| Line 324: | Line 324: | ||
| \] | \] | ||
| - | Often, the self-inductances are shortened: | + | Often, the self-inductances are abbreviated: |
| \[ | \[ | ||
| \begin{align*} | \begin{align*} | ||
| Line 753: | Line 753: | ||
| </ | </ | ||
| - | The technical voltage ratio is often defined from the no-load voltages. Here it is denoted by \(\ddot{u}\): | + | The technical voltage ratio is often defined from the no-load voltages. Here it is denoted by \(\ddot{\rm u}\): |
| \[ | \[ | ||
| Line 783: | Line 783: | ||
| \[ | \[ | ||
| \begin{align*} | \begin{align*} | ||
| - | \ddot{\ rm u}\neq n, | + | \ddot{\rm u}\neq n, |
| \end{align*} | \end{align*} | ||
| \] | \] | ||
| Line 926: | Line 926: | ||
| \underline{U}_{\rm k} | \underline{U}_{\rm k} | ||
| = | = | ||
| - | \underline{U'}_2 | + | \underline{U}'_2 |
| = | = | ||
| n \underline{U}_2 | n \underline{U}_2 | ||
| Line 1023: | Line 1023: | ||
| ===== Exercises ===== | ===== Exercises ===== | ||
| - | # | + | # |
| # | # | ||
| - | A transformer has \(N_1=1200\) turns and \(N_2=300\) turns. | + | A transformer has $N_1=1200$ turns and $N_2=300$ turns. |
| - | The primary RMS voltage is \(U_1=230~{\rm V}\). | + | The primary RMS voltage is $U_1=230~{\rm V}$. |
| - | The secondary side supplies a load current | + | The secondary side supplies a load current |
| - | * Calculate the turns ratio \(n\). | + | 1. Calculate the turns ratio $n$. |
| - | * Calculate the ideal secondary voltage \(U_2\). | + | <WRAP group> |
| - | * Calculate the magnitude of the ideal primary current \(I_1\). | + | <WRAP half column rightalign> |
| - | * State whether this is a step-up or step-down transformer. | + | #@PathBegin_HTML~2001~@# |
| - | + | <WRAP leftalign> | |
| - | #@ResultBegin_HTML~Exercise1~@# | + | The turns ratio of an ideal transformer is defined as: |
| - | + | ||
| - | \[ | + | |
| \begin{align*} | \begin{align*} | ||
| n=\frac{N_1}{N_2} | n=\frac{N_1}{N_2} | ||
| - | = | + | \end{align*} |
| + | |||
| + | Insert the given values: | ||
| + | \begin{align*} | ||
| + | n | ||
| + | &= | ||
| \frac{1200}{300} | \frac{1200}{300} | ||
| - | = | + | \\ |
| - | 4. | + | &= |
| + | 4 | ||
| \end{align*} | \end{align*} | ||
| - | \] | + | </ |
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | n=4 | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | The secondary voltage | + | 2. Calculate the ideal secondary voltage |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For an ideal transformer, | ||
| + | \begin{align*} | ||
| + | n=\frac{U_1}{U_2} | ||
| + | \end{align*} | ||
| - | \[ | + | Therefore: |
| \begin{align*} | \begin{align*} | ||
| U_2 | U_2 | ||
| - | = | + | &= |
| \frac{U_1}{n} | \frac{U_1}{n} | ||
| - | = | + | \\ |
| + | &= | ||
| \frac{230~{\rm V}}{4} | \frac{230~{\rm V}}{4} | ||
| - | = | + | \\ |
| - | 57.5~{\rm V}. | + | &= |
| + | 57.5~{\rm V} | ||
| \end{align*} | \end{align*} | ||
| - | \] | + | </ |
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | U_2=57.5~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | The primary current | + | 3. Calculate the magnitude of the ideal primary current |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For the ideal transformer, | ||
| + | \begin{align*} | ||
| + | I_1=\frac{I_2}{n} | ||
| + | \end{align*} | ||
| - | \[ | + | Insert the values: |
| \begin{align*} | \begin{align*} | ||
| I_1 | I_1 | ||
| - | = | + | &= |
| - | \frac{I_2}{n} | + | |
| - | = | + | |
| \frac{2.0~{\rm A}}{4} | \frac{2.0~{\rm A}}{4} | ||
| - | = | + | \\ |
| - | 0.50~{\rm A}. | + | &= |
| + | 0.50~{\rm A} | ||
| \end{align*} | \end{align*} | ||
| - | \] | + | </ |
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_1=0.50~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | Because \(U_2< | + | 4. State whether this is a step-up or step-down transformer. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | Compare the primary and secondary voltages: | ||
| + | \begin{align*} | ||
| + | U_1 &= 230~{\rm V} | ||
| + | \\ | ||
| + | U_2 &= 57.5~{\rm V} | ||
| + | \end{align*} | ||
| + | Since | ||
| + | \begin{align*} | ||
| + | U_2<U_1 | ||
| + | \end{align*} | ||
| + | |||
| + | the transformer reduces the voltage. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The transformer is a step-down transformer. | ||
| # | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| # | # | ||
| - | # | + | |
| + | # | ||
| # | # | ||
| Line 1086: | Line 1163: | ||
| The main magnetic reluctance is | The main magnetic reluctance is | ||
| - | \[ | ||
| \begin{align*} | \begin{align*} | ||
| R_{\rm mH}=2.0\cdot 10^6~\frac{1}{\rm H}. | R_{\rm mH}=2.0\cdot 10^6~\frac{1}{\rm H}. | ||
| \end{align*} | \end{align*} | ||
| - | \] | ||
| - | The number of turns is \(N_1=500\) and \(N_2=100\). | + | The number of turns is $N_1=500$ and $N_2=100$. |
| - | * Calculate \(L_{1{\rm H}}\). | + | 1. Calculate |
| - | * Calculate | + | <WRAP group> |
| - | * Calculate \(M\). | + | <WRAP half column rightalign> |
| - | * Check whether the units are correct. | + | #@PathBegin_HTML~2005~@# |
| - | + | <WRAP leftalign> | |
| - | #@ResultBegin_HTML~Exercise2~@# | + | The main-flux inductance of coil 1 is: |
| - | + | ||
| - | \[ | + | |
| \begin{align*} | \begin{align*} | ||
| L_{1{\rm H}} | L_{1{\rm H}} | ||
| = | = | ||
| \frac{N_1^2}{R_{\rm mH}} | \frac{N_1^2}{R_{\rm mH}} | ||
| - | = | + | \end{align*} |
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}} | ||
| + | &= | ||
| \frac{500^2}{2.0\cdot 10^6~1/{\rm H}} | \frac{500^2}{2.0\cdot 10^6~1/{\rm H}} | ||
| - | = | + | \\ |
| - | 0.125~{\rm H}. | + | &= |
| + | 0.125~{\rm H} | ||
| \end{align*} | \end{align*} | ||
| - | \] | + | </ |
