Table of Contents

Block 09/10 — Transformers and Magnetic Coupling

Learning objectives

After this 90-minute block, you can

\[ \begin{align*} \frac{\underline{U}_1^\phantom{O}}{\underline{U}_2^\phantom{O}}=\frac{N_1}{N_2}=n, \qquad \frac{\underline{I}_1}{\underline{I}_2}=-\frac{1}{n} \end{align*} \] with a clear sign convention.

Preparation at Home

Well, again

For checking your understanding please do the quick checks in the exercise section.

90-minute plan

Conceptual overview

  • A transformer is not a DC component. It needs a changing magnetic flux. In normal operation this is usually a sinusoidal flux created by AC voltage.
  • The transformer does not “create power”. Ideally, it trades voltage for current:

\[ \begin{align*} \text{higher voltage} \quad \Longleftrightarrow \quad \text{lower current} \end{align*} \]

  • The link between the two windings is the magnetic field in the iron core. This continues directly from EEE1:
    • induction explains why a changing flux induces voltage.
    • magnetic circuits explains why the iron core guides the flux.
    • inductance explains how flux linkage and current are connected.
  • Mutual inductance \(M\) measures how strongly one coil “notices” the changing current in another coil.
  • A real transformer is almost ideal, but not quite:
    • \(R_1, R_2\): copper losses in the windings.
    • \(L_{1\sigma}, L_{2\sigma}\): leakage flux that does not couple both windings.
    • \(R_{\rm Fe}\): iron losses in the core.
    • \(L_{\rm H}\): main magnetizing inductance needed to create the main flux.
  • In engineering, transformer data such as \(\rm u_k\) are not abstract: they determine voltage drop, fault current, thermal stress, and protection design.

Core content

Short Review of the Flux

In EEE1 we considered magnetic flux \(\Phi\), flux linkage / linked flux \(\Psi\), and induction.
For one coil with \(N\) turns the flux linkage is

\[ \begin{align*} \Psi = N\Phi . \end{align*} \]

Faraday's law gives

\[ \begin{align*} u(t)=\frac{{\rm d}\Psi}{{\rm d}t}=N\frac{{\rm d}\Phi}{{\rm d}t}. \end{align*} \]

(Be aware of Lenz law: Here u(t) is the terminal voltage according to the chosen voltage reference arrow. The induced voltage $u_{\rm ind}$ according to Faraday–Lenz would have the opposite sign)
In sinusoidal steady state this becomes the phasor equation

\[ \begin{align*} \underline{U}=j\omega\underline{\Psi}=j\omega N\underline{\Phi}. \end{align*} \]

This is the starting point for the transformer.

Polarity and the dot convention

Before we start with the transformer, we have to look at a common convention for the orientation of two coils to each other.

Fig. 1: Dot convention: the dots indicate corresponding winding ends. electrical_engineering_and_electronics_2:directionofcoupling.svg

Rule of thumb

Ideal single-phase transformer

electrical_engineering_and_electronics_2:ideal_transformer.svg

For an ideal transformer we assume:

Let \(N_1\) be the number of turns of the primary winding and \(N_2\) the number of turns of the secondary winding.

\[ \begin{align*} \underline{\Psi}_1 &= N_1\underline{\Phi}, & \underline{U}_1 &= j\omega\underline{\Psi}_1 = j\omega N_1\underline{\Phi}, \\ \underline{\Psi}_2 &= N_2\underline{\Phi}, & \underline{U}_2 &= j\omega\underline{\Psi}_2 = j\omega N_2\underline{\Phi}. \end{align*} \]

Dividing the two voltage equations gives the turns ratio

\[ \begin{align*} \boxed{ \frac{\underline{U}_1^\phantom{O}}{\underline{U}_2^\phantom{O}} = \frac{N_1}{N_2} = n } \end{align*} \]

with

\[ \begin{align*} n=\frac{N_1}{N_2}. \end{align*} \]

Remember: ideal transformer ratios

With the indicated reference arrows and a lossless transformer, the resulting complex power as a sum of input and output power $\underline{S}$ must be zero:

\[ \begin{align*} \underline{S}_1+\underline{S}_2= \underline{U}_1\underline{I}^*_1+\underline{U}_2\underline{I}^*_2=0 \end{align*} \]

and therefore

\[ \begin{align*} \boxed{ \frac{\underline{I}_1}{\underline{I}_2} = -\frac{\underline{U}_2^\phantom{O}}{\underline{U}_1^\phantom{O}} = -\frac{N_2}{N_1} = -\frac{1}{n} } \end{align*} \]

The minus sign is not a “loss”. It is caused by the chosen current arrows.
The primary side absorbs power while the secondary side delivers power to the load.

Analogy: gearbox for voltage and current

An ideal transformer behaves like a lossless gearbox:

  • a gearbox can trade speed for torque,
  • a transformer can trade voltage for current.

For a step-down transformer:

\[ \begin{align*} \text{lower voltage} \quad \Longleftrightarrow \quad \text{higher current}. \end{align*} \]

The power is ideally conserved, just as mechanical power is ideally conserved in a lossless gearbox.

Physical interpretation

  • If \(N_2<N_1\), the transformer steps the voltage down: \(U_2<U_1\).
  • At the same time, the secondary current can be higher: \(I_2>I_1\).
  • This is useful in robotics power supplies: a mains-side transformer or isolated converter stage may reduce voltage while increasing available current for actuators.

Exercise E1 step-down transformer for a robot controller

A transformer has \(N_1=800\) turns and \(N_2=80\) turns. The primary RMS voltage is \(U_1=230~{\rm V}\).

\[ \begin{align*} n &= \frac{N_1}{N_2} = \frac{800}{80} =10, \\ U_2 &= \frac{U_1}{n} = \frac{230~{\rm V}}{10} =23~{\rm V}. \end{align*} \]

If the secondary side supplies \(I_2=4~{\rm A}\), the ideal primary current magnitude is

\[ \begin{align*} I_1 &= \frac{I_2}{n} = \frac{4~{\rm A}}{10} =0.4~{\rm A}. \end{align*} \]

The apparent power is equal on both sides:

\[ \begin{align*} S_1 &= U_1I_1=230~{\rm V}\cdot 0.4~{\rm A}=92~{\rm VA}, \\ S_2 &= U_2I_2=23~{\rm V}\cdot 4~{\rm A}=92~{\rm VA}. \end{align*} \]

Linked fluxes and mutual inductance

For a single coil we already know that its flux linkage $\Psi = N\Phi$ is proportional to the current $i$ through the coil

\[ \begin{align*} \Psi=L i \end{align*} \]

\[ \begin{align*} \underline{\Psi}=L \underline{I} . \end{align*} \]

For two coupled coils $1$ and $2$, each flux linkage $\underline{\Psi}_1 = N\underline{\Phi}_1$ and $\underline{\Psi}_2 = N\underline{\Phi}_2$ depend on both currents $\underline{I}_1$ and $\underline{I}_2$.

electrical_engineering_and_electronics_2:ideal_transformer01.svg

Not only the current through the coil generates a part of the flux linkage, but also the other coil provides a part for the flux linkage.

\[ \begin{align*} \underline{\Psi}_1 &= \underbrace{{\color{green}{L_{11}\underline{I}_1}}}_{\text{self-linkage of coil 1}} + \underbrace{{\color{blue}{M_{12}\underline{I}_2}}}_{\text{mutual linkage from coil 2}}, \\[4pt] \underline{\Psi}_2 &= \underbrace{{\color{blue}{M_{21}\underline{I}_1}}}_{\text{mutual linkage from coil 1}} + \underbrace{{\color{green}{L_{22}\underline{I}_2}}}_{\text{self-linkage of coil 2}}. \end{align*} \]

