | = | ||
| + | \frac{N_1}{N_2} | ||
| + | = | ||
| + | n | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | with | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | n=\frac{N_1}{N_2}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | <panel type=" | ||
| + | With the indicated reference arrows and a lossless transformer, | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{S}_1+\underline{S}_2= \underline{U}_1\underline{I}^*_1+\underline{U}_2\underline{I}^*_2=0 | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | and therefore | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | \frac{\underline{I}_1}{\underline{I}_2} | ||
| + | = | ||
| + | -\frac{\underline{U}_2^\phantom{O}}{\underline{U}_1^\phantom{O}} | ||
| + | = | ||
| + | -\frac{N_2}{N_1} | ||
| + | = | ||
| + | -\frac{1}{n} | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | The minus sign is not a “loss”. It is caused by the chosen current arrows. \\ | ||
| + | The primary side **absorbs** power while the secondary side **delivers** power to the load. | ||
| + | </ | ||
| + | |||
| + | |||
| + | <panel type=" | ||
| + | An ideal transformer behaves like a lossless gearbox: | ||
| + | |||
| + | * a gearbox can trade speed for torque, | ||
| + | * a transformer can trade voltage for current. | ||
| + | |||
| + | For a step-down transformer: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \text{lower voltage} \quad \Longleftrightarrow \quad \text{higher current}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | The power is ideally conserved, just as mechanical power is ideally conserved in a lossless gearbox. | ||
| + | </ | ||
| + | |||
| + | <panel type=" | ||
| + | * If \(N_2< | ||
| + | * At the same time, the secondary current can be higher: \(I_2> | ||
| + | * This is useful in robotics power supplies: a mains-side transformer or isolated converter stage may reduce voltage while increasing available current for actuators. | ||
| + | </ | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has \(N_1=800\) turns and \(N_2=80\) turns. | ||
| + | The primary RMS voltage is \(U_1=230~{\rm V}\). | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | n &= \frac{N_1}{N_2} | ||
| + | = \frac{800}{80} | ||
| + | =10, | ||
| + | \\ | ||
| + | U_2 &= \frac{U_1}{n} | ||
| + | = \frac{230~{\rm V}}{10} | ||
| + | =23~{\rm V}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | If the secondary side supplies \(I_2=4~{\rm A}\), the ideal primary current magnitude is | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | I_1 &= \frac{I_2}{n} | ||
| + | = \frac{4~{\rm A}}{10} | ||
| + | =0.4~{\rm A}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | The apparent power is equal on both sides: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | S_1 &= U_1I_1=230~{\rm V}\cdot 0.4~{\rm A}=92~{\rm VA}, | ||
| + | \\ | ||
| + | S_2 &= U_2I_2=23~{\rm V}\cdot 4~{\rm A}=92~{\rm VA}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | ~~PAGEBREAK~~ ~~CLEARFIX~~ | ||
| + | ==== Linked fluxes and mutual inductance ==== | ||
| + | |||
| + | For a single coil we already know that its flux linkage $\Psi = N\Phi$ is proportional to the current $i$ through the coil | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \Psi=L i | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{\Psi}=L \underline{I} . | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | For two coupled coils $1$ and $2$, each flux linkage $\underline{\Psi}_1 = N\underline{\Phi}_1$ and $\underline{\Psi}_2 = N\underline{\Phi}_2$ depend on both currents $\underline{I}_1$ and $\underline{I}_2$. \\ | ||
| + | |||
| + | {{drawio> | ||
| + | \\ \\ | ||
| + | Not only the current through the coil generates a part of the flux linkage, but also the other coil provides a part for the flux linkage. | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{\Psi}_1 | ||
| + | &= | ||
| + | \underbrace{{\color{green}{L_{11}\underline{I}_1}}}_{\text{self-linkage of coil 1}} | ||
| + | + | ||
| + | \underbrace{{\color{blue}{M_{12}\underline{I}_2}}}_{\text{mutual linkage from coil 2}}, | ||
| + | \\[4pt] | ||
| + | \underline{\Psi}_2 | ||
| + | &= | ||
| + | \underbrace{{\color{blue}{M_{21}\underline{I}_1}}}_{\text{mutual linkage from coil 1}} | ||
| + | + | ||
| + | \underbrace{{\color{green}{L_{22}\underline{I}_2}}}_{\text{self-linkage of coil 2}}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | For most transformer calculations we use the symmetric case of the mutual inductances. \\ | ||
| + | (this is true for passive, stationary, and reciprocal situations, like transformers, | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | {\color{blue}{M_{12}}}={\color{blue}{M_{21}}}={\color{blue}{M}}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | Often, the self-inductances are abbreviated: | ||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \color{green}{L_{11}} \rightarrow \color{green}{L_{1}} \\ | ||
| + | \color{green}{L_{22}} \rightarrow \color{green}{L_{2}} \\ | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | Then | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | \begin{pmatrix} | ||
| + | \underline{\Psi}_1\\ | ||
| + | \underline{\Psi}_2 | ||
| + | \end{pmatrix} | ||
| + | = | ||
| + | \begin{pmatrix} | ||
| + | {\color{green}{L_{1}}} & {\color{blue}{M}}\\ | ||
| + | {\color{blue}{M}} & {\color{green}{L_{2}}} | ||
| + | \end{pmatrix} | ||
| + | \begin{pmatrix} | ||
| + | \underline{I}_1\\ | ||
| + | \underline{I}_2 | ||
| + | \end{pmatrix} | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | and | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | M=k\sqrt{L_{1}L_{2}}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | Here \(k\) is the coupling coefficient. In the shown transformer \(k\) is 1 since all flux from $1$ flows through $2$ and vice versa. \\ | ||
| + | In reality that is not the case as explained in the next chapters. | ||
| + | |||
| + | < | ||
| + | |||
| + | ^ Coupling coefficient ^ Interpretation ^ Typical example ^ | ||
| + | | \(k=0\) | ||
| + | | \(0< | ||
| + | | \(k\approx 1\) | almost all useful flux links both coils | transformer with iron core | | ||
| + | </ | ||
| + | |||
| + | \\ \\ | ||
| + | |||
| + | The mutual inductance \(M\) answers the question: | ||
| + | |||
| + | > How much flux linkage appears in coil \(2\) when the current in coil \(1\) changes? | ||
| + | |||
| + | * A large \(M\) means strong interaction. | ||
| + | * A small \(M\) means weak interaction. | ||
| + | |||
| + | \\ | ||
| + | |||
| + | <panel type=" | ||
| + | In wireless charging, the transmitter coil and receiver coil are separated by an air gap. | ||
| + | The coupling coefficient \(k\) is much smaller than in a transformer with an iron core. | ||
| + | |||
| + | If the receiver is misaligned, less flux from the transmitter passes through it. | ||
| + | Then \(M\) decreases, the induced voltage decreases, and the transmitted power decreases. | ||
| + | </ | ||
| + | |||
| + | <panel type=" | ||
| + | <WRAP right> | ||
| + | Imagine two people lying on a bed holding the same bed sheet at different positions. | ||
| + | |||
| + | * \(L_{1}\): \\ how strongly winding 1 couples its current into the shared magnetic path, \\ like person 1 moving the sheet at their hand. | ||
| + | * \(L_{2}\): \\ how strongly winding 2 couples its current into the shared magnetic path, \\ like person 2 moving the sheet at their hand. | ||
| + | * \(M\): \\ how strongly the motion from one hand is felt at the other hand through the same sheet. | ||
| + | |||
| + | In transformer language, \(L_{1}\) and \(L_{2}\) describe each winding' | ||
| + | The mutual inductance \(M\) describes the transfer between the two windings through this shared path. | ||
| + | </ | ||
| + | |||
| + | |||
| + | ==== voltages by mutual inductances and resistances ==== | ||
| + | |||
| + | For positive coupling, we get the following complex representation (since $u(t) = L\frac{{\rm d}i}{{\rm d}t} \: \longrightarrow | ||
