\[ \begin{align*} \frac{\underline{U}_1^\phantom{O}}{\underline{U}_2^\phantom{O}}=\frac{N_1}{N_2}=n, \qquad \frac{\underline{I}_1}{\underline{I}_2}=-\frac{1}{n} \end{align*} \] with a clear sign convention.
Well, again
For checking your understanding please do the quick checks in the exercise section.
\[ \begin{align*} \text{higher voltage} \quad \Longleftrightarrow \quad \text{lower current} \end{align*} \]
In EEE1 we considered magnetic flux \(\Phi\), flux linkage / linked flux \(\Psi\), and induction.
For one coil with \(N\) turns the flux linkage is
\[ \begin{align*} \Psi = N\Phi . \end{align*} \]
Faraday's law gives
\[ \begin{align*} u(t)=\frac{{\rm d}\Psi}{{\rm d}t}=N\frac{{\rm d}\Phi}{{\rm d}t}. \end{align*} \]
(Be aware of Lenz law: Here u(t) is the terminal voltage according to the chosen voltage reference arrow. The induced voltage $u_{\rm ind}$ according to Faraday–Lenz would have the opposite sign)
In sinusoidal steady state this becomes the phasor equation
\[ \begin{align*} \underline{U}=j\omega\underline{\Psi}=j\omega N\underline{\Phi}. \end{align*} \]
This is the starting point for the transformer.
Before we start with the transformer, we have to look at a common convention for the orientation of two coils to each other.
For an ideal transformer we assume:
Let \(N_1\) be the number of turns of the primary winding and \(N_2\) the number of turns of the secondary winding.
\[ \begin{align*} \underline{\Psi}_1 &= N_1\underline{\Phi}, & \underline{U}_1 &= j\omega\underline{\Psi}_1 = j\omega N_1\underline{\Phi}, \\ \underline{\Psi}_2 &= N_2\underline{\Phi}, & \underline{U}_2 &= j\omega\underline{\Psi}_2 = j\omega N_2\underline{\Phi}. \end{align*} \]
Dividing the two voltage equations gives the turns ratio
\[ \begin{align*} \boxed{ \frac{\underline{U}_1^\phantom{O}}{\underline{U}_2^\phantom{O}} = \frac{N_1}{N_2} = n } \end{align*} \]
with
\[ \begin{align*} n=\frac{N_1}{N_2}. \end{align*} \]
With the indicated reference arrows and a lossless transformer, the resulting complex power as a sum of input and output power $\underline{S}$ must be zero:
\[ \begin{align*} \underline{S}_1+\underline{S}_2= \underline{U}_1\underline{I}^*_1+\underline{U}_2\underline{I}^*_2=0 \end{align*} \]
and therefore
\[ \begin{align*} \boxed{ \frac{\underline{I}_1}{\underline{I}_2} = -\frac{\underline{U}_2^\phantom{O}}{\underline{U}_1^\phantom{O}} = -\frac{N_2}{N_1} = -\frac{1}{n} } \end{align*} \]
The minus sign is not a “loss”. It is caused by the chosen current arrows.
The primary side absorbs power while the secondary side delivers power to the load.
An ideal transformer behaves like a lossless gearbox:
For a step-down transformer:
\[ \begin{align*} \text{lower voltage} \quad \Longleftrightarrow \quad \text{higher current}. \end{align*} \]
The power is ideally conserved, just as mechanical power is ideally conserved in a lossless gearbox.
A transformer has \(N_1=800\) turns and \(N_2=80\) turns. The primary RMS voltage is \(U_1=230~{\rm V}\).