For most transformer calculations we use the symmetric case of the mutual inductances.
(this is true for passive, stationary, and reciprocal situations, like transformers, but not necessarily for motors or complex setups)

\[ \begin{align*} {\color{blue}{M_{12}}}={\color{blue}{M_{21}}}={\color{blue}{M}}. \end{align*} \]

Often, the self-inductances are abbreviated: \[ \begin{align*} \color{green}{L_{11}} \rightarrow \color{green}{L_{1}} \\ \color{green}{L_{22}} \rightarrow \color{green}{L_{2}} \\ \end{align*} \]

Then

\[ \begin{align*} \boxed{ \begin{pmatrix} \underline{\Psi}_1\\ \underline{\Psi}_2 \end{pmatrix} = \begin{pmatrix} {\color{green}{L_{1}}} & {\color{blue}{M}}\\ {\color{blue}{M}} & {\color{green}{L_{2}}} \end{pmatrix} \begin{pmatrix} \underline{I}_1\\ \underline{I}_2 \end{pmatrix} } \end{align*} \]

and

\[ \begin{align*} M=k\sqrt{L_{1}L_{2}}. \end{align*} \]

Here \(k\) is the coupling coefficient. In the shown transformer \(k\) is 1 since all flux from $1$ flows through $2$ and vice versa.
In reality that is not the case as explained in the next chapters.

Coupling coefficient Interpretation Typical example
\(k=0\) no useful flux from one coil links the other coil coils far apart
\(0<k<1\) partial coupling wireless charger with air gap or misalignment
\(k\approx 1\) almost all useful flux links both coils transformer with iron core
Tab. 1: Meaning of the coupling coefficient \(k\)



The mutual inductance \(M\) answers the question:

How much flux linkage appears in coil \(2\) when the current in coil \(1\) changes?


Engineering example: wireless charging

In wireless charging, the transmitter coil and receiver coil are separated by an air gap. The coupling coefficient \(k\) is much smaller than in a transformer with an iron core.

If the receiver is misaligned, less flux from the transmitter passes through it. Then \(M\) decreases, the induced voltage decreases, and the transmitted power decreases.

Analogy: shared bed sheet

Imagine two people lying on a bed holding the same bed sheet at different positions.

  • \(L_{1}\):
    how strongly winding 1 couples its current into the shared magnetic path,
    like person 1 moving the sheet at their hand.
  • \(L_{2}\):
    how strongly winding 2 couples its current into the shared magnetic path,
    like person 2 moving the sheet at their hand.
  • \(M\):
    how strongly the motion from one hand is felt at the other hand through the same sheet.

In transformer language, \(L_{1}\) and \(L_{2}\) describe each winding's connection to the shared main flux path.
The mutual inductance \(M\) describes the transfer between the two windings through this shared path.

voltages by mutual inductances and resistances

For positive coupling, we get the following complex representation (since $u(t) = L\frac{{\rm d}i}{{\rm d}t} \: \longrightarrow \:\underline{U}=j\omega L \underline{I}$):

\[ \begin{align*} \underline{U}_1 &= R_1 \underline{I}_1 + {\color{green} {j\omega L_{1} \underline{I}_1 }} + {\color{blue}{j\omega M \underline{I}_2 }}, \\[4pt] \underline{U}_2 &= R_2 \underline{I}_2 + {\color{blue} {j\omega M \underline{I}_1 }} + {\color{green}{j\omega L_{2} \underline{I}_2 }}. \end{align*} \]
For negative coupling, the sign of the \(M\)-term changes in the chosen equation system, see figure 2 and figure 3.

Fig. 2: Positive coupling: currents enter corresponding dotted terminals. electrical_engineering_and_electronics_2:poscoupling.svg

Fig. 3: Negative coupling: only one current enters a dotted terminal. electrical_engineering_and_electronics_2:negcoupling.svg

Tunnel Analogy for AC circuits

The dots are like matching openings for magnetic action.
A positive reference current (e.g. $i_1$) entering the dotted terminal of one winding produces a positive induced voltage (e.g. aligned with $u_2$) at the dotted terminal of the other winding.
With only a load $R_2$ connected to the secondary side, this voltage tends to drive current out of the dotted terminal into the load.

Stray and Leakage

The image of the ideal transformer shall be consecutively developed to a more realistic transformer model.
To do so, we look at the situation of two coils near each other and expand this formula for the induced voltage.

Fig. 4: Mutual induction of two coils: only part of the flux created by coil \(1\) links coil \(2\). electrical_engineering_and_electronics_2:mutualinductiontwocoils1.svg

The flux created by coil \(1\) can be split into

\[ \begin{align*} \Phi_{11} = {\color{blue}{\Phi_{21}}} + {\color{orange}{\Phi_{1 \rm \sigma}}}. \end{align*} \]

For an example, we will have a look at the instantaneous voltage induced in coil \(2\):

\[ \begin{align*} u_{2,\rm ind}(t) = \frac{{\rm d}{\color{blue}{\Psi_{21}}}}{{\rm d}t} = N_2\frac{{\rm d}{\color{blue}{\Phi_{21}}}}{{\rm d}t}. \end{align*} \]

The complex voltage induced in coil \(2\) is

\[ \begin{align*} \underline{U}_{2} = j\omega {\color{blue}{ \underline{\Psi}_{21} }} = j\omega N_2 {\color{blue}{ \underline{\Phi}_{21} }} . \end{align*} \]



Analogies

Analogy 1: two pendulums connected by a spring
Imagine two pendulums connected by a weak spring.

  • If pendulum \(1\) moves, the spring can make pendulum \(2\) move as well.
  • A strong spring transfers the motion strongly.
  • A weak spring transfers the motion only weakly.
  • If the spring is missing, pendulum \(2\) does not react.

For coupled coils:

  • the changing motion corresponds to changing current,
  • the spring corresponds to the magnetic coupling,
  • the motion transferred to the second pendulum corresponds to the induced voltage,
  • weak coupling means that only a small part of the magnetic flux links both coils.

Analogy 2: a leaky magnetic pipe
The magnetic core can be imagined as a pipe guiding magnetic flux.

  • A good iron core is like a wide, low-resistance pipe: most flux reaches the second coil.
  • A large air gap is like a narrow, difficult path: less flux reaches the second coil.
  • Leakage flux is like flow escaping through side paths: it belongs to the first coil but does not help the second coil.

This image is helpful for transformers, wireless charging coils, and current sensors.

Engineering examples

  • Transformer: very strong coupling because the iron core guides most of the flux through both windings.
  • Wireless charger: weaker coupling because the flux must cross an air gap and the coils may be misaligned.
  • Current transformer: the measured conductor acts like a one-turn primary winding; the secondary winding detects the changing magnetic field.
  • Relay coil near signal wiring: unwanted coupling can induce noise voltages in nearby loops.

Real transformer: leakage and losses

In a real transformer, not all flux links both windings.

The leakage flux can be interpreted as an additional virtual branch in the mechanical setup, see figure 5.