| + | \\ \\ | ||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{U}_1 &= R_1 \underline{I}_1 + {\color{green} {j\omega L_{1} \underline{I}_1 }} + {\color{blue}{j\omega M | ||
| + | \\[4pt] | ||
| + | \underline{U}_2 &= R_2 \underline{I}_2 + {\color{blue} | ||
| + | \end{align*} | ||
| + | \] | ||
| + | \\ | ||
| + | For negative coupling, the sign of the \(M\)-term changes in the chosen equation system, see <imgref fig_positive_coupling> | ||
| + | |||
| + | <WRAP group> | ||
| + | <WRAP column half> | ||
| + | <panel type=" | ||
| + | < | ||
| + | {{drawio> | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | <WRAP column half> | ||
| + | <panel type=" | ||
| + | < | ||
| + | {{drawio> | ||
| + | </ | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | <panel type=" | ||
| + | The dots are like matching openings for magnetic action. \\ | ||
| + | A positive reference current (e.g. $i_1$) entering the dotted terminal of one winding produces a positive induced voltage (e.g. aligned with $u_2$) at the dotted terminal of the other winding. \\ | ||
| + | With only a load $R_2$ connected to the secondary side, this voltage tends to drive current out of the dotted terminal into the load. \\ | ||
| + | </ | ||
| + | |||
| + | ~~PAGEBREAK~~ ~~CLEARFIX~~ | ||
| + | ==== Stray and Leakage ==== | ||
| + | |||
| + | The image of the ideal transformer shall be consecutively developed to a more realistic transformer model. \\ | ||
| + | To do so, we look at the situation of two coils near each other and expand this formula for the induced voltage. | ||
| < | < | ||
| Line 139: | Line 462: | ||
| {\color{blue}{\Phi_{21}}} | {\color{blue}{\Phi_{21}}} | ||
| + | + | ||
| - | {\color{orange}{\Phi_{\rm | + | {\color{orange}{\Phi_{1 \rm \sigma}}}. |
| \end{align*} | \end{align*} | ||
| \] | \] | ||
| - | * \(\Phi_{11}\): | + | * \(\Phi_{11}\): |
| - | * \({\color{blue}{\Phi_{21}}}\): | + | * \({\color{blue}{\Phi_{21}}}\): |
| - | * \({\color{orange}{\Phi_{\rm | + | * \({\color{orange}{\Phi_{1 \rm \sigma}}}\): stray or leakage flux that does **not** link coil \(2\). The Greek letter sigma $\sigma$ is used to denote leakage or " |
| - | The voltage induced in coil \(2\) is | + | For an example, we will have a look at the instantaneous |
| \[ | \[ | ||
| \begin{align*} | \begin{align*} | ||
| - | u_{{\rm ind},2}(t) | + | u_{2,\rm ind}(t) |
| + | = | ||
| + | \frac{{\rm d}{\color{blue}{\Psi_{21}}}}{{\rm d}t} | ||
| = | = | ||
| N_2\frac{{\rm d}{\color{blue}{\Phi_{21}}}}{{\rm d}t}. | N_2\frac{{\rm d}{\color{blue}{\Phi_{21}}}}{{\rm d}t}. | ||
| \end{align*} | \end{align*} | ||
| \] | \] | ||
| + | |||
| + | The complex voltage induced in coil \(2\) is | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{U}_{2} | ||
| + | = | ||
| + | j\omega {\color{blue}{ \underline{\Psi}_{21} }} | ||
| + | = | ||
| + | j\omega N_2 {\color{blue}{ \underline{\Phi}_{21} }} | ||
| + | . | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | \\ \\ | ||
| <panel type=" | <panel type=" | ||
| Line 191: | Line 531: | ||
| </ | </ | ||
| + | ==== Real transformer: | ||
| + | In a real transformer, | ||
| + | * The **main flux** \(\Phi_{\rm H}\) links primary and secondary winding. The ' | ||
| + | * The **primary leakage flux** \(\Phi_{1\sigma}\) mainly links only the primary winding. | ||
| + | * The **secondary leakage flux** \(\Phi_{2\sigma}\) mainly links only the secondary winding. | ||
| + | The leakage flux can be interpreted as an additional virtual branch in the mechanical setup, see <imgref fig_main_and_leakage_flux> | ||
| + | < | ||
| + | <panel type=" | ||
| + | < | ||
| + | {{drawio> | ||
| + | </ | ||
| + | </ | ||
| - | ... | + | The total main flux linking is given by (see <imgref fig_main_and_leakage_flux> |
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{\Phi}_{1 \rm H} = \underline{\Phi}_{21} + \underline{\Phi}_{12} = \underline{\Phi}_{\rm H} | ||
| + | \\[4pt] | ||
| + | \underline{\Phi}_{2 \rm H} = \underline{\Phi}_{21} + \underline{\Phi}_{12} = \underline{\Phi}_{\rm H} | ||
| + | \end{align*} | ||
| + | \] | ||
| - | ===== Common pitfalls | + | For the flux linkage also the leakage flux has to be considered: |
| - | * ... | + | \[ |
| + | \begin{align*} | ||
| + | \underline{\Psi}_{1} | ||
| + | \\[4pt] | ||
| + | \underline{\Psi}_{2} | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | The real flux linkage equations become | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{\Psi}_1 | ||
| + | &= \underbrace{{\color{blue | ||
| + | + \underbrace{{\color{orange}{L_{1\sigma }\underline{I}_1}} | ||
| + | \\[4pt] | ||
| + | \underline{\Psi}_2 | ||
| + | &= \underbrace{{\color{blue | ||
| + | + \underbrace{{\color{orange}{L_{2\sigma }\underline{I}_2}} | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | Equivalently, | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{\Psi}_1 | ||
| + | &= | ||
| + | L_1\underline{I}_1+M\underline{I}_2, | ||
| + | & | ||
| + | L_1&=L_{1{\rm H}}+L_{1\sigma}, | ||
| + | \\ | ||
| + | \underline{\Psi}_2 | ||
| + | &= | ||
| + | L_2\underline{I}_2+M\underline{I}_1, | ||
| + | & | ||
| + | L_2&=L_{2{\rm H}}+L_{2\sigma}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | The winding resistances \(R_1\) and \(R_2\) cause copper losses: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | P_{\rm Cu,1}=R_1I_1^2, | ||
| + | \qquad | ||
| + | P_{\rm Cu,2}=R_2I_2^2. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{U}_1 | ||
| + | &= | ||
| + | \underbrace{{\color{red}{R_1\underline{I}_1}}}_{\text{primary copper drop}} | ||
| + | + | ||
| + | \underbrace{{\color{orange}{j\omega L_{1\sigma}\underline{I}_1}}}_{\text{primary leakage drop}} | ||
| + | + | ||
| + | \underbrace{{\color{blue}{j\omega L_{1{\rm H}}\underline{I}_1+j\omega M\underline{I}_2}}}_{\text{main magnetic coupling}}, | ||
| + | \\[6pt] | ||
| + | \underline{U}_2 | ||
| + | &= | ||
| + | \underbrace{{\color{red}{R_2\underline{I}_2}}}_{\text{secondary copper drop}} | ||
| + | + | ||
| + | \underbrace{{\color{orange}{j\omega L_{2\sigma}\underline{I}_2}}}_{\text{secondary leakage drop}} | ||
| + | + | ||
| + | \underbrace{{\color{blue}{j\omega L_{2{\rm H}}\underline{I}_2+j\omega M\underline{I}_1}}}_{\text{main magnetic coupling}}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | Based, on the [[electrical_engineering_and_electronics_1: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | L_{1 \rm H} = \frac{N_1^2}{R_{\rm mFe} } \\ | ||
| + | L_{2 \rm H} = \frac{N_2^2}{R_{\rm mFe} } \\ | ||
| + | M = \frac{N_1 N_2}{R_{\rm mFe} } \\ | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | <panel type=" | ||
| + | In the previous formulas: | ||
| + | |||
| + | * <fc # | ||
| + | * <fc # | ||
| + | * <fc # | ||
| + | </ | ||
| + | |||
| + | |||
| + | <panel type=" | ||
| + | Think of the main flux as traffic on the useful road between two cities. | ||
| + | Traffic on side roads still exists, but it does not help transport goods between the two cities. | ||
| + | |||
| + | * main flux: useful road between primary and secondary winding, | ||
| + | * leakage flux: side roads that return locally, | ||
| + | * winding resistance: friction that turns useful energy into heat. | ||
| + | </ | ||
| + | |||
| + | ~~PAGEBREAK~~ ~~CLEARFIX~~ | ||
| + | |||
| + | ==== Reduced equivalent circuit referred to the primary side ==== | ||
| + | |||
| + | Since we know, that we can transform the current and voltage by the transformer, | ||
| + | |||
| + | < | ||
| + | {{drawio> | ||
| + | |||
| + | For calculations it is convenient to move all secondary-side quantities to the primary side. \\ | ||
| + | This is called **referring** or **transforming** the secondary side to the primary side. | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | \underline{U}' | ||
| + | } | ||
| + | \qquad | ||
| + | \boxed{ | ||