\[ \begin{align*} n &= \frac{N_1}{N_2} = \frac{800}{80} =10, \\ U_2 &= \frac{U_1}{n} = \frac{230~{\rm V}}{10} =23~{\rm V}. \end{align*} \]
If the secondary side supplies \(I_2=4~{\rm A}\), the ideal primary current magnitude is
\[ \begin{align*} I_1 &= \frac{I_2}{n} = \frac{4~{\rm A}}{10} =0.4~{\rm A}. \end{align*} \]
The apparent power is equal on both sides:
\[ \begin{align*} S_1 &= U_1I_1=230~{\rm V}\cdot 0.4~{\rm A}=92~{\rm VA}, \\ S_2 &= U_2I_2=23~{\rm V}\cdot 4~{\rm A}=92~{\rm VA}. \end{align*} \]
For a single coil we already know that its flux linkage $\Psi = N\Phi$ is proportional to the current $i$ through the coil
\[ \begin{align*} \Psi=L i \end{align*} \]
\[ \begin{align*} \underline{\Psi}=L \underline{I} . \end{align*} \]
For two coupled coils $1$ and $2$, each flux linkage $\underline{\Psi}_1 = N\underline{\Phi}_1$ and $\underline{\Psi}_2 = N\underline{\Phi}_2$ depend on both currents $\underline{I}_1$ and $\underline{I}_2$.
Not only the current through the coil generates a part of the flux linkage, but also the other coil provides a part for the flux linkage.
\[ \begin{align*} \underline{\Psi}_1 &= \underbrace{{\color{green}{L_{11}\underline{I}_1}}}_{\text{self-linkage of coil 1}} + \underbrace{{\color{blue}{M_{12}\underline{I}_2}}}_{\text{mutual linkage from coil 2}}, \\[4pt] \underline{\Psi}_2 &= \underbrace{{\color{blue}{M_{21}\underline{I}_1}}}_{\text{mutual linkage from coil 1}} + \underbrace{{\color{green}{L_{22}\underline{I}_2}}}_{\text{self-linkage of coil 2}}. \end{align*} \]
For most transformer calculations we use the symmetric case of the mutual inductances.
(this is true for passive, stationary, and reciprocal situations, like transformers, but not necessarily for motors or complex setups)
\[ \begin{align*} {\color{blue}{M_{12}}}={\color{blue}{M_{21}}}={\color{blue}{M}}. \end{align*} \]
Often, the self-inductances are abbreviated: \[ \begin{align*} \color{green}{L_{11}} \rightarrow \color{green}{L_{1}} \\ \color{green}{L_{22}} \rightarrow \color{green}{L_{2}} \\ \end{align*} \]
Then
\[ \begin{align*} \boxed{ \begin{pmatrix} \underline{\Psi}_1\\ \underline{\Psi}_2 \end{pmatrix} = \begin{pmatrix} {\color{green}{L_{1}}} & {\color{blue}{M}}\\ {\color{blue}{M}} & {\color{green}{L_{2}}} \end{pmatrix} \begin{pmatrix} \underline{I}_1\\ \underline{I}_2 \end{pmatrix} } \end{align*} \]
and
\[ \begin{align*} M=k\sqrt{L_{1}L_{2}}. \end{align*} \]
Here \(k\) is the coupling coefficient. In the shown transformer \(k\) is 1 since all flux from $1$ flows through $2$ and vice versa.
In reality that is not the case as explained in the next chapters.
| Coupling coefficient | Interpretation | Typical example |
|---|---|---|
| \(k=0\) | no useful flux from one coil links the other coil | coils far apart |
| \(0<k<1\) | partial coupling | wireless charger with air gap or misalignment |
| \(k\approx 1\) | almost all useful flux links both coils | transformer with iron core |
The mutual inductance \(M\) answers the question:
How much flux linkage appears in coil \(2\) when the current in coil \(1\) changes?
In wireless charging, the transmitter coil and receiver coil are separated by an air gap. The coupling coefficient \(k\) is much smaller than in a transformer with an iron core.
If the receiver is misaligned, less flux from the transmitter passes through it. Then \(M\) decreases, the induced voltage decreases, and the transmitted power decreases.
Imagine two people lying on a bed holding the same bed sheet at different positions.
In transformer language, \(L_{1}\) and \(L_{2}\) describe each winding's connection to the shared main flux path.
The mutual inductance \(M\) describes the transfer between the two windings through this shared path.