Fig. 5: Main flux and leakage fluxes in a real transformer. electrical_engineering_and_electronics_2:real_transformer.svg

The total main flux linking is given by (see figure 5) \[ \begin{align*} \underline{\Phi}_{1 \rm H} = \underline{\Phi}_{21} + \underline{\Phi}_{12} = \underline{\Phi}_{\rm H} \\[4pt] \underline{\Phi}_{2 \rm H} = \underline{\Phi}_{21} + \underline{\Phi}_{12} = \underline{\Phi}_{\rm H} \end{align*} \]

For the flux linkage also the leakage flux has to be considered: \[ \begin{align*} \underline{\Psi}_{1} =N_1 ( \underline{\Phi}_{21} + \underline{\Phi}_{12} + \underline{\Phi}_{1\sigma}) \\[4pt] \underline{\Psi}_{2} =N_2 ( \underline{\Phi}_{21} + \underline{\Phi}_{12} + \underline{\Phi}_{2\sigma}) \end{align*} \]

The real flux linkage equations become

\[ \begin{align*} \underline{\Psi}_1 &= \underbrace{{\color{blue }{L_{1{\rm H}}\underline{I}_1 + M\underline{I}_2}} }_{\text{main magnetic path}} + \underbrace{{\color{orange}{L_{1\sigma }\underline{I}_1}} }_{\text{primary leakage} }, \\[4pt] \underline{\Psi}_2 &= \underbrace{{\color{blue }{M\underline{I}_1 + L_{2{\rm H}}\underline{I}_2 }} }_{\text{main magnetic path}} + \underbrace{{\color{orange}{L_{2\sigma }\underline{I}_2}} }_{\text{secondary leakage} }. \end{align*} \]

Equivalently,

\[ \begin{align*} \underline{\Psi}_1 &= L_1\underline{I}_1+M\underline{I}_2, & L_1&=L_{1{\rm H}}+L_{1\sigma}, \\ \underline{\Psi}_2 &= L_2\underline{I}_2+M\underline{I}_1, & L_2&=L_{2{\rm H}}+L_{2\sigma}. \end{align*} \]

The winding resistances \(R_1\) and \(R_2\) cause copper losses:

\[ \begin{align*} P_{\rm Cu,1}=R_1I_1^2, \qquad P_{\rm Cu,2}=R_2I_2^2. \end{align*} \]

\[ \begin{align*} \underline{U}_1 &= \underbrace{{\color{red}{R_1\underline{I}_1}}}_{\text{primary copper drop}} + \underbrace{{\color{orange}{j\omega L_{1\sigma}\underline{I}_1}}}_{\text{primary leakage drop}} + \underbrace{{\color{blue}{j\omega L_{1{\rm H}}\underline{I}_1+j\omega M\underline{I}_2}}}_{\text{main magnetic coupling}}, \\[6pt] \underline{U}_2 &= \underbrace{{\color{red}{R_2\underline{I}_2}}}_{\text{secondary copper drop}} + \underbrace{{\color{orange}{j\omega L_{2\sigma}\underline{I}_2}}}_{\text{secondary leakage drop}} + \underbrace{{\color{blue}{j\omega L_{2{\rm H}}\underline{I}_2+j\omega M\underline{I}_1}}}_{\text{main magnetic coupling}}. \end{align*} \]

Based, on the block19 and block20 of last semester, the inductances can be calculated by the reluctance $R_{\rm mFe}$ of the iron core and the number of turns $N_1$, $N_2$:

\[ \begin{align*} \boxed{ L_{1 \rm H} = \frac{N_1^2}{R_{\rm mFe} } \\ L_{2 \rm H} = \frac{N_2^2}{R_{\rm mFe} } \\ M = \frac{N_1 N_2}{R_{\rm mFe} } \\ } \end{align*} \]

Color scheme for the equivalent equations

In the previous formulas:

  • red terms:
    winding resistance and copper loss, which convert electrical energy into heat.
  • orange terms:
    leakage flux, which is unwanted but unavoidable, because magnetic field lines can also close through the surrounding air.
  • blue terms:
    useful main magnetic coupling, which is responsible for transformer action.

Analogy: useful road and side roads

Think of the main flux as traffic on the useful road between two cities. Traffic on side roads still exists, but it does not help transport goods between the two cities.

  • main flux: useful road between primary and secondary winding,
  • leakage flux: side roads that return locally,
  • winding resistance: friction that turns useful energy into heat.

Reduced equivalent circuit referred to the primary side

Since we know, that we can transform the current and voltage by the transformer, we can use this also to simplify the circuit.

Fig. 6: equivalent circuit of a real transformer electrical_engineering_and_electronics_2:reduced_eq_circuit.svg

For calculations it is convenient to move all secondary-side quantities to the primary side.
This is called referring or transforming the secondary side to the primary side.

\[ \begin{align*} \boxed{ \underline{U}'_2=n\underline{U}_2 } \qquad \boxed{ \underline{I}'_2=\frac{1}{n}\underline{I}_2 } \end{align*} \]

The secondary resistance and leakage reactance are transformed by \(n^2\) since $R = U / I$:

\[ \begin{align*} \boxed{ R'_2=n^2R_2 } \qquad \boxed{ X'_{2\sigma}=n^2X_{2\sigma} } \end{align*} \]

Fig. 7: reduced equivalent circuit of a real transformer electrical_engineering_and_electronics_2:reduced_eq_circuit02.svg

In the reduced equivalent circuit:

The phasor diagram is shown in figure 8.

Fig. 8: phasor diagram of a real transformer electrical_engineering_and_electronics_2:phasor_real_trafo01.svg

Why the reduced circuit is useful

Once all quantities are referred to one side, the transformer can be calculated like an AC network with impedances.
This uses the same method as complex network calculation: replace components by impedances and apply Kirchhoff's laws.

No-load operation of the real transformer

No-load operation means that the secondary side is open:

\[ \begin{align*} \underline{I}_2=0. \end{align*} \]

The primary side still draws a small no-load current \(\underline{I}_{10}\). This current has two parts:

\[ \begin{align*} \underline{I}_{10} = \underline{I}_{\rm Fe} + \underline{I}_{\rm m}. \end{align*} \]

Fig. 9: No-load phasor diagram: the no-load current is the sum of iron-loss current and magnetizing current. electrical_engineering_and_electronics_2:block09_no_load_phasor_diagram.svg

The technical voltage ratio is often defined from the no-load voltages. Here it is denoted by \(\ddot{\rm u}\):

\[ \boxed{ \begin{align*} \ddot{\rm u} = \frac{\text{higher voltage}}{\text{lower voltage}} \bigg|_{\rm no~load}. \end{align*} } \]

For a step-down transformer:

\[ \begin{align*} \ddot{\rm u} = \frac{U_{1{\rm N}}}{U_{20}}. \end{align*} \]

Here \(U_{1{\rm N}}\) is the rated primary voltage and \(U_{20}\) is the open-circuit secondary voltage.

Because of real voltage drops and magnetizing effects,

\[ \begin{align*} \ddot{\rm u}\neq n, \end{align*} \]

but for many practical transformers

\[ \begin{align*} \ddot{\rm u}\approx n. \end{align*} \]

Short-circuit operation of the real transformer

In the short-circuit test, the secondary side is shorted, so $\underline{U}_2=0$.
The primary voltage $\underline{U}_1$ is increased only until rated current flows.
Because the short-circuit impedance is small, this requires only a small fraction of the rated primary voltage.
Therefore the main flux and the magnetizing current are small, so the magnetizing branch can usually be neglected.

\[ \begin{align*} \Big|\; jX_{1{\rm H}} \; || \;R_{\rm Fe} \;\Big| \;\; \gg \;\; \Big|\; jX_{1\sigma} + \;R_1 + jX'_{2\sigma} + \;R'_2 \;\Big| . \end{align*} \]

Fig. 10: Short-circuit equivalent circuit of a real transformer. electrical_engineering_and_electronics_2:block09_short_circuit_equivalent_circuit.svg

This gives the short-circuit equivalent circuit with

\[ \begin{align*} \boxed{ R_{\rm k}=R_1+R'_2 } \qquad \boxed{ X_{\rm k}=X_{1\sigma}+X'_{2\sigma} } \end{align*} \]

and

\[ \begin{align*} \underline{Z}_{\rm k} = R_{\rm k}+jX_{\rm k}. \end{align*} \]

Definition: rated short-circuit voltage

The rated short-circuit voltage \(U_{1{\rm k}}\) is the primary voltage that must be applied while the secondary side is shorted so that rated primary current \(I_{1{\rm N}}\) flows.