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}}=0.125~{\rm H} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | \[ | + | 2. Calculate $L_{2{\rm H}}$. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The main-flux inductance of coil 2 is: | ||
| \begin{align*} | \begin{align*} | ||
| L_{2{\rm H}} | L_{2{\rm H}} | ||
| = | = | ||
| \frac{N_2^2}{R_{\rm mH}} | \frac{N_2^2}{R_{\rm mH}} | ||
| - | = | + | \end{align*} |
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| + | &= | ||
| \frac{100^2}{2.0\cdot 10^6~1/{\rm H}} | \frac{100^2}{2.0\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.0050~{\rm H} | ||
| + | \\ | ||
| + | &= | ||
| + | 5.0~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| = | = | ||
| 0.0050~{\rm H} | 0.0050~{\rm H} | ||
| = | = | ||
| - | 5.0~{\rm mH}. | + | 5.0~{\rm mH} |
| \end{align*} | \end{align*} | ||
| - | \] | + | # |
| + | </ | ||
| + | </ | ||
| - | \[ | + | 3. Calculate $M$. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The mutual inductance is: | ||
| \begin{align*} | \begin{align*} | ||
| M | M | ||
| = | = | ||
| \frac{N_1N_2}{R_{\rm mH}} | \frac{N_1N_2}{R_{\rm mH}} | ||
| - | = | + | \end{align*} |
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | M | ||
| + | &= | ||
| \frac{500\cdot 100}{2.0\cdot 10^6~1/{\rm H}} | \frac{500\cdot 100}{2.0\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.025~{\rm H} | ||
| + | \\ | ||
| + | &= | ||
| + | 25~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | M | ||
| = | = | ||
| 0.025~{\rm H} | 0.025~{\rm H} | ||
| = | = | ||
| - | 25~{\rm mH}. | + | 25~{\rm mH} |
| \end{align*} | \end{align*} | ||
| - | \] | + | # |
| + | </ | ||
| + | </ | ||
| - | The unit is correct because | + | 4. Check whether the units are correct. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The reluctance | ||
| + | \begin{align*} | ||
| + | [R_{\rm mH}]=\frac{1}{\rm H} | ||
| + | \end{align*} | ||
| + | The number of turns is dimensionless. Therefore: | ||
| + | \begin{align*} | ||
| + | \left[ | ||
| + | \frac{N^2}{R_{\rm mH}} | ||
| + | \right] | ||
| + | = | ||
| + | \frac{1}{1/ | ||
| + | = | ||
| + | {\rm H} | ||
| + | \end{align*} | ||
| + | |||
| + | The same argument applies to the mutual inductance: | ||
| + | \begin{align*} | ||
| + | \left[ | ||
| + | \frac{N_1N_2}{R_{\rm mH}} | ||
| + | \right] | ||
| + | = | ||
| + | {\rm H} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The unit is correct because | ||
| + | \begin{align*} | ||
| + | \frac{1}{1/ | ||
| + | \end{align*} | ||
| # | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| # | # | ||
| - | # | + | |
| + | # | ||
| # | # | ||
| - | A transformer has \(n=5\). | + | Two coils are wound on the same magnetic core. The shared main magnetic path has the reluctance |
| - | The secondary winding resistance is \(R_2=0.20~\Omega\) and the secondary leakage reactance is \(X_{2\sigma}=0.35~\Omega\). | + | |
| - | Calculate the values | + | \begin{align*} |
| + | R_{\rm mH}=1.6\cdot 10^6~\frac{1}{\rm H}. | ||
| + | \end{align*} | ||
| - | # | + | The numbers of turns are |
| - | \[ | ||
| \begin{align*} | \begin{align*} | ||
| - | R'_2 | + | N_1=400, |
| + | \qquad | ||
| + | N_2=100. | ||
| + | \end{align*} | ||
| + | |||
| + | The leakage inductances are | ||
| + | |||
| + | \begin{align*} | ||
| + | L_{1\sigma}=4.0~{\rm mH}, | ||
| + | \qquad | ||
| + | L_{2\sigma}=0.30~{\rm mH}. | ||
| + | \end{align*} | ||
| + | |||
| + | 1. Calculate $L_{1{\rm H}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The main-flux self-inductance of coil 1 is: | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}} | ||
| = | = | ||
| - | n^2R_2 | + | \frac{N_1^2}{R_{\rm mH}} |
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}} | ||
| + | &= | ||
| + | \frac{400^2}{1.6\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.100~{\rm H} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_{1{\rm H}}=0.100~{\rm H}=100~{\rm mH} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Calculate $L_{2{\rm H}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The main-flux self-inductance of coil 2 is: | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| = | = | ||
| - | 5^2\cdot 0.20~\Omega | + | \frac{N_2^2}{R_{\rm mH}} |
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| + | &= | ||
| + | \frac{100^2}{1.6\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.00625~{\rm H} | ||
| + | \\ | ||
| + | &= | ||
| + | 6.25~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_{2{\rm H}} | ||
| = | = | ||
| - | 25\cdot | + | 0.00625~{\rm H} |
| = | = | ||
| - | 5.0~\Omega. | + | 6.25~{\rm mH} |
| \end{align*} | \end{align*} | ||
| - | \] | + | # |
| + | </ | ||
| + | </ | ||
| - | \[ | + | 3. Calculate $M$. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The mutual inductance is: | ||
| \begin{align*} | \begin{align*} | ||
| - | X' | + | M |
| = | = | ||
| - | n^2X_{2\sigma} | + | \frac{N_1N_2}{R_{\rm mH}} |
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | M | ||
| + | &= | ||
| + | \frac{400\cdot 100}{1.6\cdot 10^6~1/{\rm H}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.025~{\rm H} | ||
| + | \\ | ||
| + | &= | ||
| + | 25~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | M | ||
| = | = | ||
| - | 5^2\cdot | + | 0.025~{\rm H} |
| = | = | ||
| - | 25\cdot 0.35~\Omega | + | 25~{\rm mH} |
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Calculate the total self-inductances $L_1$ and $L_2$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The total self-inductance is the sum of main-flux inductance and leakage inductance. | ||
| + | |||
| + | For coil 1: | ||
| + | \begin{align*} | ||
| + | L_1 | ||
| + | &= | ||
| + | L_{1{\rm H}}+L_{1\sigma} | ||
| + | \\ | ||
| + | &= | ||
| + | 100~{\rm mH}+4.0~{\rm mH} | ||
| + | \\ | ||