| + | \underline{I}' | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | The secondary resistance and leakage reactance are transformed by \(n^2\) since $R = U / I$: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | R' | ||
| + | } | ||
| + | \qquad | ||
| + | \boxed{ | ||
| + | X' | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | < | ||
| + | {{drawio> | ||
| + | |||
| + | In the reduced equivalent circuit: | ||
| + | |||
| + | * \(R_1\) and \(R' | ||
| + | * \(jX_{1\sigma}\) and \(jX' | ||
| + | * \(jX_{1{\rm H}}\) models the magnetizing branch. | ||
| + | * \(R_{\rm Fe}\) is placed parallel to \(jX_{1{\rm H}}\) to model iron losses. | ||
| + | * \(R_{\rm L}\) is a load resistor for the phasor diagram. | ||
| + | |||
| + | The phasor diagram is shown in <imgref fig_phasor_eq_circ01> | ||
| + | * The upper one only shows the main voltages and currents. \\ For an ohmic load current is parallel to $\underline{U}' | ||
| + | * The lower one shows all voltages and currents. | ||
| + | |||
| + | |||
| + | < | ||
| + | {{drawio> | ||
| + | |||
| + | |||
| + | <panel type=" | ||
| + | Once all quantities are referred to one side, the transformer can be calculated like an AC network with impedances. | ||
| + | This uses the same method as [[block04|complex network calculation]]: | ||
| + | </ | ||
| + | |||
| + | ==== No-load operation of the real transformer ==== | ||
| + | |||
| + | No-load operation means that the secondary side is open: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{I}_2=0. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | The primary side still draws a small no-load current \(\underline{I}_{10}\). This current has two parts: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{I}_{10} | ||
| + | = | ||
| + | \underline{I}_{\rm Fe} | ||
| + | + | ||
| + | \underline{I}_{\rm m}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | * \(\underline{I}_{\rm Fe}\): current through \(R_{\rm Fe}\), in phase with voltage, represents iron losses. | ||
| + | * \(\underline{I}_{\rm m}\): magnetizing current through \(jX_{1{\rm H}}\), approximately \(90^\circ\) lagging. | ||
| + | |||
| + | < | ||
| + | <panel type=" | ||
| + | < | ||
| + | {{drawio> | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | The technical voltage ratio is often defined from the no-load voltages. Here it is denoted by \(\ddot{\rm u}\): | ||
| + | |||
| + | \[ | ||
| + | \boxed{ | ||
| + | \begin{align*} | ||
| + | \ddot{\rm u} | ||
| + | = | ||
| + | \frac{\text{higher voltage}}{\text{lower voltage}} | ||
| + | \bigg|_{\rm no~load}. | ||
| + | \end{align*} | ||
| + | } | ||
| + | \] | ||
| + | |||
| + | For a step-down transformer: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \ddot{\rm u} | ||
| + | = | ||
| + | \frac{U_{1{\rm N}}}{U_{20}}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | Here \(U_{1{\rm N}}\) is the rated primary voltage and \(U_{20}\) is the open-circuit secondary voltage. | ||
| + | |||
| + | < | ||
| + | Because of real voltage drops and magnetizing effects, | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \ddot{\rm u}\neq n, | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | but for many practical transformers | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \ddot{\rm u}\approx n. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | </ | ||
| + | |||
| + | ==== Short-circuit operation of the real transformer ==== | ||
| + | |||
| + | In the short-circuit test, the secondary side is shorted, so $\underline{U}_2=0$. \\ | ||
| + | The primary voltage $\underline{U}_1$ is increased only until rated current flows. \\ | ||
| + | Because the short-circuit impedance is small, this requires only a small fraction of the rated primary voltage. \\ | ||
| + | Therefore the main flux and the magnetizing current are small, so the magnetizing branch can usually be neglected. | ||
| + | |||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \Big|\; jX_{1{\rm H}} \; || \;R_{\rm Fe} \;\Big| | ||
| + | \;\; \gg \;\; | ||
| + | \Big|\; jX_{1\sigma} + \;R_1 + jX' | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | < | ||
| + | <panel type=" | ||
| + | < | ||
| + | {{drawio> | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | This gives the short-circuit equivalent circuit with | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | R_{\rm k}=R_1+R' | ||
| + | } | ||
| + | \qquad | ||
| + | \boxed{ | ||
| + | X_{\rm k}=X_{1\sigma}+X' | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | and | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{Z}_{\rm k} | ||
| + | = | ||
| + | R_{\rm k}+jX_{\rm k}. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | |||
| + | |||
| + | <panel type=" | ||
| + | The **rated short-circuit voltage** \(U_{1{\rm k}}\) is the primary voltage that must be applied while the secondary side is shorted so that rated primary current \(I_{1{\rm N}}\) flows. | ||
| + | |||
| + | As a relative value: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | {\rm u_k} | ||
| + | = | ||
| + | \frac{U_{1{\rm k}}}{U_{1{\rm N}}}\cdot 100~\% | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | * Small \(\rm u_k\) means: small internal impedance. \\ When a short-circuit fault on the secondary side happens, the input current can get very high. | ||
| + | * Large \(\rm u_k\) means: high internal impedance. \\ Stronger current limitation, but also larger voltage drop under load. | ||
| + | </ | ||
| + | |||
| + | The continuous short-circuit current for rated primary voltage is | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | I_{1{\rm k}} | ||
| + | = | ||
| + | \frac{U_{1{\rm N}}}{U_{1{\rm k}}}\cdot I_{1{\rm N}} | ||
| + | = | ||
| + | I_{1{\rm N}}\cdot \frac{100~\%}{{\rm u_k}} | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | where \(\rm u_k\) is inserted as a percentage value. | ||
| + | |||
| + | <WRAP column 100%> | ||
| + | <panel type=" | ||
| + | For a first approximation of the maximum instantaneous current the following formula can be used: | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | i_{{\rm peak}} | ||
| + | = | ||
| + | 2.54 \cdot I_{1 \rm k} | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | </ | ||
| + | </ | ||
| + | |||
| + | |||
| + | ==== Real transformer under load ==== | ||
| + | |||
| + | Under load, the short-circuit equivalent circuit is often sufficient for engineering estimates. | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \underline{U}_{\rm k} | ||
| + | = | ||
| + | \left(R_{\rm k}+jX_{\rm k}\right)\underline{I}_1. | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | < | ||
| + | <panel type=" | ||
| + | < | ||
| + | {{drawio> | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | This voltage drop is subtracted vectorially from the primary-side voltage relation. \\ | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | \underline{U}_1 | ||
| + | - | ||
| + | \underline{U}_{\rm k} | ||
| + | = | ||
| + | \underline{U}' | ||
| + | = | ||
| + | n \underline{U}_2 | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | If the magnetizing branch is neglected for the load calculation, | ||
| + | |||
| + | \[ | ||
| + | \begin{align*} | ||
| + | \boxed{ | ||
| + | \frac{\underline{I}_1}{\underline{I}_2} | ||
| + | = | ||
| + | -\frac{N_2}{N_1} | ||
| + | = | ||
| + | -\frac{1}{n} | ||
| + | } | ||
| + | \end{align*} | ||
| + | \] | ||
| + | |||
| + | |||
| + | The Kapp triangle (see yellow triangle in <imgref fig_kapp_triangle> | ||
| + | |||
| + | < | ||
| + | < | ||
| + | </ | ||
| + | < | ||
| + | {{url> | ||
| + | |||
| + | </ | ||
| + | |||
| + | < | ||
| + | <button type=" | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | |||
| + | <panel type=" | ||
| + | In a robot with motors, the supply transformer may show a lower output voltage during high acceleration because the motor currents increase. | ||
| + | The Kapp triangle helps estimate this voltage drop. This is important for: | ||
| + | |||
| + | * selecting transformer size, | ||
| + | * checking whether the DC link after a rectifier remains high enough, | ||