As a relative value:

\[ \begin{align*} \boxed{ {\rm u_k} = \frac{U_{1{\rm k}}}{U_{1{\rm N}}}\cdot 100~\% } \end{align*} \]

  • Small \(\rm u_k\) means: small internal impedance.
    When a short-circuit fault on the secondary side happens, the input current can get very high.
  • Large \(\rm u_k\) means: high internal impedance.
    Stronger current limitation, but also larger voltage drop under load.

The continuous short-circuit current for rated primary voltage is

\[ \begin{align*} \boxed{ I_{1{\rm k}} = \frac{U_{1{\rm N}}}{U_{1{\rm k}}}\cdot I_{1{\rm N}} = I_{1{\rm N}}\cdot \frac{100~\%}{{\rm u_k}} } \end{align*} \]

where \(\rm u_k\) is inserted as a percentage value.

Definition: approximation for the first peak current

For a first approximation of the maximum instantaneous current the following formula can be used:

\[ \begin{align*} \boxed{ i_{{\rm peak}} = 2.54 \cdot I_{1 \rm k} } \end{align*} \]

Real transformer under load

Under load, the short-circuit equivalent circuit is often sufficient for engineering estimates.

\[ \begin{align*} \underline{U}_{\rm k} = \left(R_{\rm k}+jX_{\rm k}\right)\underline{I}_1. \end{align*} \]

Fig. 11: Kapp triangle: approximate voltage drop under load using R_k*I and X_k*I. electrical_engineering_and_electronics_2:block09_kapp_triangle.svg

This voltage drop is subtracted vectorially from the primary-side voltage relation.

\[ \begin{align*} \boxed{ \underline{U}_1 - \underline{U}_{\rm k} = \underline{U}'_2 = n \underline{U}_2 } \end{align*} \]

If the magnetizing branch is neglected for the load calculation, then the series current relation is approximately $\underline{I}'_2 \approx -\underline{I}_1$. Therefore the ideal current transformation can still be used as an approximation.

\[ \begin{align*} \boxed{ \frac{\underline{I}_1}{\underline{I}_2} = -\frac{N_2}{N_1} = -\frac{1}{n} } \end{align*} \]

The Kapp triangle (see yellow triangle in figure 11) represents the formula for $\underline{U}_{\rm k}$.

Fig. 12: animation of Kapp triangle

press here for the animation

Engineering use: voltage regulation

In a robot with motors, the supply transformer may show a lower output voltage during high acceleration because the motor currents increase. The Kapp triangle helps estimate this voltage drop. This is important for:

  • selecting transformer size,
  • checking whether the DC link after a rectifier remains high enough,
  • designing fuses and protective devices,
  • avoiding undervoltage resets in control electronics.

Construction types and cooling

Transformer behavior is influenced by construction.

Fig. 13: Transformer types electrical_engineering_and_electronics_2:block09_core_type_transformer.svg

Cooling types:


Mechatronics examples

  • Isolating transformer: safe diagnostic supply for laboratory setups.
  • Control transformer: supplies \(24~{\rm V}\) or similar low-voltage control circuits.
  • Current transformer: measures large motor currents with galvanic isolation.
  • Welding transformer: intentionally high short-circuit voltage and current limitation for welding processes.

Typical technical transformer data

Name / use Typical \({\rm u_k}\) Secondary voltage \(U_2\) Important note
Power transformer \(4\ldots 12~\%\) application-dependent low voltage drop, high fault currents possible
Isolating transformer \(\approx 10~\%\) max. \(250~{\rm V}\) galvanic isolation for safety and measurement
Toy transformer \(\approx 20~\%\) max. \(24~{\rm V}\) current limitation is desired
Doorbell transformer \(\approx 40~\%\) max. \(12~{\rm V}\), often several taps simple robust low-voltage supply
Ignition transformer \(\approx 100~\%\) \(\leq 14~{\rm kV}\) high voltage, limited current
Welding transformer \(\approx 100~\%\) max. \(70~{\rm V}\) large current, strong current limitation
Voltage transformer \(<1~\%\) \(100~{\rm V}\) operate with high load resistance, approximately no-load
Current transformer \(100~\%\) \(0~{\rm V}\) ideal secondary voltage operate with low burden, approximately short-circuit
Tab. 2: Typical transformer types, short-circuit voltage, and secondary voltage



Important safety note: current transformers

A current transformer secondary must not be opened while primary current flows.
If the secondary circuit is open, the transformer tries to maintain the magnetic balance and can generate dangerous high voltages.

Exercises

Exercise E2 Quick check: ideal transformer voltage and current ratio

A transformer has $N_1=1200$ turns and $N_2=300$ turns.
The primary RMS voltage is $U_1=230~{\rm V}$.
The secondary side supplies a load current $I_2=2.0~{\rm A}$.

1. Calculate the turns ratio $n$.

Solution

The turns ratio of an ideal transformer is defined as: \begin{align*} n=\frac{N_1}{N_2} \end{align*}

Insert the given values: \begin{align*} n &= \frac{1200}{300} \\ &= 4 \end{align*}

Result

\begin{align*} n=4 \end{align*}

2. Calculate the ideal secondary voltage $U_2$.

Solution

For an ideal transformer, the voltage ratio follows the turns ratio: \begin{align*} n=\frac{U_1}{U_2} \end{align*}

Therefore: \begin{align*} U_2 &= \frac{U_1}{n} \\ &= \frac{230~{\rm V}}{4} \\ &= 57.5~{\rm V} \end{align*}

Result

\begin{align*} U_2=57.5~{\rm V} \end{align*}

3. Calculate the magnitude of the ideal primary current $I_1$.

Solution

For the ideal transformer, the current ratio is inverse to the voltage ratio: \begin{align*} I_1=\frac{I_2}{n} \end{align*}

Insert the values: \begin{align*} I_1 &= \frac{2.0~{\rm A}}{4} \\ &= 0.50~{\rm A} \end{align*}

Result

\begin{align*} I_1=0.50~{\rm A} \end{align*}

4. State whether this is a step-up or step-down transformer.

Solution

Compare the primary and secondary voltages: \begin{align*} U_1 &= 230~{\rm V} \\ U_2 &= 57.5~{\rm V} \end{align*}

Since \begin{align*} U_2<U_1 \end{align*}

the transformer reduces the voltage.

Result

The transformer is a step-down transformer.

Exercise E3 Quick check: mutual inductance from reluctance

Two coils are wound on the same ideal magnetic core. The main magnetic reluctance is

\begin{align*} R_{\rm mH}=2.0\cdot 10^6~\frac{1}{\rm H}. \end{align*}

The number of turns is $N_1=500$ and $N_2=100$.