| + | &= | ||
| + | 104~{\rm mH} | ||
| + | \end{align*} | ||
| + | |||
| + | For coil 2: | ||
| + | \begin{align*} | ||
| + | L_2 | ||
| + | &= | ||
| + | L_{2{\rm H}}+L_{2\sigma} | ||
| + | \\ | ||
| + | &= | ||
| + | 6.25~{\rm mH}+0.30~{\rm mH} | ||
| + | \\ | ||
| + | &= | ||
| + | 6.55~{\rm mH} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | L_1 &= 104~{\rm mH} | ||
| + | \\ | ||
| + | L_2 &= 6.55~{\rm mH} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Calculate the coupling coefficient $k=\frac{M}{\sqrt{L_1L_2}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The coupling coefficient is: | ||
| + | \begin{align*} | ||
| + | k | ||
| = | = | ||
| - | 8.75~\Omega. | + | \frac{M}{\sqrt{L_1L_2}} |
| \end{align*} | \end{align*} | ||
| - | \] | ||
| - | The unit remains | + | Insert the values in henry: |
| + | \begin{align*} | ||
| + | k | ||
| + | &= | ||
| + | \frac{0.025~{\rm H}}{\sqrt{0.104~{\rm H}\cdot 0.00655~{\rm H}}} | ||
| + | \\ | ||
| + | & | ||
| + | 0.96 | ||
| + | \end{align*} | ||
| + | The coupling is strong, but not ideal, because leakage inductances are present. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | k\approx 0.96 | ||
| + | \end{align*} | ||
| + | |||
| + | The coupling is strong, but not ideal. | ||
| # | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| # | # | ||
| - | # | + | |
| + | # | ||
| # | # | ||
| - | A transformer has a rated primary current \(I_{1{\rm N}}=10~{\rm A}\) and a short-circuit voltage \({\rm u_k}=5~\%\). | + | A transformer has $n=5$. |
| + | The secondary winding resistance is $R_2=0.20~\Omega$ | ||
| - | * Calculate the continuous short-circuit current \(I_{1{\rm k}}\) when rated primary | + | Calculate the values $R'_2$ and $X'_{2\sigma}$ referred to the primary |
| - | * Estimate the initial peak short-circuit current \(i_{\rm p}\) using \(i_{\rm p}\approx 2.54 I_{1{\rm k}}\). | + | |
| - | #@ResultBegin_HTML~Exercise4~@# | + | 1. Calculate $R' |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | #@PathBegin_HTML~2014~@# | ||
| + | <WRAP leftalign> | ||
| + | When a resistance is referred from the secondary side to the primary side, it is multiplied by $n^2$: | ||
| + | \begin{align*} | ||
| + | R'_2 | ||
| + | = | ||
| + | n^2R_2 | ||
| + | \end{align*} | ||
| - | \[ | + | Insert the values: |
| + | \begin{align*} | ||
| + | R'_2 | ||
| + | &= | ||
| + | 5^2\cdot 0.20~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 25\cdot 0.20~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 5.0~\Omega | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | R' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Calculate $X' | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The secondary leakage reactance is also referred to the primary side by multiplying with $n^2$: | ||
| + | \begin{align*} | ||
| + | X' | ||
| + | = | ||
| + | n^2X_{2\sigma} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | X' | ||
| + | &= | ||
| + | 5^2\cdot 0.35~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 25\cdot 0.35~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 8.75~\Omega | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | X' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Check the unit. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The turns ratio $n$ is dimensionless: | ||
| + | \begin{align*} | ||
| + | [n]=1 | ||
| + | \end{align*} | ||
| + | |||
| + | Therefore, multiplying by $n^2$ does not change the unit: | ||
| + | \begin{align*} | ||
| + | [R'_2] &= \Omega | ||
| + | \\ | ||
| + | [X' | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The unit remains $\Omega$, because $n$ is dimensionless. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has a rated primary current $I_{1{\rm N}}=10~{\rm A}$ and a short-circuit voltage ${\rm u_k}=5~\%$. | ||
| + | |||
| + | 1. Calculate the continuous short-circuit current $I_{1{\rm k}}$ when rated primary voltage is applied. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The short-circuit current can be estimated from the rated current and the relative short-circuit voltage: | ||
| \begin{align*} | \begin{align*} | ||
| I_{1{\rm k}} | I_{1{\rm k}} | ||
| = | = | ||
| I_{1{\rm N}}\cdot \frac{100~\%}{\rm u_k} | I_{1{\rm N}}\cdot \frac{100~\%}{\rm u_k} | ||
| - | = | + | \end{align*} |
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}} | ||
| + | &= | ||
| 10~{\rm A}\cdot \frac{100~\%}{5~\%} | 10~{\rm A}\cdot \frac{100~\%}{5~\%} | ||
| - | = | + | \\ |
| - | 200~{\rm A}. | + | &= |
| + | 200~{\rm A} | ||
| \end{align*} | \end{align*} | ||
| - | \] | + | </ |
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}}=200~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | \[ | + | 2. Estimate the initial peak short-circuit current $i_{\rm p}$ using $i_{\rm p}\approx 2.54 I_{1{\rm k}}$. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The initial peak current is estimated by: | ||
| \begin{align*} | \begin{align*} | ||
| i_{\rm p} | i_{\rm p} | ||
| \approx | \approx | ||
| 2.54\cdot I_{1{\rm k}} | 2.54\cdot I_{1{\rm k}} | ||
| - | = | + | \end{align*} |
| + | |||
| + | Insert the continuous short-circuit current: | ||
| + | \begin{align*} | ||
| + | i_{\rm p} | ||
| + | & | ||
| 2.54\cdot 200~{\rm A} | 2.54\cdot 200~{\rm A} | ||
| - | = | + | \\ |
| - | 508~{\rm A}. | + | &= |
| + | 508~{\rm A} | ||
| \end{align*} | \end{align*} | ||
| - | \] | ||
| The short-circuit current is much larger than the rated current. Protection devices must be selected accordingly. | The short-circuit current is much larger than the rated current. Protection devices must be selected accordingly. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | i_{\rm p}\approx 508~{\rm A} | ||