| + | * designing fuses and protective devices, | ||
| + | * avoiding undervoltage resets in control electronics. | ||
| + | </ | ||
| + | |||
| + | ==== Construction types and cooling ==== | ||
| + | |||
| + | Transformer behavior is influenced by construction. | ||
| + | |||
| + | < | ||
| + | <panel type=" | ||
| + | < | ||
| + | {{drawio> | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | Cooling types: | ||
| + | |||
| + | * **Dry-type transformer: | ||
| + | * **Oil transformer: | ||
| + | \\ | ||
| + | <panel type=" | ||
| + | * **Isolating transformer: | ||
| + | * **Control transformer: | ||
| + | * **Current transformer: | ||
| + | * **Welding transformer: | ||
| + | </ | ||
| + | |||
| + | ==== Typical technical transformer data ==== | ||
| + | |||
| + | < | ||
| + | |||
| + | ^ Name / use ^ Typical \({\rm u_k}\) ^ Secondary voltage \(U_2\) ^ Important note ^ | ||
| + | | Power transformer | ||
| + | | Isolating transformer | ||
| + | | Toy transformer | ||
| + | | Doorbell transformer | ||
| + | | Ignition transformer | ||
| + | | Welding transformer | ||
| + | | Voltage transformer | ||
| + | | Current transformer | ||
| + | </ | ||
| + | |||
| + | \\ \\ | ||
| + | |||
| + | <WRAP column 100%> | ||
| + | <panel type=" | ||
| + | A current transformer secondary must not be opened while primary current flows. | ||
| + | If the secondary circuit is open, the transformer tries to maintain the magnetic balance and can generate dangerous high voltages. | ||
| + | </ | ||
| + | </ | ||
| ===== Exercises ===== | ===== Exercises ===== | ||
| - | ==== Worked examples ==== | ||
| - | ... | + | # |
| + | # | ||
| - | ===== Embedded resources ===== | + | A transformer has $N_1=1200$ turns and $N_2=300$ turns. |
| - | < | + | The primary RMS voltage is $U_1=230~{\rm V}$. \\ |
| - | Explanation (video): ... | + | The secondary side supplies a load current $I_2=2.0~{\rm A}$. |
| + | |||
| + | 1. Calculate the turns ratio $n$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The turns ratio of an ideal transformer is defined as: | ||
| + | \begin{align*} | ||
| + | n=\frac{N_1}{N_2} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the given values: | ||
| + | \begin{align*} | ||
| + | n | ||
| + | &= | ||
| + | \frac{1200}{300} | ||
| + | \\ | ||
| + | &= | ||
| + | 4 | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | n=4 | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| </ | </ | ||
| - | ~~PAGEBREAK~~ ~~CLEARFIX~~ | + | 2. Calculate the ideal secondary voltage $U_2$. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For an ideal transformer, | ||
| + | \begin{align*} | ||
| + | n=\frac{U_1}{U_2} | ||
| + | \end{align*} | ||
| + | Therefore: | ||
| + | \begin{align*} | ||
| + | U_2 | ||
| + | &= | ||
| + | \frac{U_1}{n} | ||
| + | \\ | ||
| + | &= | ||
| + | \frac{230~{\rm V}}{4} | ||
| + | \\ | ||
| + | &= | ||
| + | 57.5~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | U_2=57.5~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Calculate the magnitude of the ideal primary current $I_1$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For the ideal transformer, | ||
| + | \begin{align*} | ||
| + | I_1=\frac{I_2}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_1 | ||
| + | &= | ||
| + | \frac{2.0~{\rm A}}{4} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.50~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_1=0.50~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. State whether this is a step-up or step-down transformer. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | Compare the primary and secondary voltages: | ||
| + | \begin{align*} | ||
| + | U_1 &= 230~{\rm V} | ||
| + | \\ | ||
| + | U_2 &= 57.5~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | Since | ||
| + | \begin{align*} | ||
| + | U_2<U_1 | ||
| + | \end{align*} | ||
| + | |||
| + | the transformer reduces the voltage. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The transformer is a step-down transformer. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | Two coils are wound on the same ideal magnetic core. | ||
| + | The main magnetic reluctance is | ||
| + | |||
| + | \begin{align*} | ||
| + | R_{\rm mH}=2.0\cdot 10^6~\frac{1}{\rm H}. | ||
| + | \end{align*} | ||
| + | |||
| + | The number of turns is $N_1=500$ and $N_2=100$. | ||
| + | |||
| + | 1. Calculate $L_{1{\rm H}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The main-flux inductance of coil 1 is: | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}} | ||
| + | = | ||
| + | \frac{N_1^2}{R_{\rm mH}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}} | ||
| + | &= | ||
| + | \frac{500^2}{2.0\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.125~{\rm H} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}}=0.125~{\rm H} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Calculate $L_{2{\rm H}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The main-flux inductance of coil 2 is: | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| + | = | ||
| + | \frac{N_2^2}{R_{\rm mH}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| + | &= | ||
| + | \frac{100^2}{2.0\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.0050~{\rm H} | ||
| + | \\ | ||
| + | &= | ||
| + | 5.0~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| + | = | ||
| + | 0.0050~{\rm H} | ||
| + | = | ||
| + | 5.0~{\rm mH} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Calculate $M$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The mutual inductance is: | ||
| + | \begin{align*} | ||
| + | M | ||
| + | = | ||
| + | \frac{N_1N_2}{R_{\rm mH}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | M | ||
| + | &= | ||
| + | \frac{500\cdot 100}{2.0\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.025~{\rm H} | ||
| + | \\ | ||
| + | &= | ||
| + | 25~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | M | ||
| + | = | ||
| + | 0.025~{\rm H} | ||
| + | = | ||
| + | 25~{\rm mH} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Check whether the units are correct. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The reluctance is given in: | ||
| + | \begin{align*} | ||
| + | [R_{\rm mH}]=\frac{1}{\rm H} | ||
| + | \end{align*} | ||
| + | |||
| + | The number of turns is dimensionless. Therefore: | ||
| + | \begin{align*} | ||
| + | \left[ | ||
| + | \frac{N^2}{R_{\rm mH}} | ||
| + | \right] | ||
| + | = | ||
| + | \frac{1}{1/ | ||
| + | = | ||
| + | {\rm H} | ||
| + | \end{align*} | ||
| + | |||
| + | The same argument applies to the mutual inductance: | ||
| + | \begin{align*} | ||
| + | \left[ | ||
| + | \frac{N_1N_2}{R_{\rm mH}} | ||
| + | \right] | ||
| + | = | ||
| + | {\rm H} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The unit is correct because | ||
| + | \begin{align*} | ||
| + | \frac{1}{1/ | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | Two coils are wound on the same magnetic core. The shared main magnetic path has the reluctance | ||
| + | |||
| + | \begin{align*} | ||
| + | R_{\rm mH}=1.6\cdot 10^6~\frac{1}{\rm H}. | ||
| + | \end{align*} | ||
| + | |||
| + | The numbers of turns are | ||
| + | |||
| + | \begin{align*} | ||
| + | N_1=400, | ||
| + | \qquad | ||
| + | N_2=100. | ||
| + | \end{align*} | ||
| + | |||
| + | The leakage inductances are | ||
| + | |||
| + | \begin{align*} | ||
| + | L_{1\sigma}=4.0~{\rm mH}, | ||
| + | \qquad | ||
| + | L_{2\sigma}=0.30~{\rm mH}. | ||
| + | \end{align*} | ||
| + | |||
| + | 1. Calculate $L_{1{\rm H}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The main-flux self-inductance of coil 1 is: | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}} | ||
| + | = | ||
| + | \frac{N_1^2}{R_{\rm mH}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}} | ||
| + | &= | ||