1. Calculate $L_{1{\rm H}}$.

Solution

The main-flux inductance of coil 1 is: \begin{align*} L_{1{\rm H}} = \frac{N_1^2}{R_{\rm mH}} \end{align*}

Insert the values: \begin{align*} L_{1{\rm H}} &= \frac{500^2}{2.0\cdot 10^6~1/{\rm H}} \\ &= 0.125~{\rm H} \end{align*}

Result

\begin{align*} L_{1{\rm H}}=0.125~{\rm H} \end{align*}

2. Calculate $L_{2{\rm H}}$.

Solution

The main-flux inductance of coil 2 is: \begin{align*} L_{2{\rm H}} = \frac{N_2^2}{R_{\rm mH}} \end{align*}

Insert the values: \begin{align*} L_{2{\rm H}} &= \frac{100^2}{2.0\cdot 10^6~1/{\rm H}} \\ &= 0.0050~{\rm H} \\ &= 5.0~{\rm mH} \end{align*}

Result

\begin{align*} L_{2{\rm H}} = 0.0050~{\rm H} = 5.0~{\rm mH} \end{align*}

3. Calculate $M$.

Solution

The mutual inductance is: \begin{align*} M = \frac{N_1N_2}{R_{\rm mH}} \end{align*}

Insert the values: \begin{align*} M &= \frac{500\cdot 100}{2.0\cdot 10^6~1/{\rm H}} \\ &= 0.025~{\rm H} \\ &= 25~{\rm mH} \end{align*}

Result

\begin{align*} M = 0.025~{\rm H} = 25~{\rm mH} \end{align*}

4. Check whether the units are correct.

Solution

The reluctance is given in: \begin{align*} [R_{\rm mH}]=\frac{1}{\rm H} \end{align*}

The number of turns is dimensionless. Therefore: \begin{align*} \left[ \frac{N^2}{R_{\rm mH}} \right] = \frac{1}{1/{\rm H}} = {\rm H} \end{align*}

The same argument applies to the mutual inductance: \begin{align*} \left[ \frac{N_1N_2}{R_{\rm mH}} \right] = {\rm H} \end{align*}

Result

The unit is correct because \begin{align*} \frac{1}{1/{\rm H}}={\rm H} \end{align*}

Exercise E4 Mutual inductance and leakage from a magnetic path

Two coils are wound on the same magnetic core. The shared main magnetic path has the reluctance

\begin{align*} R_{\rm mH}=1.6\cdot 10^6~\frac{1}{\rm H}. \end{align*}

The numbers of turns are

\begin{align*} N_1=400, \qquad N_2=100. \end{align*}

The leakage inductances are

\begin{align*} L_{1\sigma}=4.0~{\rm mH}, \qquad L_{2\sigma}=0.30~{\rm mH}. \end{align*}

1. Calculate $L_{1{\rm H}}$.

Solution

The main-flux self-inductance of coil 1 is: \begin{align*} L_{1{\rm H}} = \frac{N_1^2}{R_{\rm mH}} \end{align*}

Insert the values: \begin{align*} L_{1{\rm H}} &= \frac{400^2}{1.6\cdot 10^6~1/{\rm H}} \\ &= 0.100~{\rm H} \end{align*}

Result

\begin{align*} L_{1{\rm H}}=0.100~{\rm H}=100~{\rm mH} \end{align*}

2. Calculate $L_{2{\rm H}}$.

Solution

The main-flux self-inductance of coil 2 is: \begin{align*} L_{2{\rm H}} = \frac{N_2^2}{R_{\rm mH}} \end{align*}

Insert the values: \begin{align*} L_{2{\rm H}} &= \frac{100^2}{1.6\cdot 10^6~1/{\rm H}} \\ &= 0.00625~{\rm H} \\ &= 6.25~{\rm mH} \end{align*}

Result

\begin{align*} L_{2{\rm H}} = 0.00625~{\rm H} = 6.25~{\rm mH} \end{align*}

3. Calculate $M$.

Solution

The mutual inductance is: \begin{align*} M = \frac{N_1N_2}{R_{\rm mH}} \end{align*}

Insert the values: \begin{align*} M &= \frac{400\cdot 100}{1.6\cdot 10^6~1/{\rm H}} \\ &= 0.025~{\rm H} \\ &= 25~{\rm mH} \end{align*}

Result

\begin{align*} M = 0.025~{\rm H} = 25~{\rm mH} \end{align*}

4. Calculate the total self-inductances $L_1$ and $L_2$.

Solution

The total self-inductance is the sum of main-flux inductance and leakage inductance.

For coil 1: \begin{align*} L_1 &= L_{1{\rm H}}+L_{1\sigma} \\ &= 100~{\rm mH}+4.0~{\rm mH} \\ &= 104~{\rm mH} \end{align*}

For coil 2: \begin{align*} L_2 &= L_{2{\rm H}}+L_{2\sigma} \\ &= 6.25~{\rm mH}+0.30~{\rm mH} \\ &= 6.55~{\rm mH} \end{align*}

Result

\begin{align*} L_1 &= 104~{\rm mH} \\ L_2 &= 6.55~{\rm mH} \end{align*}

5. Calculate the coupling coefficient $k=\frac{M}{\sqrt{L_1L_2}}$.

Solution

The coupling coefficient is: \begin{align*} k = \frac{M}{\sqrt{L_1L_2}} \end{align*}

Insert the values in henry: \begin{align*} k &= \frac{0.025~{\rm H}}{\sqrt{0.104~{\rm H}\cdot 0.00655~{\rm H}}} \\ &\approx 0.96 \end{align*}

The coupling is strong, but not ideal, because leakage inductances are present.

Result

\begin{align*} k\approx 0.96 \end{align*}

The coupling is strong, but not ideal.

Exercise E5 Quick check: referring secondary quantities to the primary side

A transformer has $n=5$. The secondary winding resistance is $R_2=0.20~\Omega$ and the secondary leakage reactance is $X_{2\sigma}=0.35~\Omega$.

Calculate the values $R'_2$ and $X'_{2\sigma}$ referred to the primary side.

1. Calculate $R'_2$.

Solution

When a resistance is referred from the secondary side to the primary side, it is multiplied by $n^2$: \begin{align*} R'_2 = n^2R_2 \end{align*}

Insert the values: \begin{align*} R'_2 &= 5^2\cdot 0.20~\Omega \\ &= 25\cdot 0.20~\Omega \\ &= 5.0~\Omega \end{align*}

Result

\begin{align*} R'_2=5.0~\Omega \end{align*}

2. Calculate $X'_{2\sigma}$.

Solution

The secondary leakage reactance is also referred to the primary side by multiplying with $n^2$: \begin{align*} X'_{2\sigma} = n^2X_{2\sigma} \end{align*}

Insert the values: \begin{align*} X'_{2\sigma} &= 5^2\cdot 0.35~\Omega \\ &= 25\cdot 0.35~\Omega \\ &= 8.75~\Omega \end{align*}

Result

\begin{align*} X'_{2\sigma}=8.75~\Omega \end{align*}

3. Check the unit.

Solution

The turns ratio $n$ is dimensionless: \begin{align*} [n]=1 \end{align*}

Therefore, multiplying by $n^2$ does not change the unit: \begin{align*} [R'_2] &= \Omega \\ [X'_{2\sigma}] &= \Omega \end{align*}

Result

The unit remains $\Omega$, because $n$ is dimensionless.

Exercise E6 Quick check: short-circuit voltage and fault current

A transformer has a rated primary current $I_{1{\rm N}}=10~{\rm A}$ and a short-circuit voltage ${\rm u_k}=5~\%$.