| + | \end{align*} | ||
| + | Protection devices must be selected accordingly. | ||
| # | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| # | # | ||
| - | # | + | |
| + | # | ||
| # | # | ||
| Line 1234: | Line 1744: | ||
| Rated data and equivalent circuit data are: | Rated data and equivalent circuit data are: | ||
| - | \[ | ||
| \begin{align*} | \begin{align*} | ||
| U_{1{\rm N}}& | U_{1{\rm N}}& | ||
| Line 1250: | Line 1759: | ||
| X_{2\sigma}& | X_{2\sigma}& | ||
| \end{align*} | \end{align*} | ||
| - | \] | ||
| - | |||
| - | Assume \(n=\frac{U_{1{\rm N}}}{U_{2{\rm N}}}\). The magnetizing branch is neglected for the loaded operating point. | ||
| - | * Calculate \(n\). | + | Assume $n=\frac{U_{1{\rm N}}}{U_{2{\rm N}}}$. The magnetizing branch is neglected for the loaded operating point. |
| - | * Refer \(R_2\) and \(X_{2\sigma}\) to the primary side. | + | |
| - | * Calculate \(R_{\rm k}\) and \(X_{\rm k}\). | + | |
| - | * Calculate the primary rated current magnitude \(I_{1{\rm N}}\) using the ideal current ratio. | + | |
| - | * Estimate the magnitude of the internal voltage drop \(U_{\rm k}\approx |\underline{Z}_{\rm k}|I_{1{\rm N}}\). | + | |
| - | #@ResultBegin_HTML~Exercise5~@# | + | 1. Calculate $n$. |
| - | + | <WRAP group> | |
| - | The turns ratio is | + | <WRAP half column rightalign> |
| - | + | #@PathBegin_HTML~2019~@# | |
| - | \[ | + | <WRAP leftalign> |
| + | The turns ratio is estimated from the rated voltages: | ||
| \begin{align*} | \begin{align*} | ||
| n | n | ||
| = | = | ||
| \frac{U_{1{\rm N}}}{U_{2{\rm N}}} | \frac{U_{1{\rm N}}}{U_{2{\rm N}}} | ||
| - | = | + | \end{align*} |
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | n | ||
| + | &= | ||
| \frac{230~{\rm V}}{23~{\rm V}} | \frac{230~{\rm V}}{23~{\rm V}} | ||
| - | = | + | \\ |
| - | 10. | + | &= |
| + | 10 | ||
| \end{align*} | \end{align*} | ||
| - | \] | + | </ |
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | n=10 | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | The secondary | + | 2. Refer $R_2$ and $X_{2\sigma}$ to the primary side. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | Secondary | ||
| + | \begin{align*} | ||
| + | R'_2 &= n^2R_2 | ||
| + | \\ | ||
| + | X' | ||
| + | \end{align*} | ||
| - | \[ | + | With $n=10$: |
| \begin{align*} | \begin{align*} | ||
| R'_2 | R'_2 | ||
| &= | &= | ||
| - | n^2R_2 | ||
| - | = | ||
| 10^2\cdot 0.012~\Omega | 10^2\cdot 0.012~\Omega | ||
| - | = | ||
| - | 1.2~\Omega, | ||
| \\ | \\ | ||
| + | &= | ||
| + | 1.2~\Omega | ||
| + | \\[4pt] | ||
| X' | X' | ||
| &= | &= | ||
| - | n^2X_{2\sigma} | ||
| - | = | ||
| 10^2\cdot 0.018~\Omega | 10^2\cdot 0.018~\Omega | ||
| - | = | + | \\ |
| - | 1.8~\Omega. | + | &= |
| + | 1.8~\Omega | ||
| \end{align*} | \end{align*} | ||
| - | \] | + | </ |
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | R'_2 &= 1.2~\Omega | ||
| + | \\ | ||
| + | X' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | Therefore | + | 3. Calculate $R_{\rm k}$ and $X_{\rm k}$. |
| - | + | <WRAP group> | |
| - | \[ | + | <WRAP half column rightalign> |
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The short-circuit equivalent values are the sums of the primary quantities and the referred secondary quantities: | ||
| \begin{align*} | \begin{align*} | ||
| R_{\rm k} | R_{\rm k} | ||
| &= | &= | ||
| R_1+R' | R_1+R' | ||
| - | = | ||
| - | 1.2~\Omega+1.2~\Omega | ||
| - | = | ||
| - | 2.4~\Omega, | ||
| \\ | \\ | ||
| X_{\rm k} | X_{\rm k} | ||
| &= | &= | ||
| X_{1\sigma}+X' | X_{1\sigma}+X' | ||
| - | = | + | \end{align*} |
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | R_{\rm k} | ||
| + | &= | ||
| + | 1.2~\Omega+1.2~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 2.4~\Omega | ||
| + | \\[4pt] | ||
| + | X_{\rm k} | ||
| + | &= | ||
| 1.8~\Omega+1.8~\Omega | 1.8~\Omega+1.8~\Omega | ||
| - | = | + | \\ |
| - | 3.6~\Omega. | + | &= |
| + | 3.6~\Omega | ||
| \end{align*} | \end{align*} | ||
| - | \] | + | </ |
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | R_{\rm k} &= 2.4~\Omega | ||
| + | \\ | ||
| + | X_{\rm k} &= 3.6~\Omega | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | The primary current magnitude | + | 4. Calculate the primary |
| - | + | <WRAP group> | |
| - | \[ | + | <WRAP half column rightalign> |
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For an ideal transformer, | ||
| \begin{align*} | \begin{align*} | ||
| I_{1{\rm N}} | I_{1{\rm N}} | ||
| = | = | ||
| \frac{I_{2{\rm N}}}{n} | \frac{I_{2{\rm N}}}{n} | ||
| - | = | + | \end{align*} |
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm N}} | ||
| + | &= | ||
| \frac{5.0~{\rm A}}{10} | \frac{5.0~{\rm A}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.50~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_{1{\rm N}}=0.50~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Estimate the magnitude of the internal voltage drop $U_{\rm k}\approx |\underline{Z}_{\rm k}|I_{1{\rm N}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | First calculate the magnitude of the short-circuit impedance: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| = | = | ||
| - | 0.50~{\rm A}. | + | \sqrt{R_{\rm k}^2+X_{\rm k}^2} |
| \end{align*} | \end{align*} | ||
| - | \] | ||
| - | The magnitude of the short-circuit impedance is | + | Insert |
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | &= | ||
| + | \sqrt{(2.4~\Omega)^2+(3.6~\Omega)^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.33~\Omega | ||
| + | \end{align*} | ||
| - | \[ | + | Now calculate the internal voltage drop: |
| + | \begin{align*} | ||
| + | U_{\rm k} | ||
| + | & | ||