| + | \frac{400^2}{1.6\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.100~{\rm H} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}}=0.100~{\rm H}=100~{\rm mH} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Calculate $L_{2{\rm H}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The main-flux self-inductance of coil 2 is: | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| + | = | ||
| + | \frac{N_2^2}{R_{\rm mH}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| + | &= | ||
| + | \frac{100^2}{1.6\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.00625~{\rm H} | ||
| + | \\ | ||
| + | &= | ||
| + | 6.25~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| + | = | ||
| + | 0.00625~{\rm H} | ||
| + | = | ||
| + | 6.25~{\rm mH} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Calculate $M$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The mutual inductance is: | ||
| + | \begin{align*} | ||
| + | M | ||
| + | = | ||
| + | \frac{N_1N_2}{R_{\rm mH}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | M | ||
| + | &= | ||
| + | \frac{400\cdot 100}{1.6\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.025~{\rm H} | ||
| + | \\ | ||
| + | &= | ||
| + | 25~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | M | ||
| + | = | ||
| + | 0.025~{\rm H} | ||
| + | = | ||
| + | 25~{\rm mH} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Calculate the total self-inductances $L_1$ and $L_2$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The total self-inductance is the sum of main-flux inductance and leakage inductance. | ||
| + | |||
| + | For coil 1: | ||
| + | \begin{align*} | ||
| + | L_1 | ||
| + | &= | ||
| + | L_{1{\rm H}}+L_{1\sigma} | ||
| + | \\ | ||
| + | &= | ||
| + | 100~{\rm mH}+4.0~{\rm mH} | ||
| + | \\ | ||
| + | &= | ||
| + | 104~{\rm mH} | ||
| + | \end{align*} | ||
| + | |||
| + | For coil 2: | ||
| + | \begin{align*} | ||
| + | L_2 | ||
| + | &= | ||
| + | L_{2{\rm H}}+L_{2\sigma} | ||
| + | \\ | ||
| + | &= | ||
| + | 6.25~{\rm mH}+0.30~{\rm mH} | ||
| + | \\ | ||
| + | &= | ||
| + | 6.55~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_1 &= 104~{\rm mH} | ||
| + | \\ | ||
| + | L_2 &= 6.55~{\rm mH} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Calculate the coupling coefficient $k=\frac{M}{\sqrt{L_1L_2}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The coupling coefficient is: | ||
| + | \begin{align*} | ||
| + | k | ||
| + | = | ||
| + | \frac{M}{\sqrt{L_1L_2}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values in henry: | ||
| + | \begin{align*} | ||
| + | k | ||
| + | &= | ||
| + | \frac{0.025~{\rm H}}{\sqrt{0.104~{\rm H}\cdot 0.00655~{\rm H}}} | ||
| + | \\ | ||
| + | & | ||
| + | 0.96 | ||
| + | \end{align*} | ||
| + | |||
| + | The coupling is strong, but not ideal, because leakage inductances are present. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | k\approx 0.96 | ||
| + | \end{align*} | ||
| + | |||
| + | The coupling is strong, but not ideal. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has $n=5$. | ||
| + | The secondary winding resistance is $R_2=0.20~\Omega$ and the secondary leakage reactance is $X_{2\sigma}=0.35~\Omega$. | ||
| + | |||
| + | Calculate the values $R'_2$ and $X' | ||
| + | |||
| + | 1. Calculate $R' | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | When a resistance is referred from the secondary side to the primary side, it is multiplied by $n^2$: | ||
| + | \begin{align*} | ||
| + | R'_2 | ||
| + | = | ||
| + | n^2R_2 | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | R'_2 | ||
| + | &= | ||
| + | 5^2\cdot 0.20~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 25\cdot 0.20~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 5.0~\Omega | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | R' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Calculate $X' | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The secondary leakage reactance is also referred to the primary side by multiplying with $n^2$: | ||
| + | \begin{align*} | ||
| + | X' | ||
| + | = | ||
| + | n^2X_{2\sigma} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | X' | ||
| + | &= | ||
| + | 5^2\cdot 0.35~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 25\cdot 0.35~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 8.75~\Omega | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | X' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Check the unit. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The turns ratio $n$ is dimensionless: | ||
| + | \begin{align*} | ||
| + | [n]=1 | ||
| + | \end{align*} | ||
| + | |||
| + | Therefore, multiplying by $n^2$ does not change the unit: | ||
| + | \begin{align*} | ||
| + | [R'_2] &= \Omega | ||
| + | \\ | ||
| + | [X' | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The unit remains $\Omega$, because $n$ is dimensionless. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has a rated primary current $I_{1{\rm N}}=10~{\rm A}$ and a short-circuit voltage ${\rm u_k}=5~\%$. | ||
| + | |||
| + | 1. Calculate the continuous short-circuit current $I_{1{\rm k}}$ when rated primary voltage is applied. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The short-circuit current can be estimated from the rated current and the relative short-circuit voltage: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}} | ||
| + | = | ||
| + | I_{1{\rm N}}\cdot \frac{100~\%}{\rm u_k} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}} | ||
| + | &= | ||
| + | 10~{\rm A}\cdot \frac{100~\%}{5~\%} | ||
| + | \\ | ||
| + | &= | ||
| + | 200~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}}=200~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Estimate the initial peak short-circuit current $i_{\rm p}$ using $i_{\rm p}\approx 2.54 I_{1{\rm k}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The initial peak current is estimated by: | ||
| + | \begin{align*} | ||
| + | i_{\rm p} | ||
| + | \approx | ||
| + | 2.54\cdot I_{1{\rm k}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the continuous short-circuit current: | ||
| + | \begin{align*} | ||
| + | i_{\rm p} | ||
| + | & | ||
| + | 2.54\cdot 200~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 508~{\rm A} | ||
| + | \end{align*} | ||
| + | |||
| + | The short-circuit current is much larger than the rated current. Protection devices must be selected accordingly. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | i_{\rm p}\approx 508~{\rm A} | ||
| + | \end{align*} | ||
| + | |||
| + | Protection devices must be selected accordingly. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A single-phase transformer supplies an actuator driver. | ||
| + | Rated data and equivalent circuit data are: | ||
| + | |||
| + | \begin{align*} | ||
| + | U_{1{\rm N}}& | ||
| + | & | ||
| + | U_{2{\rm N}}& | ||
| + | & | ||
| + | I_{2{\rm N}}& | ||
| + | \\ | ||
| + | R_1& | ||
| + | & | ||
| + | X_{1\sigma}& | ||
| + | \\ | ||
| + | R_2& | ||
| + | & | ||
| + | X_{2\sigma}& | ||
| + | \end{align*} | ||
| + | |||
| + | Assume $n=\frac{U_{1{\rm N}}}{U_{2{\rm N}}}$. The magnetizing branch is neglected for the loaded operating point. | ||
| + | |||
| + | 1. Calculate $n$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The turns ratio is estimated from the rated voltages: | ||
| + | \begin{align*} | ||
| + | n | ||
| + | = | ||
| + | \frac{U_{1{\rm N}}}{U_{2{\rm N}}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | n | ||
| + | &= | ||
| + | \frac{230~{\rm V}}{23~{\rm V}} | ||
| + | \\ | ||
| + | &= | ||
| + | 10 | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | n=10 | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Refer $R_2$ and $X_{2\sigma}$ to the primary side. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | Secondary quantities are referred to the primary side by multiplying them with $n^2$: | ||
| + | \begin{align*} | ||
| + | R'_2 &= n^2R_2 | ||
| + | \\ | ||
| + | X' | ||
| + | \end{align*} | ||
| + | |||
| + | With $n=10$: | ||
| + | \begin{align*} | ||
| + | R'_2 | ||
| + | &= | ||
| + | 10^2\cdot 0.012~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 1.2~\Omega | ||