1. Calculate the continuous short-circuit current $I_{1{\rm k}}$ when rated primary voltage is applied.

Solution

The short-circuit current can be estimated from the rated current and the relative short-circuit voltage: \begin{align*} I_{1{\rm k}} = I_{1{\rm N}}\cdot \frac{100~\%}{\rm u_k} \end{align*}

Insert the values: \begin{align*} I_{1{\rm k}} &= 10~{\rm A}\cdot \frac{100~\%}{5~\%} \\ &= 200~{\rm A} \end{align*}

Result

\begin{align*} I_{1{\rm k}}=200~{\rm A} \end{align*}

2. Estimate the initial peak short-circuit current $i_{\rm p}$ using $i_{\rm p}\approx 2.54 I_{1{\rm k}}$.

Solution

The initial peak current is estimated by: \begin{align*} i_{\rm p} \approx 2.54\cdot I_{1{\rm k}} \end{align*}

Insert the continuous short-circuit current: \begin{align*} i_{\rm p} &\approx 2.54\cdot 200~{\rm A} \\ &= 508~{\rm A} \end{align*}

The short-circuit current is much larger than the rated current. Protection devices must be selected accordingly.

Result

\begin{align*} i_{\rm p}\approx 508~{\rm A} \end{align*}

Protection devices must be selected accordingly.

Exercise E7 Longer exercise: transformer equivalent circuit for an actuator supply

A single-phase transformer supplies an actuator driver. Rated data and equivalent circuit data are:

\begin{align*} U_{1{\rm N}}&=230~{\rm V}, & U_{2{\rm N}}&=23~{\rm V}, & I_{2{\rm N}}&=5.0~{\rm A}, \\ R_1&=1.2~\Omega, & X_{1\sigma}&=1.8~\Omega, \\ R_2&=0.012~\Omega, & X_{2\sigma}&=0.018~\Omega. \end{align*}

Assume $n=\frac{U_{1{\rm N}}}{U_{2{\rm N}}}$. The magnetizing branch is neglected for the loaded operating point.

1. Calculate $n$.

Solution

The turns ratio is estimated from the rated voltages: \begin{align*} n = \frac{U_{1{\rm N}}}{U_{2{\rm N}}} \end{align*}

Insert the values: \begin{align*} n &= \frac{230~{\rm V}}{23~{\rm V}} \\ &= 10 \end{align*}

Result

\begin{align*} n=10 \end{align*}

2. Refer $R_2$ and $X_{2\sigma}$ to the primary side.

Solution

Secondary quantities are referred to the primary side by multiplying them with $n^2$: \begin{align*} R'_2 &= n^2R_2 \\ X'_{2\sigma} &= n^2X_{2\sigma} \end{align*}

With $n=10$: \begin{align*} R'_2 &= 10^2\cdot 0.012~\Omega \\ &= 1.2~\Omega \\[4pt] X'_{2\sigma} &= 10^2\cdot 0.018~\Omega \\ &= 1.8~\Omega \end{align*}

Result

\begin{align*} R'_2 &= 1.2~\Omega \\ X'_{2\sigma} &= 1.8~\Omega \end{align*}

3. Calculate $R_{\rm k}$ and $X_{\rm k}$.

Solution

The short-circuit equivalent values are the sums of the primary quantities and the referred secondary quantities: \begin{align*} R_{\rm k} &= R_1+R'_2 \\ X_{\rm k} &= X_{1\sigma}+X'_{2\sigma} \end{align*}

Insert the values: \begin{align*} R_{\rm k} &= 1.2~\Omega+1.2~\Omega \\ &= 2.4~\Omega \\[4pt] X_{\rm k} &= 1.8~\Omega+1.8~\Omega \\ &= 3.6~\Omega \end{align*}

Result

\begin{align*} R_{\rm k} &= 2.4~\Omega \\ X_{\rm k} &= 3.6~\Omega \end{align*}

4. Calculate the primary rated current magnitude $I_{1{\rm N}}$ using the ideal current ratio.

Solution

For an ideal transformer, the primary current magnitude is: \begin{align*} I_{1{\rm N}} = \frac{I_{2{\rm N}}}{n} \end{align*}

Insert the values: \begin{align*} I_{1{\rm N}} &= \frac{5.0~{\rm A}}{10} \\ &= 0.50~{\rm A} \end{align*}

Result

\begin{align*} I_{1{\rm N}}=0.50~{\rm A} \end{align*}

5. Estimate the magnitude of the internal voltage drop $U_{\rm k}\approx |\underline{Z}_{\rm k}|I_{1{\rm N}}$.

Solution

First calculate the magnitude of the short-circuit impedance: \begin{align*} |\underline{Z}_{\rm k}| = \sqrt{R_{\rm k}^2+X_{\rm k}^2} \end{align*}

Insert the values: \begin{align*} |\underline{Z}_{\rm k}| &= \sqrt{(2.4~\Omega)^2+(3.6~\Omega)^2} \\ &= 4.33~\Omega \end{align*}

Now calculate the internal voltage drop: \begin{align*} U_{\rm k} &\approx |\underline{Z}_{\rm k}|I_{1{\rm N}} \\ &= 4.33~\Omega\cdot 0.50~{\rm A} \\ &= 2.17~{\rm V} \end{align*}

This is a primary-side voltage drop. On the secondary side: \begin{align*} \frac{2.17~{\rm V}}{10} = 0.217~{\rm V} \end{align*}

For a $23~{\rm V}$ actuator supply this is small but not zero.

Result

\begin{align*} |\underline{Z}_{\rm k}| &= 4.33~\Omega \\ U_{\rm k} &\approx 2.17~{\rm V} \end{align*}

Secondary-side equivalent: \begin{align*} U_{\rm k,2}\approx 0.217~{\rm V} \end{align*}

Exercise E8 Short-circuit voltage from the transformer impedance

A transformer has the rated primary data

\begin{align*} U_{1{\rm N}}=230~{\rm V}, \qquad I_{1{\rm N}}=2.0~{\rm A}. \end{align*}

The short-circuit equivalent impedance referred to the primary side is

\begin{align*} R_{\rm k}=1.5~\Omega, \qquad X_{\rm k}=4.0~\Omega. \end{align*}

1. Calculate $|\underline{Z}_{\rm k}|$.

Solution

The short-circuit impedance magnitude is: \begin{align*} |\underline{Z}_{\rm k}| = \sqrt{R_{\rm k}^2+X_{\rm k}^2} \end{align*}

Insert the values: \begin{align*} |\underline{Z}_{\rm k}| &= \sqrt{(1.5~\Omega)^2+(4.0~\Omega)^2} \\ &= 4.27~\Omega \end{align*}

Result

\begin{align*} |\underline{Z}_{\rm k}|=4.27~\Omega \end{align*}

2. Calculate the rated short-circuit voltage $U_{1{\rm k}}$.

Solution

The primary voltage required to drive rated current through the short-circuited transformer is: \begin{align*} U_{1{\rm k}} = |\underline{Z}_{\rm k}|I_{1{\rm N}} \end{align*}

Insert the values: \begin{align*} U_{1{\rm k}} &= 4.27~\Omega\cdot 2.0~{\rm A} \\ &= 8.54~{\rm V} \end{align*}

Result

\begin{align*} U_{1{\rm k}}=8.54~{\rm V} \end{align*}

3. Calculate the relative short-circuit voltage ${\rm u_k}$.

Solution

The relative short-circuit voltage is: \begin{align*} {\rm u_k} = \frac{U_{1{\rm k}}}{U_{1{\rm N}}}\cdot 100~\% \end{align*}

Insert the values: \begin{align*} {\rm u_k} &= \frac{8.54~{\rm V}}{230~{\rm V}}\cdot 100~\% \\ &= 3.71~\% \end{align*}

Result

\begin{align*} {\rm u_k}=3.71~\% \end{align*}

4. Calculate the prospective continuous short-circuit current $I_{1{\rm k}}$ for rated primary voltage.

Solution

The prospective continuous short-circuit current is: \begin{align*} I_{1{\rm k}} = I_{1{\rm N}}\cdot \frac{100~\%}{\rm u_k} \end{align*}

Insert the values: \begin{align*} I_{1{\rm k}} &= 2.0~{\rm A}\cdot \frac{100}{3.71} \\ &= 53.9~{\rm A} \end{align*}

Result

\begin{align*} I_{1{\rm k}}=53.9~{\rm A} \end{align*}

5. Calculate the approximate first peak current $i_{\rm peak}\approx 2.54 I_{1{\rm k}}$.

Solution

The approximate first peak current is: \begin{align*} i_{\rm peak} \approx 2.54 I_{1{\rm k}} \end{align*}

Insert the short-circuit current: \begin{align*} i_{\rm peak} &\approx 2.54\cdot 53.9~{\rm A} \\ &= 137~{\rm A} \end{align*}

Even though the rated current is only $2.0~{\rm A}$, a short-circuit fault could lead to a much larger current until protection reacts.