| + | |\underline{Z}_{\rm k}|I_{1{\rm N}} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.33~\Omega\cdot 0.50~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 2.17~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | This is a primary-side voltage drop. On the secondary side: | ||
| + | \begin{align*} | ||
| + | \frac{2.17~{\rm V}}{10} | ||
| + | = | ||
| + | 0.217~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | For a $23~{\rm V}$ actuator supply this is small but not zero. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| &= 4.33~\Omega | ||
| + | \\ | ||
| + | U_{\rm k} & | ||
| + | \end{align*} | ||
| + | |||
| + | Secondary-side equivalent: | ||
| + | \begin{align*} | ||
| + | U_{\rm k,2}\approx 0.217~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the rated primary data | ||
| + | |||
| + | \begin{align*} | ||
| + | U_{1{\rm N}}=230~{\rm V}, | ||
| + | \qquad | ||
| + | I_{1{\rm N}}=2.0~{\rm A}. | ||
| + | \end{align*} | ||
| + | |||
| + | The short-circuit equivalent impedance referred to the primary side is | ||
| + | |||
| + | \begin{align*} | ||
| + | R_{\rm k}=1.5~\Omega, | ||
| + | \qquad | ||
| + | X_{\rm k}=4.0~\Omega. | ||
| + | \end{align*} | ||
| + | |||
| + | |||
| + | 1. Calculate $|\underline{Z}_{\rm k}|$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The short-circuit impedance magnitude is: | ||
| \begin{align*} | \begin{align*} | ||
| |\underline{Z}_{\rm k}| | |\underline{Z}_{\rm k}| | ||
| = | = | ||
| \sqrt{R_{\rm k}^2+X_{\rm k}^2} | \sqrt{R_{\rm k}^2+X_{\rm k}^2} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | &= | ||
| + | \sqrt{(1.5~\Omega)^2+(4.0~\Omega)^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.27~\Omega | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}|=4.27~\Omega | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Calculate the rated short-circuit voltage $U_{1{\rm k}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The primary voltage required to drive rated current through the short-circuited transformer is: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} | ||
| = | = | ||
| - | \sqrt{(2.4~\Omega)^2+(3.6~\Omega)^2} | + | |\underline{Z}_{\rm k}|I_{1{\rm N}} |
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} | ||
| + | &= | ||
| + | 4.27~\Omega\cdot 2.0~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 8.54~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}}=8.54~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Calculate the relative short-circuit voltage ${\rm u_k}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The relative short-circuit voltage is: | ||
| + | \begin{align*} | ||
| + | {\rm u_k} | ||
| = | = | ||
| - | 4.33~\Omega. | + | \frac{U_{1{\rm k}}}{U_{1{\rm N}}}\cdot 100~\% |
| \end{align*} | \end{align*} | ||
| - | \] | ||
| - | Thus the internal voltage drop estimate is | + | Insert |
| + | \begin{align*} | ||
| + | {\rm u_k} | ||
| + | &= | ||
| + | \frac{8.54~{\rm V}}{230~{\rm V}}\cdot 100~\% | ||
| + | \\ | ||
| + | &= | ||
| + | 3.71~\% | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | {\rm u_k}=3.71~\% | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | \[ | + | 4. Calculate the prospective continuous short-circuit current $I_{1{\rm k}}$ for rated primary voltage. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The prospective continuous short-circuit current is: | ||
| \begin{align*} | \begin{align*} | ||
| - | U_{\rm k} | + | I_{1{\rm k}} |
| + | = | ||
| + | I_{1{\rm N}}\cdot \frac{100~\%}{\rm u_k} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}} | ||
| + | &= | ||
| + | 2.0~{\rm A}\cdot \frac{100}{3.71} | ||
| + | \\ | ||
| + | &= | ||
| + | 53.9~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_{1{\rm k}}=53.9~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Calculate the approximate first peak current $i_{\rm peak}\approx 2.54 I_{1{\rm k}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The approximate first peak current is: | ||
| + | \begin{align*} | ||
| + | i_{\rm peak} | ||
| \approx | \approx | ||
| - | |\underline{Z}_{\rm k}|I_{1{\rm N}} | + | 2.54 I_{1{\rm k}} |
| + | \end{align*} | ||
| + | |||
| + | Insert the short-circuit current: | ||
| + | \begin{align*} | ||
| + | i_{\rm peak} | ||
| + | & | ||
| + | 2.54\cdot 53.9~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 137~{\rm A} | ||
| + | \end{align*} | ||
| + | |||
| + | Even though the rated current is only $2.0~{\rm A}$, a short-circuit fault could lead to a much larger current until protection reacts. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | i_{\rm peak}\approx 137~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the turns ratio $n=10$. | ||
| + | |||
| + | The short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.4~\Omega$, | ||
| + | The secondary load current is $I_2=4.0~{\rm A}$. The load has the power factor $\cos\varphi=0.8$ and is inductive. | ||
| + | |||
| + | Estimate the voltage drop on the secondary side using | ||
| + | |||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | \approx | ||
| + | I_1\left(R_{\rm k}\cos\varphi+X_{\rm k}\sin\varphi\right) | ||
| + | \end{align*} | ||
| + | |||
| + | and | ||
| + | |||
| + | \begin{align*} | ||
| + | \Delta U_2\approx \frac{\Delta U_1}{n}. | ||
| + | \end{align*} | ||
| + | |||
| + | 1. Calculate the primary current magnitude $I_1$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The primary current magnitude is approximately: | ||
| + | \begin{align*} | ||
| + | I_1 | ||
| = | = | ||
| - | 4.33~\Omega\cdot 0.50~{\rm A} | + | \frac{I_2}{n} |
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_1 | ||
| + | &= | ||
| + | \frac{4.0~{\rm A}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.40~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_1=0.40~{\rm A} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Determine $\sin\varphi$ for the inductive load. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For an inductive load with $\cos\varphi=0.8$: | ||