| + | \\[4pt] | ||
| + | X' | ||
| + | &= | ||
| + | 10^2\cdot 0.018~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 1.8~\Omega | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | R'_2 &= 1.2~\Omega | ||
| + | \\ | ||
| + | X' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Calculate $R_{\rm k}$ and $X_{\rm k}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The short-circuit equivalent values are the sums of the primary quantities and the referred secondary quantities: | ||
| + | \begin{align*} | ||
| + | R_{\rm k} | ||
| + | &= | ||
| + | R_1+R' | ||
| + | \\ | ||
| + | X_{\rm k} | ||
| + | &= | ||
| + | X_{1\sigma}+X' | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | R_{\rm k} | ||
| + | &= | ||
| + | 1.2~\Omega+1.2~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 2.4~\Omega | ||
| + | \\[4pt] | ||
| + | X_{\rm k} | ||
| + | &= | ||
| + | 1.8~\Omega+1.8~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 3.6~\Omega | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | R_{\rm k} &= 2.4~\Omega | ||
| + | \\ | ||
| + | X_{\rm k} &= 3.6~\Omega | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Calculate the primary rated current magnitude $I_{1{\rm N}}$ using the ideal current ratio. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For an ideal transformer, | ||
| + | \begin{align*} | ||
| + | I_{1{\rm N}} | ||
| + | = | ||
| + | \frac{I_{2{\rm N}}}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm N}} | ||
| + | &= | ||
| + | \frac{5.0~{\rm A}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.50~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_{1{\rm N}}=0.50~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Estimate the magnitude of the internal voltage drop $U_{\rm k}\approx |\underline{Z}_{\rm k}|I_{1{\rm N}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | First calculate the magnitude of the short-circuit impedance: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | = | ||
| + | \sqrt{R_{\rm k}^2+X_{\rm k}^2} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | &= | ||
| + | \sqrt{(2.4~\Omega)^2+(3.6~\Omega)^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.33~\Omega | ||
| + | \end{align*} | ||
| + | |||
| + | Now calculate the internal voltage drop: | ||
| + | \begin{align*} | ||
| + | U_{\rm k} | ||
| + | & | ||
| + | |\underline{Z}_{\rm k}|I_{1{\rm N}} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.33~\Omega\cdot 0.50~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 2.17~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | This is a primary-side voltage drop. On the secondary side: | ||
| + | \begin{align*} | ||
| + | \frac{2.17~{\rm V}}{10} | ||
| + | = | ||
| + | 0.217~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | For a $23~{\rm V}$ actuator supply this is small but not zero. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| &= 4.33~\Omega | ||
| + | \\ | ||
| + | U_{\rm k} & | ||
| + | \end{align*} | ||
| + | |||
| + | Secondary-side equivalent: | ||
| + | \begin{align*} | ||
| + | U_{\rm k,2}\approx 0.217~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the rated primary data | ||
| + | |||
| + | \begin{align*} | ||
| + | U_{1{\rm N}}=230~{\rm V}, | ||
| + | \qquad | ||
| + | I_{1{\rm N}}=2.0~{\rm A}. | ||
| + | \end{align*} | ||
| + | |||
| + | The short-circuit equivalent impedance referred to the primary side is | ||
| + | |||
| + | \begin{align*} | ||
| + | R_{\rm k}=1.5~\Omega, | ||
| + | \qquad | ||
| + | X_{\rm k}=4.0~\Omega. | ||
| + | \end{align*} | ||
| + | |||
| + | |||
| + | 1. Calculate $|\underline{Z}_{\rm k}|$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The short-circuit impedance magnitude is: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | = | ||
| + | \sqrt{R_{\rm k}^2+X_{\rm k}^2} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | &= | ||
| + | \sqrt{(1.5~\Omega)^2+(4.0~\Omega)^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.27~\Omega | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}|=4.27~\Omega | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Calculate the rated short-circuit voltage $U_{1{\rm k}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The primary voltage required to drive rated current through the short-circuited transformer is: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} | ||
| + | = | ||
| + | |\underline{Z}_{\rm k}|I_{1{\rm N}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} | ||
| + | &= | ||
| + | 4.27~\Omega\cdot 2.0~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 8.54~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}}=8.54~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Calculate the relative short-circuit voltage ${\rm u_k}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The relative short-circuit voltage is: | ||
| + | \begin{align*} | ||
| + | {\rm u_k} | ||
| + | = | ||
| + | \frac{U_{1{\rm k}}}{U_{1{\rm N}}}\cdot 100~\% | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | {\rm u_k} | ||
| + | &= | ||
| + | \frac{8.54~{\rm V}}{230~{\rm V}}\cdot 100~\% | ||
| + | \\ | ||
| + | &= | ||
| + | 3.71~\% | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | {\rm u_k}=3.71~\% | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Calculate the prospective continuous short-circuit current $I_{1{\rm k}}$ for rated primary voltage. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The prospective continuous short-circuit current is: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}} | ||
| + | = | ||
| + | I_{1{\rm N}}\cdot \frac{100~\%}{\rm u_k} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}} | ||
| + | &= | ||
| + | 2.0~{\rm A}\cdot \frac{100}{3.71} | ||
| + | \\ | ||
| + | &= | ||
| + | 53.9~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}}=53.9~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Calculate the approximate first peak current $i_{\rm peak}\approx 2.54 I_{1{\rm k}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The approximate first peak current is: | ||
| + | \begin{align*} | ||
| + | i_{\rm peak} | ||
| + | \approx | ||
| + | 2.54 I_{1{\rm k}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the short-circuit current: | ||
| + | \begin{align*} | ||
| + | i_{\rm peak} | ||
| + | & | ||
| + | 2.54\cdot 53.9~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 137~{\rm A} | ||
| + | \end{align*} | ||
| + | |||
| + | Even though the rated current is only $2.0~{\rm A}$, a short-circuit fault could lead to a much larger current until protection reacts. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | i_{\rm peak}\approx 137~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the turns ratio $n=10$. | ||
| + | |||
| + | The short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.4~\Omega$, | ||
| + | The secondary load current is $I_2=4.0~{\rm A}$. The load has the power factor $\cos\varphi=0.8$ and is inductive. | ||
| + | |||
| + | Estimate the voltage drop on the secondary side using | ||
| + | |||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | \approx | ||
| + | I_1\left(R_{\rm k}\cos\varphi+X_{\rm k}\sin\varphi\right) | ||
| + | \end{align*} | ||
| + | |||
| + | and | ||
| + | |||
| + | \begin{align*} | ||
| + | \Delta U_2\approx \frac{\Delta U_1}{n}. | ||
| + | \end{align*} | ||
| + | |||
| + | 1. Calculate the primary current magnitude $I_1$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The primary current magnitude is approximately: | ||
| + | \begin{align*} | ||
| + | I_1 | ||
| + | = | ||
| + | \frac{I_2}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_1 | ||
| + | &= | ||
| + | \frac{4.0~{\rm A}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.40~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_1=0.40~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Determine $\sin\varphi$ for the inductive load. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For an inductive load with $\cos\varphi=0.8$: | ||