For positive coupling, we get the following complex representation (since $u(t) = L\frac{{\rm d}i}{{\rm d}t} \: \longrightarrow \:\underline{U}=j\omega L \underline{I}$):
\[
\begin{align*}
\underline{U}_1 &= R_1 \underline{I}_1 + {\color{green} {j\omega L_{1} \underline{I}_1 }} + {\color{blue}{j\omega M \underline{I}_2 }},
\\[4pt]
\underline{U}_2 &= R_2 \underline{I}_2 + {\color{blue} {j\omega M \underline{I}_1 }} + {\color{green}{j\omega L_{2} \underline{I}_2 }}.
\end{align*}
\]
For negative coupling, the sign of the \(M\)-term changes in the chosen equation system, see figure 2 and figure 3.
The dots are like matching openings for magnetic action.
A positive reference current (e.g. $i_1$) entering the dotted terminal of one winding produces a positive induced voltage (e.g. aligned with $u_2$) at the dotted terminal of the other winding.
With only a load $R_2$ connected to the secondary side, this voltage tends to drive current out of the dotted terminal into the load.
The image of the ideal transformer shall be consecutively developed to a more realistic transformer model.
To do so, we look at the situation of two coils near each other and expand this formula for the induced voltage.
The flux created by coil \(1\) can be split into
\[ \begin{align*} \Phi_{11} = {\color{blue}{\Phi_{21}}} + {\color{orange}{\Phi_{1 \rm \sigma}}}. \end{align*} \]
For an example, we will have a look at the instantaneous voltage induced in coil \(2\):
\[ \begin{align*} u_{2,\rm ind}(t) = \frac{{\rm d}{\color{blue}{\Psi_{21}}}}{{\rm d}t} = N_2\frac{{\rm d}{\color{blue}{\Phi_{21}}}}{{\rm d}t}. \end{align*} \]
The complex voltage induced in coil \(2\) is
\[ \begin{align*} \underline{U}_{2} = j\omega {\color{blue}{ \underline{\Psi}_{21} }} = j\omega N_2 {\color{blue}{ \underline{\Phi}_{21} }} . \end{align*} \]
Analogy 1: two pendulums connected by a spring
Imagine two pendulums connected by a weak spring.
For coupled coils:
Analogy 2: a leaky magnetic pipe
The magnetic core can be imagined as a pipe guiding magnetic flux.
This image is helpful for transformers, wireless charging coils, and current sensors.
In a real transformer, not all flux links both windings.
The leakage flux can be interpreted as an additional virtual branch in the mechanical setup, see figure 5.
The total main flux linking is given by (see figure 5) \[ \begin{align*} \underline{\Phi}_{1 \rm H} = \underline{\Phi}_{21} + \underline{\Phi}_{12} = \underline{\Phi}_{\rm H} \\[4pt] \underline{\Phi}_{2 \rm H} = \underline{\Phi}_{21} + \underline{\Phi}_{12} = \underline{\Phi}_{\rm H} \end{align*} \]
For the flux linkage also the leakage flux has to be considered: \[ \begin{align*} \underline{\Psi}_{1} =N_1 ( \underline{\Phi}_{21} + \underline{\Phi}_{12} + \underline{\Phi}_{1\sigma}) \\[4pt] \underline{\Psi}_{2} =N_2 ( \underline{\Phi}_{21} + \underline{\Phi}_{12} + \underline{\Phi}_{2\sigma}) \end{align*} \]
The real flux linkage equations become
\[ \begin{align*} \underline{\Psi}_1 &= \underbrace{{\color{blue }{L_{1{\rm H}}\underline{I}_1 + M\underline{I}_2}} }_{\text{main magnetic path}} + \underbrace{{\color{orange}{L_{1\sigma }\underline{I}_1}} }_{\text{primary leakage} }, \\[4pt] \underline{\Psi}_2 &= \underbrace{{\color{blue }{M\underline{I}_1 + L_{2{\rm H}}\underline{I}_2 }} }_{\text{main magnetic path}} + \underbrace{{\color{orange}{L_{2\sigma }\underline{I}_2}} }_{\text{secondary leakage} }. \end{align*} \]
Equivalently,
\[ \begin{align*} \underline{\Psi}_1 &= L_1\underline{I}_1+M\underline{I}_2, & L_1&=L_{1{\rm H}}+L_{1\sigma}, \\ \underline{\Psi}_2 &= L_2\underline{I}_2+M\underline{I}_1, & L_2&=L_{2{\rm H}}+L_{2\sigma}. \end{align*} \]