| + | \begin{align*} | ||
| + | \sin\varphi | ||
| = | = | ||
| - | 2.17~{\rm V}. | + | \sqrt{1-\cos^2\varphi} |
| \end{align*} | \end{align*} | ||
| - | \] | ||
| - | This is a primary-side voltage drop. On the secondary side it corresponds approximately to | + | Insert the value: |
| + | \begin{align*} | ||
| + | \sin\varphi | ||
| + | &= | ||
| + | \sqrt{1-0.8^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.6 | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \sin\varphi=0.6 | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| - | \[ | + | 3. Estimate the primary-side voltage drop $\Delta U_1$. |
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | Use the Kapp approximation: | ||
| \begin{align*} | \begin{align*} | ||
| - | \frac{2.17~{\rm V}}{10}=0.217~{\rm V}. | + | \Delta U_1 |
| + | & | ||
| + | I_1\left(R_{\rm k}\cos\varphi+X_{\rm k}\sin\varphi\right) | ||
| \end{align*} | \end{align*} | ||
| - | \] | ||
| - | For a \(23~{\rm V}\) actuator supply this is small but not zero. | + | Insert the values: |
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | & | ||
| + | 0.40~{\rm A} | ||
| + | \left( | ||
| + | 2.4~\Omega\cdot 0.8 | ||
| + | + | ||
| + | 3.6~\Omega\cdot 0.6 | ||
| + | \right) | ||
| + | \\ | ||
| + | &= | ||
| + | 0.40~{\rm A} | ||
| + | \left( | ||
| + | 1.92~\Omega+2.16~\Omega | ||
| + | \right) | ||
| + | \\ | ||
| + | &= | ||
| + | 1.63~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_1\approx 1.63~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | 4. Estimate the secondary-side voltage drop $\Delta U_2$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The secondary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | \approx | ||
| + | \frac{\Delta U_1}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | & | ||
| + | \frac{1.63~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.163~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The secondary voltage decreases by approximately $0.16~{\rm V}$ for this operating point. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_2\approx 0.163~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The secondary voltage decreases by approximately $0.16~{\rm V}$. | ||
| # | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the rated primary voltage $U_{1{\rm N}}=230~{\rm V}$. | ||
| + | Its rated primary current is $I_{1{\rm N}}=3.0~{\rm A}$. | ||
| + | |||
| + | At rated voltage and no-load operation, the magnetizing current is approximately $I_{\rm m, | ||
| + | The short-circuit voltage is ${\rm u_k}=6.0~\%$. | ||
| + | |||
| + | Assume that the magnetizing current is approximately proportional to the applied voltage. | ||
| + | \\ \\ \\ | ||
| + | 1. Calculate the short-circuit test voltage $U_{1{\rm k}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The short-circuit test voltage is: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} | ||
| + | = | ||
| + | \frac{\rm u_k}{100~\%}\cdot U_{1{\rm N}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} | ||
| + | &= | ||
| + | 0.06\cdot 230~{\rm V} | ||
| + | \\ | ||
| + | &= | ||
| + | 13.8~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}}=13.8~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Estimate the magnetizing current $I_{\rm m,k}$ during the short-circuit test. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The magnetizing current is assumed to be proportional to the voltage: | ||
| + | \begin{align*} | ||
| + | I_{\rm m,k} | ||
| + | = | ||
| + | I_{\rm m,N}\cdot \frac{U_{1{\rm k}}}{U_{1{\rm N}}} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I_{\rm m,k} | ||
| + | &= | ||
| + | 0.12~{\rm A}\cdot \frac{13.8~{\rm V}}{230~{\rm V}} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.0072~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 7.2~{\rm mA} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I_{\rm m,k} | ||
| + | = | ||
| + | 0.0072~{\rm A} | ||
| + | = | ||
| + | 7.2~{\rm mA} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Compare $I_{\rm m,k}$ with $I_{1{\rm N}}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | Compare the short-circuit magnetizing current with the rated current: | ||
| + | \begin{align*} | ||
| + | \frac{I_{\rm m, | ||
| + | = | ||
| + | \frac{0.0072~{\rm A}}{3.0~{\rm A}} | ||
| + | \end{align*} | ||
| + | |||
| + | Calculate the ratio: | ||
| + | \begin{align*} | ||
| + | \frac{I_{\rm m, | ||
| + | &= | ||
| + | 0.0024 | ||
| + | \\ | ||
| + | &= | ||
| + | 0.24~\% | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \frac{I_{\rm m, | ||
| + | = | ||
| + | 0.24~\% | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Explain why the magnetizing branch can be neglected. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | During the short-circuit test, the applied voltage is much smaller than the rated voltage: | ||
| + | \begin{align*} | ||
| + | U_{1{\rm k}} \ll U_{1{\rm N}} | ||
| + | \end{align*} | ||
| + | |||
| + | Since the magnetizing current is assumed to be approximately proportional to the applied voltage, the magnetizing current is also very small: | ||
| + | \begin{align*} | ||
| + | I_{\rm m, | ||
| + | \end{align*} | ||
| + | |||
| + | Compared with the rated current: | ||
| + | \begin{align*} | ||
| + | I_{1{\rm N}}=3.0~{\rm A} | ||
| + | \end{align*} | ||
| + | |||
| + | the magnetizing current is only $0.24~\%$. | ||
| + | |||