| + | \begin{align*} | ||
| + | \sin\varphi | ||
| + | = | ||
| + | \sqrt{1-\cos^2\varphi} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the value: | ||
| + | \begin{align*} | ||
| + | \sin\varphi | ||
| + | &= | ||
| + | \sqrt{1-0.8^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.6 | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \sin\varphi=0.6 | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Estimate the primary-side voltage drop $\Delta U_1$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | Use the Kapp approximation: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | & | ||
| + | I_1\left(R_{\rm k}\cos\varphi+X_{\rm k}\sin\varphi\right) | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | & | ||
| + | 0.40~{\rm A} | ||
| + | \left( | ||
| + | 2.4~\Omega\cdot 0.8 | ||
| + | + | ||
| + | 3.6~\Omega\cdot 0.6 | ||
| + | \right) | ||
| + | \\ | ||
| + | &= | ||
| + | 0.40~{\rm A} | ||
| + | \left( | ||
| + | 1.92~\Omega+2.16~\Omega | ||
| + | \right) | ||
| + | \\ | ||
| + | &= | ||
| + | 1.63~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_1\approx 1.63~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Estimate the secondary-side voltage drop $\Delta U_2$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The secondary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | \approx | ||
| + | \frac{\Delta U_1}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | & | ||
| + | \frac{1.63~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.163~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The secondary voltage decreases by approximately $0.16~{\rm V}$ for this operating point. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_2\approx 0.163~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The secondary voltage decreases by approximately $0.16~{\rm V}$. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the rated primary voltage $U_{1{\rm N}}=230~{\rm V}$. | ||
| + | Its rated primary current is $I_{1{\rm N}}=3.0~{\rm A}$. | ||
| + | |||
| + | At rated voltage and no-load operation, the magnetizing current is approximately $I_{\rm m, | ||
| + | The short-circuit voltage is ${\rm u_k}=6.0~\%$. | ||
| + | |||
| + | Assume that the magnetizing current is approximately proportional to the applied voltage. | ||
| + | \\ \\ \\ | ||
| + | 1. Calculate the short-circuit test voltage $U_{1{\rm k}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The short-circuit test voltage is: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} | ||
| + | = | ||
| + | \frac{\rm u_k}{100~\%}\cdot U_{1{\rm N}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} | ||
| + | &= | ||
| + | 0.06\cdot 230~{\rm V} | ||
| + | \\ | ||
| + | &= | ||
| + | 13.8~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}}=13.8~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Estimate the magnetizing current $I_{\rm m,k}$ during the short-circuit test. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The magnetizing current is assumed to be proportional to the voltage: | ||
| + | \begin{align*} | ||
| + | I_{\rm m,k} | ||
| + | = | ||
| + | I_{\rm m,N}\cdot \frac{U_{1{\rm k}}}{U_{1{\rm N}}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_{\rm m,k} | ||
| + | &= | ||
| + | 0.12~{\rm A}\cdot \frac{13.8~{\rm V}}{230~{\rm V}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.0072~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 7.2~{\rm mA} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_{\rm m,k} | ||
| + | = | ||
| + | 0.0072~{\rm A} | ||
| + | = | ||
| + | 7.2~{\rm mA} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Compare $I_{\rm m,k}$ with $I_{1{\rm N}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | Compare the short-circuit magnetizing current with the rated current: | ||
| + | \begin{align*} | ||
| + | \frac{I_{\rm m, | ||
| + | = | ||
| + | \frac{0.0072~{\rm A}}{3.0~{\rm A}} | ||
| + | \end{align*} | ||
| + | |||
| + | Calculate the ratio: | ||
| + | \begin{align*} | ||
| + | \frac{I_{\rm m, | ||
| + | &= | ||
| + | 0.0024 | ||
| + | \\ | ||
| + | &= | ||
| + | 0.24~\% | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \frac{I_{\rm m, | ||
| + | = | ||
| + | 0.24~\% | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Explain why the magnetizing branch can be neglected. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | During the short-circuit test, the applied voltage is much smaller than the rated voltage: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} \ll U_{1{\rm N}} | ||
| + | \end{align*} | ||
| + | |||
| + | Since the magnetizing current is assumed to be approximately proportional to the applied voltage, the magnetizing current is also very small: | ||
| + | \begin{align*} | ||
| + | I_{\rm m, | ||
| + | \end{align*} | ||
| + | |||
| + | Compared with the rated current: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm N}}=3.0~{\rm A} | ||
| + | \end{align*} | ||
| + | |||
| + | the magnetizing current is only $0.24~\%$. | ||
| + | |||
| + | So during the short-circuit test, almost all current flows through the short-circuit path consisting of $R_{\rm k}$ and $X_{\rm k}$. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The magnetizing branch $R_{\rm Fe}\parallel jX_{1{\rm H}}$ can usually be neglected in the short-circuit test. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the turns ratio $n=10$. The short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.0~\Omega$, | ||
| + | |||
| + | The secondary load current is $I_2=5.0~{\rm A}$. The load is ohmic-inductive with $\cos\varphi=0.8$. | ||
| + | |||
| + | The no-load current on the primary side is approximately $I_{10}=0.03~{\rm A}$. | ||
| + | \\ \\ \\ | ||
| + | 1. Calculate the load-related primary current $I' | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The load-related primary current is: | ||
| + | \begin{align*} | ||
| + | I'_2 | ||
| + | = | ||
| + | \frac{I_2}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I'_2 | ||
| + | &= | ||
| + | \frac{5.0~{\rm A}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.50~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Estimate the primary-side voltage drop. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The voltage drop is estimated with: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | \approx | ||
| + | I'_2 | ||
| + | \left( | ||
| + | R_{\rm k}\cos\varphi | ||
| + | + | ||
| + | X_{\rm k}\sin\varphi | ||
| + | \right) | ||
| + | \end{align*} | ||
| + | |||
| + | For $\cos\varphi=0.8$: | ||
| + | \begin{align*} | ||
| + | \sin\varphi | ||
| + | &= | ||
| + | \sqrt{1-\cos^2\varphi} | ||
| + | \\ | ||
| + | &= | ||
| + | \sqrt{1-0.8^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.6 | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | & | ||
| + | 0.50~{\rm A} | ||
| + | \left( | ||
| + | 2.0~\Omega\cdot 0.8 | ||
| + | + | ||
| + | 4.0~\Omega\cdot 0.6 | ||
| + | \right) | ||
| + | \\ | ||
| + | &= | ||
| + | 0.50~{\rm A} | ||
| + | \left( | ||
| + | 1.6~\Omega+2.4~\Omega | ||
| + | \right) | ||
| + | \\ | ||
| + | &= | ||
| + | 2.0~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_1\approx 2.0~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Calculate the secondary-side voltage drop $\Delta U_2\approx \frac{\Delta U_1}{n}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The secondary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | \approx | ||
| + | \frac{\Delta U_1}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | & | ||
| + | \frac{2.0~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.20~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_2\approx 0.20~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Estimate an upper bound for the neglected voltage drop caused by $I_{10}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | First calculate the magnitude of the short-circuit impedance: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | = | ||