Result

\begin{align*} i_{\rm peak}\approx 137~{\rm A} \end{align*}

Exercise E9 Voltage drop under load using the Kapp approximation

A transformer has the turns ratio $n=10$.

The short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.4~\Omega$, $X_{\rm k}=3.6~\Omega$.
The secondary load current is $I_2=4.0~{\rm A}$. The load has the power factor $\cos\varphi=0.8$ and is inductive.

Estimate the voltage drop on the secondary side using

\begin{align*} \Delta U_1 \approx I_1\left(R_{\rm k}\cos\varphi+X_{\rm k}\sin\varphi\right) \end{align*}

and

\begin{align*} \Delta U_2\approx \frac{\Delta U_1}{n}. \end{align*}

1. Calculate the primary current magnitude $I_1$.

Solution

The primary current magnitude is approximately: \begin{align*} I_1 = \frac{I_2}{n} \end{align*}

Insert the values: \begin{align*} I_1 &= \frac{4.0~{\rm A}}{10} \\ &= 0.40~{\rm A} \end{align*}

Result

\begin{align*} I_1=0.40~{\rm A} \end{align*}

2. Determine $\sin\varphi$ for the inductive load.

Solution

For an inductive load with $\cos\varphi=0.8$: \begin{align*} \sin\varphi = \sqrt{1-\cos^2\varphi} \end{align*}

Insert the value: \begin{align*} \sin\varphi &= \sqrt{1-0.8^2} \\ &= 0.6 \end{align*}

Result

\begin{align*} \sin\varphi=0.6 \end{align*}

3. Estimate the primary-side voltage drop $\Delta U_1$.

Solution

Use the Kapp approximation: \begin{align*} \Delta U_1 &\approx I_1\left(R_{\rm k}\cos\varphi+X_{\rm k}\sin\varphi\right) \end{align*}

Insert the values: \begin{align*} \Delta U_1 &\approx 0.40~{\rm A} \left( 2.4~\Omega\cdot 0.8 + 3.6~\Omega\cdot 0.6 \right) \\ &= 0.40~{\rm A} \left( 1.92~\Omega+2.16~\Omega \right) \\ &= 1.63~{\rm V} \end{align*}

Result

\begin{align*} \Delta U_1\approx 1.63~{\rm V} \end{align*}

4. Estimate the secondary-side voltage drop $\Delta U_2$.

Solution

The secondary-side voltage drop is: \begin{align*} \Delta U_2 \approx \frac{\Delta U_1}{n} \end{align*}

Insert the values: \begin{align*} \Delta U_2 &\approx \frac{1.63~{\rm V}}{10} \\ &= 0.163~{\rm V} \end{align*}

The secondary voltage decreases by approximately $0.16~{\rm V}$ for this operating point.

Result

\begin{align*} \Delta U_2\approx 0.163~{\rm V} \end{align*}

The secondary voltage decreases by approximately $0.16~{\rm V}$.

Exercise E10 Why the magnetizing branch can be neglected in the short-circuit test

A transformer has the rated primary voltage $U_{1{\rm N}}=230~{\rm V}$. Its rated primary current is $I_{1{\rm N}}=3.0~{\rm A}$.

At rated voltage and no-load operation, the magnetizing current is approximately $I_{\rm m,N}=0.12~{\rm A}$. The short-circuit voltage is ${\rm u_k}=6.0~\%$.

Assume that the magnetizing current is approximately proportional to the applied voltage.


1. Calculate the short-circuit test voltage $U_{1{\rm k}}$.

Solution

The short-circuit test voltage is: \begin{align*} U_{1{\rm k}} = \frac{\rm u_k}{100~\%}\cdot U_{1{\rm N}} \end{align*}

Insert the values: \begin{align*} U_{1{\rm k}} &= 0.06\cdot 230~{\rm V} \\ &= 13.8~{\rm V} \end{align*}

Result

\begin{align*} U_{1{\rm k}}=13.8~{\rm V} \end{align*}

2. Estimate the magnetizing current $I_{\rm m,k}$ during the short-circuit test.

Solution

The magnetizing current is assumed to be proportional to the voltage: \begin{align*} I_{\rm m,k} = I_{\rm m,N}\cdot \frac{U_{1{\rm k}}}{U_{1{\rm N}}} \end{align*}

Insert the values: \begin{align*} I_{\rm m,k} &= 0.12~{\rm A}\cdot \frac{13.8~{\rm V}}{230~{\rm V}} \\ &= 0.0072~{\rm A} \\ &= 7.2~{\rm mA} \end{align*}

Result

\begin{align*} I_{\rm m,k} = 0.0072~{\rm A} = 7.2~{\rm mA} \end{align*}

3. Compare $I_{\rm m,k}$ with $I_{1{\rm N}}$.

Solution

Compare the short-circuit magnetizing current with the rated current: \begin{align*} \frac{I_{\rm m,k}}{I_{1{\rm N}}} = \frac{0.0072~{\rm A}}{3.0~{\rm A}} \end{align*}

Calculate the ratio: \begin{align*} \frac{I_{\rm m,k}}{I_{1{\rm N}}} &= 0.0024 \\ &= 0.24~\% \end{align*}

Result

\begin{align*} \frac{I_{\rm m,k}}{I_{1{\rm N}}} = 0.24~\% \end{align*}

4. Explain why the magnetizing branch can be neglected.

Solution

During the short-circuit test, the applied voltage is much smaller than the rated voltage: \begin{align*} U_{1{\rm k}} \ll U_{1{\rm N}} \end{align*}

Since the magnetizing current is assumed to be approximately proportional to the applied voltage, the magnetizing current is also very small: \begin{align*} I_{\rm m,k}=7.2~{\rm mA} \end{align*}

Compared with the rated current: \begin{align*} I_{1{\rm N}}=3.0~{\rm A} \end{align*}

the magnetizing current is only $0.24~\%$.

So during the short-circuit test, almost all current flows through the short-circuit path consisting of $R_{\rm k}$ and $X_{\rm k}$.

Result

The magnetizing branch $R_{\rm Fe}\parallel jX_{1{\rm H}}$ can usually be neglected in the short-circuit test.

Exercise E11 Why the short-circuit equivalent circuit is often sufficient under load

A transformer has the turns ratio $n=10$. The short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.0~\Omega$, $X_{\rm k}=4.0~\Omega$.

The secondary load current is $I_2=5.0~{\rm A}$. The load is ohmic-inductive with $\cos\varphi=0.8$.

The no-load current on the primary side is approximately $I_{10}=0.03~{\rm A}$.