| + | So during the short-circuit test, almost all current flows through the short-circuit path consisting of $R_{\rm k}$ and $X_{\rm k}$. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The magnetizing branch $R_{\rm Fe}\parallel jX_{1{\rm H}}$ can usually be neglected in the short-circuit test. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the turns ratio $n=10$. The short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.0~\Omega$, | ||
| + | |||
| + | The secondary load current is $I_2=5.0~{\rm A}$. The load is ohmic-inductive with $\cos\varphi=0.8$. | ||
| + | |||
| + | The no-load current on the primary side is approximately $I_{10}=0.03~{\rm A}$. | ||
| + | \\ \\ \\ | ||
| + | 1. Calculate the load-related primary current $I' | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The load-related primary current is: | ||
| + | \begin{align*} | ||
| + | I'_2 | ||
| + | = | ||
| + | \frac{I_2}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I'_2 | ||
| + | &= | ||
| + | \frac{5.0~{\rm A}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.50~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Estimate the primary-side voltage drop. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The voltage drop is estimated with: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | \approx | ||
| + | I'_2 | ||
| + | \left( | ||
| + | R_{\rm k}\cos\varphi | ||
| + | + | ||
| + | X_{\rm k}\sin\varphi | ||
| + | \right) | ||
| + | \end{align*} | ||
| + | |||
| + | For $\cos\varphi=0.8$: | ||
| + | \begin{align*} | ||
| + | \sin\varphi | ||
| + | &= | ||
| + | \sqrt{1-\cos^2\varphi} | ||
| + | \\ | ||
| + | &= | ||
| + | \sqrt{1-0.8^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.6 | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | & | ||
| + | 0.50~{\rm A} | ||
| + | \left( | ||
| + | 2.0~\Omega\cdot 0.8 | ||
| + | + | ||
| + | 4.0~\Omega\cdot 0.6 | ||
| + | \right) | ||
| + | \\ | ||
| + | &= | ||
| + | 0.50~{\rm A} | ||
| + | \left( | ||
| + | 1.6~\Omega+2.4~\Omega | ||
| + | \right) | ||
| + | \\ | ||
| + | &= | ||
| + | 2.0~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_1\approx 2.0~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Calculate the secondary-side voltage drop $\Delta U_2\approx \frac{\Delta U_1}{n}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The secondary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | \approx | ||
| + | \frac{\Delta U_1}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | & | ||
| + | \frac{2.0~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.20~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_2\approx 0.20~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Estimate an upper bound for the neglected voltage drop caused by $I_{10}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | First calculate the magnitude of the short-circuit impedance: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | = | ||
| + | \sqrt{R_{\rm k}^2+X_{\rm k}^2} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| | ||
| + | &= | ||
| + | \sqrt{(2.0~\Omega)^2+(4.0~\Omega)^2} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.47~\Omega | ||
| + | \end{align*} | ||
| + | |||
| + | The upper bound for the voltage drop caused by the no-load current is: | ||
| + | \begin{align*} | ||
| + | \Delta U_{1,10} | ||
| + | &\leq | ||
| + | |\underline{Z}_{\rm k}|I_{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 4.47~\Omega\cdot 0.03~{\rm A} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.134~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | On the secondary side: | ||
| + | \begin{align*} | ||
| + | \Delta U_{2,10} | ||
| + | &\leq | ||
| + | \frac{0.134~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.0134~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | |\underline{Z}_{\rm k}| &= 4.47~\Omega | ||
| + | \\ | ||
| + | \Delta U_{1,10} &\leq 0.134~{\rm V} | ||
| + | \\ | ||
| + | \Delta U_{2,10} &\leq 0.0134~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Decide whether the short-circuit equivalent circuit is sufficient for this load estimate. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The load-related secondary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_2\approx 0.20~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The estimated neglected secondary-side voltage drop caused by the no-load current is at most: | ||
| + | \begin{align*} | ||
| + | \Delta U_{2, | ||
| + | \end{align*} | ||
| + | |||
| + | This is small compared with the load-related drop of $0.20~{\rm V}$. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | For this engineering estimate, the short-circuit equivalent circuit is sufficient. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | # | ||
| + | |||
| + | |||
| + | # | ||
| + | # | ||
| + | |||
| + | A transformer has the rated primary voltage of $U_1=230~{\rm V}$ and and the turns ratio $n=10$. A resistive load draws $I_2=4.0~{\rm A}$. \\ | ||
| + | For the real transformer, | ||
| + | The iron loss is approximately $P_{\rm Fe}=1.5~{\rm W}$. \\ | ||
| + | Assume a resistive load with $\cos\varphi=1$. | ||
| + | \\ \\ | ||
| + | 1. Calculate the ideal secondary voltage $U_{2,\rm ideal}$. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For the ideal transformer: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm ideal} | ||
| + | = | ||
| + | \frac{U_1}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm ideal} | ||
| + | &= | ||
| + | \frac{230~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 23.0~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | U_{2,\rm ideal}=23.0~{\rm V} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 2. Calculate the load-related primary current $I' | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The load-related primary current is: | ||
| + | \begin{align*} | ||
| + | I'_2 | ||
| + | = | ||