The winding resistances \(R_1\) and \(R_2\) cause copper losses:
\[ \begin{align*} P_{\rm Cu,1}=R_1I_1^2, \qquad P_{\rm Cu,2}=R_2I_2^2. \end{align*} \]
\[ \begin{align*} \underline{U}_1 &= \underbrace{{\color{red}{R_1\underline{I}_1}}}_{\text{primary copper drop}} + \underbrace{{\color{orange}{j\omega L_{1\sigma}\underline{I}_1}}}_{\text{primary leakage drop}} + \underbrace{{\color{blue}{j\omega L_{1{\rm H}}\underline{I}_1+j\omega M\underline{I}_2}}}_{\text{main magnetic coupling}}, \\[6pt] \underline{U}_2 &= \underbrace{{\color{red}{R_2\underline{I}_2}}}_{\text{secondary copper drop}} + \underbrace{{\color{orange}{j\omega L_{2\sigma}\underline{I}_2}}}_{\text{secondary leakage drop}} + \underbrace{{\color{blue}{j\omega L_{2{\rm H}}\underline{I}_2+j\omega M\underline{I}_1}}}_{\text{main magnetic coupling}}. \end{align*} \]
Based, on the block19 and block20 of last semester, the inductances can be calculated by the reluctance $R_{\rm mFe}$ of the iron core and the number of turns $N_1$, $N_2$:
\[ \begin{align*} \boxed{ L_{1 \rm H} = \frac{N_1^2}{R_{\rm mFe} } \\ L_{2 \rm H} = \frac{N_2^2}{R_{\rm mFe} } \\ M = \frac{N_1 N_2}{R_{\rm mFe} } \\ } \end{align*} \]
In the previous formulas:
Think of the main flux as traffic on the useful road between two cities. Traffic on side roads still exists, but it does not help transport goods between the two cities.
Since we know, that we can transform the current and voltage by the transformer, we can use this also to simplify the circuit.
Fig. 6: equivalent circuit of a real transformer
For calculations it is convenient to move all secondary-side quantities to the primary side.
This is called referring or transforming the secondary side to the primary side.
\[ \begin{align*} \boxed{ \underline{U}'_2=n\underline{U}_2 } \qquad \boxed{ \underline{I}'_2=\frac{1}{n}\underline{I}_2 } \end{align*} \]
The secondary resistance and leakage reactance are transformed by \(n^2\) since $R = U / I$:
\[ \begin{align*} \boxed{ R'_2=n^2R_2 } \qquad \boxed{ X'_{2\sigma}=n^2X_{2\sigma} } \end{align*} \]
Fig. 7: reduced equivalent circuit of a real transformer
In the reduced equivalent circuit:
The phasor diagram is shown in figure 8.
Fig. 8: phasor diagram of a real transformer
Once all quantities are referred to one side, the transformer can be calculated like an AC network with impedances.
This uses the same method as complex network calculation: replace components by impedances and apply Kirchhoff's laws.
No-load operation means that the secondary side is open:
\[ \begin{align*} \underline{I}_2=0. \end{align*} \]
The primary side still draws a small no-load current \(\underline{I}_{10}\). This current has two parts:
\[ \begin{align*} \underline{I}_{10} = \underline{I}_{\rm Fe} + \underline{I}_{\rm m}. \end{align*} \]
The technical voltage ratio is often defined from the no-load voltages. Here it is denoted by \(\ddot{\rm u}\):
\[ \boxed{ \begin{align*} \ddot{\rm u} = \frac{\text{higher voltage}}{\text{lower voltage}} \bigg|_{\rm no~load}. \end{align*} } \]
For a step-down transformer:
\[ \begin{align*} \ddot{\rm u} = \frac{U_{1{\rm N}}}{U_{20}}. \end{align*} \]
Here \(U_{1{\rm N}}\) is the rated primary voltage and \(U_{20}\) is the open-circuit secondary voltage.
\[ \begin{align*} \ddot{\rm u}\neq n, \end{align*} \]
but for many practical transformers
\[ \begin{align*} \ddot{\rm u}\approx n. \end{align*} \]
In the short-circuit test, the secondary side is shorted, so $\underline{U}_2=0$.