| + | \sqrt{R_{\rm k}^2+X_{\rm k}^2} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | &= | ||
| + | \sqrt{(2.0~\Omega)^2+(4.0~\Omega)^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.47~\Omega | ||
| + | \end{align*} | ||
| + | |||
| + | The upper bound for the voltage drop caused by the no-load current is: | ||
| + | \begin{align*} | ||
| + | \Delta U_{1,10} | ||
| + | &\leq | ||
| + | |\underline{Z}_{\rm k}|I_{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.47~\Omega\cdot 0.03~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.134~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | On the secondary side: | ||
| + | \begin{align*} | ||
| + | \Delta U_{2,10} | ||
| + | &\leq | ||
| + | \frac{0.134~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.0134~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| &= 4.47~\Omega | ||
| + | \\ | ||
| + | \Delta U_{1,10} &\leq 0.134~{\rm V} | ||
| + | \\ | ||
| + | \Delta U_{2,10} &\leq 0.0134~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Decide whether the short-circuit equivalent circuit is sufficient for this load estimate. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The load-related secondary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_2\approx 0.20~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The estimated neglected secondary-side voltage drop caused by the no-load current is at most: | ||
| + | \begin{align*} | ||
| + | \Delta U_{2, | ||
| + | \end{align*} | ||
| + | |||
| + | This is small compared with the load-related drop of $0.20~{\rm V}$. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | For this engineering estimate, the short-circuit equivalent circuit is sufficient. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the rated primary voltage of $U_1=230~{\rm V}$ and and the turns ratio $n=10$. A resistive load draws $I_2=4.0~{\rm A}$. \\ | ||
| + | For the real transformer, | ||
| + | The iron loss is approximately $P_{\rm Fe}=1.5~{\rm W}$. \\ | ||
| + | Assume a resistive load with $\cos\varphi=1$. | ||
| + | \\ \\ | ||
| + | 1. Calculate the ideal secondary voltage $U_{2,\rm ideal}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For the ideal transformer: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm ideal} | ||
| + | = | ||
| + | \frac{U_1}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm ideal} | ||
| + | &= | ||
| + | \frac{230~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 23.0~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | U_{2,\rm ideal}=23.0~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Calculate the load-related primary current $I' | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The load-related primary current is: | ||
| + | \begin{align*} | ||
| + | I'_2 | ||
| + | = | ||
| + | \frac{I_2}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I'_2 | ||
| + | &= | ||
| + | \frac{4.0~{\rm A}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.40~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Estimate the real secondary voltage. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For a resistive load, the approximate primary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | \approx | ||
| + | I' | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | & | ||
| + | 0.40~{\rm A}\cdot 2.4~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 0.96~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The corresponding secondary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | & | ||
| + | \frac{\Delta U_1}{n} | ||
| + | \\ | ||
| + | &= | ||
| + | \frac{0.96~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.096~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | Thus the real secondary voltage is approximately: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm real} | ||
| + | & | ||
| + | 23.0~{\rm V}-0.096~{\rm V} | ||
| + | \\ | ||
| + | &= | ||
| + | 22.90~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_1 & | ||
| + | \\ | ||
| + | \Delta U_2 & | ||
| + | \\ | ||
| + | U_{2,\rm real} & | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Estimate the copper losses. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The copper losses are: | ||
| + | \begin{align*} | ||
| + | P_{\rm Cu} | ||
| + | \approx | ||
| + | R_{\rm k}(I' | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | P_{\rm Cu} | ||
| + | & | ||
| + | 2.4~\Omega\cdot (0.40~{\rm A})^2 | ||
| + | \\ | ||
| + | &= | ||
| + | 0.384~{\rm W} | ||
| + | \end{align*} | ||
| + | |||
| + | The real transformer also has iron losses: | ||
| + | \begin{align*} | ||
| + | P_{\rm Fe}=1.5~{\rm W} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | P_{\rm Cu}\approx 0.384~{\rm W} | ||
| + | \end{align*} | ||
| + | |||
| + | Additionally: | ||
| + | \begin{align*} | ||
| + | P_{\rm Fe}=1.5~{\rm W} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Compare ideal and real transformer behavior. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For the ideal transformer: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm ideal}=23.0~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | For the real transformer: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm real}\approx 22.90~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The real transformer has copper losses and iron losses: | ||
| + | \begin{align*} | ||
| + | P_{\rm Cu}& | ||
| + | \\ | ||
| + | P_{\rm Fe}& | ||
| + | \end{align*} | ||
| + | |||
| + | So the main differences are: | ||
| + | |||
| + | * the ideal transformer has exactly $U_2=23.0~{\rm V}$, the real transformer has a slightly lower voltage, | ||
| + | * the ideal transformer has no losses, the real transformer has copper and iron losses, | ||
| + | * the ideal transformer has no leakage voltage drop, the real transformer has a load-dependent voltage drop. | ||
| + | |||
| + | For this operating point the transformer is close to ideal, but not exactly ideal. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The real transformer differs from the ideal transformer by: | ||
| + | |||
| + | * a slightly lower secondary voltage, | ||
| + | * copper and iron losses, | ||
| + | * a load-dependent voltage drop. | ||
| + | |||
| + | For this operating point it is close to ideal, but not exactly ideal. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | ===== Common pitfalls ===== | ||
| + | |||
| + | * **Using a transformer with DC:** A transformer needs changing flux. With DC, after the switching transient, an ideal transformer no longer transfers voltage. A real transformer may overheat because the winding resistance limits the current only weakly. | ||
| + | * **Forgetting the current ratio sign:** The minus sign in \(\frac{\underline{I}_1}{\underline{I}_2}=-\frac{1}{n}\) comes from reference arrows. Do not interpret it as negative power loss. | ||
| + | * **Mixing peak values and RMS values:** In AC power and transformer ratings, \(U\) and \(I\) usually mean RMS values. Time functions are written \(u(t)\), \(i(t)\). Instantaneous short-circuit peaks are written here as \(i_{\rm p}\). | ||
| + | * **Confusing reluctance and resistance: | ||
| + | * **Confusing \(n\) and the technical no-load voltage ratio \(\ddot{\rm u}\):** The ideal ratio is \(n=\frac{N_1}{N_2}\). The measured no-load voltage ratio is close to \(n\), but not exactly equal for a real transformer. | ||
| + | * **Forgetting the square when referring impedances: | ||
| + | * **Ignoring leakage reactance: | ||
| + | * **Treating \(\rm u_k\) as a voltage in volts:** \(\rm u_k\) is normally given in percent. Insert it consistently in formulas. | ||
| + | * **Using \(2.54\) as a universal law:** The first short-circuit peak depends on the \(R/X\) ratio and on the switching instant. The factor \(2.54\) is an approximation. | ||
| + | * **Opening a current transformer secondary: | ||
| + | * **Assuming ideal isolation at every frequency: | ||
| + | |||
| + | ===== Embedded resources ===== | ||