| + | \frac{I_2}{n} | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | I'_2 | ||
| + | &= | ||
| + | \frac{4.0~{\rm A}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.40~{\rm A} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | I' | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 3. Estimate the real secondary voltage. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For a resistive load, the approximate primary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | \approx | ||
| + | I' | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | \Delta U_1 | ||
| + | & | ||
| + | 0.40~{\rm A}\cdot 2.4~\Omega | ||
| + | \\ | ||
| + | &= | ||
| + | 0.96~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The corresponding secondary-side voltage drop is: | ||
| + | \begin{align*} | ||
| + | \Delta U_2 | ||
| + | & | ||
| + | \frac{\Delta U_1}{n} | ||
| + | \\ | ||
| + | &= | ||
| + | \frac{0.96~{\rm V}}{10} | ||
| + | \\ | ||
| + | &= | ||
| + | 0.096~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | Thus the real secondary voltage is approximately: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm real} | ||
| + | & | ||
| + | 23.0~{\rm V}-0.096~{\rm V} | ||
| + | \\ | ||
| + | &= | ||
| + | 22.90~{\rm V} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | \Delta U_1 & | ||
| + | \\ | ||
| + | \Delta U_2 & | ||
| + | \\ | ||
| + | U_{2,\rm real} & | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 4. Estimate the copper losses. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | The copper losses are: | ||
| + | \begin{align*} | ||
| + | P_{\rm Cu} | ||
| + | \approx | ||
| + | R_{\rm k}(I' | ||
| + | \end{align*} | ||
| + | |||
| + | Insert the values: | ||
| + | \begin{align*} | ||
| + | P_{\rm Cu} | ||
| + | & | ||
| + | 2.4~\Omega\cdot (0.40~{\rm A})^2 | ||
| + | \\ | ||
| + | &= | ||
| + | 0.384~{\rm W} | ||
| + | \end{align*} | ||
| + | |||
| + | The real transformer also has iron losses: | ||
| + | \begin{align*} | ||
| + | P_{\rm Fe}=1.5~{\rm W} | ||
| + | \end{align*} | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | \begin{align*} | ||
| + | P_{\rm Cu}\approx 0.384~{\rm W} | ||
| + | \end{align*} | ||
| + | |||
| + | Additionally: | ||
| + | \begin{align*} | ||
| + | P_{\rm Fe}=1.5~{\rm W} | ||
| + | \end{align*} | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| + | 5. Compare ideal and real transformer behavior. | ||
| + | <WRAP group> | ||
| + | <WRAP half column rightalign> | ||
| + | # | ||
| + | <WRAP leftalign> | ||
| + | For the ideal transformer: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm ideal}=23.0~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | For the real transformer: | ||
| + | \begin{align*} | ||
| + | U_{2,\rm real}\approx 22.90~{\rm V} | ||
| + | \end{align*} | ||
| + | |||
| + | The real transformer has copper losses and iron losses: | ||
| + | \begin{align*} | ||
| + | P_{\rm Cu}& | ||
| + | \\ | ||
| + | P_{\rm Fe}& | ||
| + | \end{align*} | ||
| + | |||
| + | So the main differences are: | ||
| + | |||
| + | * the ideal transformer has exactly $U_2=23.0~{\rm V}$, the real transformer has a slightly lower voltage, | ||
| + | * the ideal transformer has no losses, the real transformer has copper and iron losses, | ||
| + | * the ideal transformer has no leakage voltage drop, the real transformer has a load-dependent voltage drop. | ||
| + | |||
| + | For this operating point the transformer is close to ideal, but not exactly ideal. | ||
| + | </ | ||
| + | # | ||
| + | </ | ||
| + | <WRAP half column> | ||
| + | # | ||
| + | The real transformer differs from the ideal transformer by: | ||
| + | |||
| + | * a slightly lower secondary voltage, | ||
| + | * copper and iron losses, | ||
| + | * a load-dependent voltage drop. | ||
| + | |||
| + | For this operating point it is close to ideal, but not exactly ideal. | ||
| + | # | ||
| + | </ | ||
| + | </ | ||
| + | |||
| # | # | ||
| Line 1381: | Line 2954: | ||
| * **Mixing peak values and RMS values:** In AC power and transformer ratings, \(U\) and \(I\) usually mean RMS values. Time functions are written \(u(t)\), \(i(t)\). Instantaneous short-circuit peaks are written here as \(i_{\rm p}\). | * **Mixing peak values and RMS values:** In AC power and transformer ratings, \(U\) and \(I\) usually mean RMS values. Time functions are written \(u(t)\), \(i(t)\). Instantaneous short-circuit peaks are written here as \(i_{\rm p}\). | ||
| * **Confusing reluctance and resistance: | * **Confusing reluctance and resistance: | ||
| - | * **Confusing \(n\) and the technical no-load voltage ratio \(\ddot{u}\): | + | * **Confusing \(n\) and the technical no-load voltage ratio \(\ddot{\rm u}\):** The ideal ratio is \(n=\frac{N_1}{N_2}\). The measured no-load voltage ratio is close to \(n\), but not exactly equal for a real transformer. |
| * **Forgetting the square when referring impedances: | * **Forgetting the square when referring impedances: | ||
| * **Ignoring leakage reactance: | * **Ignoring leakage reactance: | ||
| - | * **Treating \(\rm u_k\) as a voltage in volts:** \(u_{\rm k}\) is normally given in percent. Insert it consistently in formulas. | + | * **Treating \(\rm u_k\) as a voltage in volts:** \(\rm u_k\) is normally given in percent. Insert it consistently in formulas. |
| * **Using \(2.54\) as a universal law:** The first short-circuit peak depends on the \(R/X\) ratio and on the switching instant. The factor \(2.54\) is an approximation. | * **Using \(2.54\) as a universal law:** The first short-circuit peak depends on the \(R/X\) ratio and on the switching instant. The factor \(2.54\) is an approximation. | ||
| * **Opening a current transformer secondary: | * **Opening a current transformer secondary: | ||