The primary voltage $\underline{U}_1$ is increased only until rated current flows.
Because the short-circuit impedance is small, this requires only a small fraction of the rated primary voltage.
Therefore the main flux and the magnetizing current are small, so the magnetizing branch can usually be neglected.
\[ \begin{align*} \Big|\; jX_{1{\rm H}} \; || \;R_{\rm Fe} \;\Big| \;\; \gg \;\; \Big|\; jX_{1\sigma} + \;R_1 + jX'_{2\sigma} + \;R'_2 \;\Big| . \end{align*} \]
This gives the short-circuit equivalent circuit with
\[ \begin{align*} \boxed{ R_{\rm k}=R_1+R'_2 } \qquad \boxed{ X_{\rm k}=X_{1\sigma}+X'_{2\sigma} } \end{align*} \]
and
\[ \begin{align*} \underline{Z}_{\rm k} = R_{\rm k}+jX_{\rm k}. \end{align*} \]
The rated short-circuit voltage \(U_{1{\rm k}}\) is the primary voltage that must be applied while the secondary side is shorted so that rated primary current \(I_{1{\rm N}}\) flows.
As a relative value:
\[ \begin{align*} \boxed{ {\rm u_k} = \frac{U_{1{\rm k}}}{U_{1{\rm N}}}\cdot 100~\% } \end{align*} \]
The continuous short-circuit current for rated primary voltage is
\[ \begin{align*} \boxed{ I_{1{\rm k}} = \frac{U_{1{\rm N}}}{U_{1{\rm k}}}\cdot I_{1{\rm N}} = I_{1{\rm N}}\cdot \frac{100~\%}{{\rm u_k}} } \end{align*} \]
where \(\rm u_k\) is inserted as a percentage value.
For a first approximation of the maximum instantaneous current the following formula can be used:
\[ \begin{align*} \boxed{ i_{{\rm peak}} = 2.54 \cdot I_{1 \rm k} } \end{align*} \]
Under load, the short-circuit equivalent circuit is often sufficient for engineering estimates.
\[ \begin{align*} \underline{U}_{\rm k} = \left(R_{\rm k}+jX_{\rm k}\right)\underline{I}_1. \end{align*} \]
This voltage drop is subtracted vectorially from the primary-side voltage relation.
\[ \begin{align*} \boxed{ \underline{U}_1 - \underline{U}_{\rm k} = \underline{U}'_2 = n \underline{U}_2 } \end{align*} \]
If the magnetizing branch is neglected for the load calculation, then the series current relation is approximately $\underline{I}'_2 \approx -\underline{I}_1$. Therefore the ideal current transformation can still be used as an approximation.
\[ \begin{align*} \boxed{ \frac{\underline{I}_1}{\underline{I}_2} = -\frac{N_2}{N_1} = -\frac{1}{n} } \end{align*} \]
The Kapp triangle (see yellow triangle in figure 11) represents the formula for $\underline{U}_{\rm k}$.
In a robot with motors, the supply transformer may show a lower output voltage during high acceleration because the motor currents increase. The Kapp triangle helps estimate this voltage drop. This is important for:
Transformer behavior is influenced by construction.