1. Calculate the load-related primary current $I'_2$.

Solution

The load-related primary current is: \begin{align*} I'_2 = \frac{I_2}{n} \end{align*}

Insert the values: \begin{align*} I'_2 &= \frac{5.0~{\rm A}}{10} \\ &= 0.50~{\rm A} \end{align*}

Result

\begin{align*} I'_2=0.50~{\rm A} \end{align*}

2. Estimate the primary-side voltage drop.

Solution

The voltage drop is estimated with: \begin{align*} \Delta U_1 \approx I'_2 \left( R_{\rm k}\cos\varphi + X_{\rm k}\sin\varphi \right) \end{align*}

For $\cos\varphi=0.8$: \begin{align*} \sin\varphi &= \sqrt{1-\cos^2\varphi} \\ &= \sqrt{1-0.8^2} \\ &= 0.6 \end{align*}

Insert the values: \begin{align*} \Delta U_1 &\approx 0.50~{\rm A} \left( 2.0~\Omega\cdot 0.8 + 4.0~\Omega\cdot 0.6 \right) \\ &= 0.50~{\rm A} \left( 1.6~\Omega+2.4~\Omega \right) \\ &= 2.0~{\rm V} \end{align*}

Result

\begin{align*} \Delta U_1\approx 2.0~{\rm V} \end{align*}

3. Calculate the secondary-side voltage drop $\Delta U_2\approx \frac{\Delta U_1}{n}$.

Solution

The secondary-side voltage drop is: \begin{align*} \Delta U_2 \approx \frac{\Delta U_1}{n} \end{align*}

Insert the values: \begin{align*} \Delta U_2 &\approx \frac{2.0~{\rm V}}{10} \\ &= 0.20~{\rm V} \end{align*}

Result

\begin{align*} \Delta U_2\approx 0.20~{\rm V} \end{align*}

4. Estimate an upper bound for the neglected voltage drop caused by $I_{10}$.

Solution

First calculate the magnitude of the short-circuit impedance: \begin{align*} |\underline{Z}_{\rm k}| = \sqrt{R_{\rm k}^2+X_{\rm k}^2} \end{align*}

Insert the values: \begin{align*} |\underline{Z}_{\rm k}| &= \sqrt{(2.0~\Omega)^2+(4.0~\Omega)^2} \\ &= 4.47~\Omega \end{align*}

The upper bound for the voltage drop caused by the no-load current is: \begin{align*} \Delta U_{1,10} &\leq |\underline{Z}_{\rm k}|I_{10} \\ &= 4.47~\Omega\cdot 0.03~{\rm A} \\ &= 0.134~{\rm V} \end{align*}

On the secondary side: \begin{align*} \Delta U_{2,10} &\leq \frac{0.134~{\rm V}}{10} \\ &= 0.0134~{\rm V} \end{align*}

Result

\begin{align*} |\underline{Z}_{\rm k}| &= 4.47~\Omega \\ \Delta U_{1,10} &\leq 0.134~{\rm V} \\ \Delta U_{2,10} &\leq 0.0134~{\rm V} \end{align*}

5. Decide whether the short-circuit equivalent circuit is sufficient for this load estimate.

Solution

The load-related secondary-side voltage drop is: \begin{align*} \Delta U_2\approx 0.20~{\rm V} \end{align*}

The estimated neglected secondary-side voltage drop caused by the no-load current is at most: \begin{align*} \Delta U_{2,10}\leq 0.0134~{\rm V} \end{align*}

This is small compared with the load-related drop of $0.20~{\rm V}$.

Result

For this engineering estimate, the short-circuit equivalent circuit is sufficient.

Exercise E12 Ideal transformer versus real transformer

A transformer has the rated primary voltage of $U_1=230~{\rm V}$ and and the turns ratio $n=10$. A resistive load draws $I_2=4.0~{\rm A}$.
For the real transformer, the short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.4~\Omega$, $X_{\rm k}=3.2~\Omega$.
The iron loss is approximately $P_{\rm Fe}=1.5~{\rm W}$.
Assume a resistive load with $\cos\varphi=1$.

1. Calculate the ideal secondary voltage $U_{2,\rm ideal}$.

Solution

For the ideal transformer: \begin{align*} U_{2,\rm ideal} = \frac{U_1}{n} \end{align*}

Insert the values: \begin{align*} U_{2,\rm ideal} &= \frac{230~{\rm V}}{10} \\ &= 23.0~{\rm V} \end{align*}

Result

\begin{align*} U_{2,\rm ideal}=23.0~{\rm V} \end{align*}

2. Calculate the load-related primary current $I'_2$.

Solution

The load-related primary current is: \begin{align*} I'_2 = \frac{I_2}{n} \end{align*}

Insert the values: \begin{align*} I'_2 &= \frac{4.0~{\rm A}}{10} \\ &= 0.40~{\rm A} \end{align*}

Result

\begin{align*} I'_2=0.40~{\rm A} \end{align*}

3. Estimate the real secondary voltage.

Solution

For a resistive load, the approximate primary-side voltage drop is: \begin{align*} \Delta U_1 \approx I'_2R_{\rm k} \end{align*}

Insert the values: \begin{align*} \Delta U_1 &\approx 0.40~{\rm A}\cdot 2.4~\Omega \\ &= 0.96~{\rm V} \end{align*}

The corresponding secondary-side voltage drop is: \begin{align*} \Delta U_2 &\approx \frac{\Delta U_1}{n} \\ &= \frac{0.96~{\rm V}}{10} \\ &= 0.096~{\rm V} \end{align*}

Thus the real secondary voltage is approximately: \begin{align*} U_{2,\rm real} &\approx 23.0~{\rm V}-0.096~{\rm V} \\ &= 22.90~{\rm V} \end{align*}

Result

\begin{align*} \Delta U_1 &\approx 0.96~{\rm V} \\ \Delta U_2 &\approx 0.096~{\rm V} \\ U_{2,\rm real} &\approx 22.90~{\rm V} \end{align*}

4. Estimate the copper losses.

Solution

The copper losses are: \begin{align*} P_{\rm Cu} \approx R_{\rm k}(I'_2)^2 \end{align*}

Insert the values: \begin{align*} P_{\rm Cu} &\approx 2.4~\Omega\cdot (0.40~{\rm A})^2 \\ &= 0.384~{\rm W} \end{align*}

The real transformer also has iron losses: \begin{align*} P_{\rm Fe}=1.5~{\rm W} \end{align*}

Result

\begin{align*} P_{\rm Cu}\approx 0.384~{\rm W} \end{align*}

Additionally: \begin{align*} P_{\rm Fe}=1.5~{\rm W} \end{align*}

5. Compare ideal and real transformer behavior.

Solution

For the ideal transformer: \begin{align*} U_{2,\rm ideal}=23.0~{\rm V} \end{align*}

For the real transformer: \begin{align*} U_{2,\rm real}\approx 22.90~{\rm V} \end{align*}

The real transformer has copper losses and iron losses: \begin{align*} P_{\rm Cu}&\approx 0.384~{\rm W} \\ P_{\rm Fe}&=1.5~{\rm W} \end{align*}

So the main differences are:

  • the ideal transformer has exactly $U_2=23.0~{\rm V}$, the real transformer has a slightly lower voltage,
  • the ideal transformer has no losses, the real transformer has copper and iron losses,
  • the ideal transformer has no leakage voltage drop, the real transformer has a load-dependent voltage drop.

For this operating point the transformer is close to ideal, but not exactly ideal.

Result

The real transformer differs from the ideal transformer by:

  • a slightly lower secondary voltage,
  • copper and iron losses,
  • a load-dependent voltage drop.

For this operating point it is close to ideal, but not exactly ideal.

Common pitfalls

Embedded resources