Cooling types:
| Name / use | Typical \({\rm u_k}\) | Secondary voltage \(U_2\) | Important note |
|---|---|---|---|
| Power transformer | \(4\ldots 12~\%\) | application-dependent | low voltage drop, high fault currents possible |
| Isolating transformer | \(\approx 10~\%\) | max. \(250~{\rm V}\) | galvanic isolation for safety and measurement |
| Toy transformer | \(\approx 20~\%\) | max. \(24~{\rm V}\) | current limitation is desired |
| Doorbell transformer | \(\approx 40~\%\) | max. \(12~{\rm V}\), often several taps | simple robust low-voltage supply |
| Ignition transformer | \(\approx 100~\%\) | \(\leq 14~{\rm kV}\) | high voltage, limited current |
| Welding transformer | \(\approx 100~\%\) | max. \(70~{\rm V}\) | large current, strong current limitation |
| Voltage transformer | \(<1~\%\) | \(100~{\rm V}\) | operate with high load resistance, approximately no-load |
| Current transformer | \(100~\%\) | \(0~{\rm V}\) ideal secondary voltage | operate with low burden, approximately short-circuit |
A current transformer secondary must not be opened while primary current flows.
If the secondary circuit is open, the transformer tries to maintain the magnetic balance and can generate dangerous high voltages.
A transformer has $N_1=1200$ turns and $N_2=300$ turns.
The primary RMS voltage is $U_1=230~{\rm V}$.
The secondary side supplies a load current $I_2=2.0~{\rm A}$.
1. Calculate the turns ratio $n$.
The turns ratio of an ideal transformer is defined as: \begin{align*} n=\frac{N_1}{N_2} \end{align*}
Insert the given values: \begin{align*} n &= \frac{1200}{300} \\ &= 4 \end{align*}
2. Calculate the ideal secondary voltage $U_2$.
For an ideal transformer, the voltage ratio follows the turns ratio: \begin{align*} n=\frac{U_1}{U_2} \end{align*}
Therefore: \begin{align*} U_2 &= \frac{U_1}{n} \\ &= \frac{230~{\rm V}}{4} \\ &= 57.5~{\rm V} \end{align*}
3. Calculate the magnitude of the ideal primary current $I_1$.
For the ideal transformer, the current ratio is inverse to the voltage ratio: \begin{align*} I_1=\frac{I_2}{n} \end{align*}
Insert the values: \begin{align*} I_1 &= \frac{2.0~{\rm A}}{4} \\ &= 0.50~{\rm A} \end{align*}
4. State whether this is a step-up or step-down transformer.
Compare the primary and secondary voltages: \begin{align*} U_1 &= 230~{\rm V} \\ U_2 &= 57.5~{\rm V} \end{align*}
Since \begin{align*} U_2<U_1 \end{align*}
the transformer reduces the voltage.
Two coils are wound on the same ideal magnetic core. The main magnetic reluctance is
\begin{align*} R_{\rm mH}=2.0\cdot 10^6~\frac{1}{\rm H}. \end{align*}
The number of turns is $N_1=500$ and $N_2=100$.
1. Calculate $L_{1{\rm H}}$.
The main-flux inductance of coil 1 is: \begin{align*} L_{1{\rm H}} = \frac{N_1^2}{R_{\rm mH}} \end{align*}
Insert the values: \begin{align*} L_{1{\rm H}} &= \frac{500^2}{2.0\cdot 10^6~1/{\rm H}} \\ &= 0.125~{\rm H} \end{align*}
2. Calculate $L_{2{\rm H}}$.
The main-flux inductance of coil 2 is: \begin{align*} L_{2{\rm H}} = \frac{N_2^2}{R_{\rm mH}} \end{align*}
Insert the values: \begin{align*} L_{2{\rm H}} &= \frac{100^2}{2.0\cdot 10^6~1/{\rm H}} \\ &= 0.0050~{\rm H} \\ &= 5.0~{\rm mH} \end{align*}
3. Calculate $M$.
The mutual inductance is: \begin{align*} M = \frac{N_1N_2}{R_{\rm mH}} \end{align*}
Insert the values: \begin{align*} M &= \frac{500\cdot 100}{2.0\cdot 10^6~1/{\rm H}} \\ &= 0.025~{\rm H} \\ &= 25~{\rm mH} \end{align*}
4. Check whether the units are correct.
The reluctance is given in: \begin{align*} [R_{\rm mH}]=\frac{1}{\rm H} \end{align*}
The number of turns is dimensionless. Therefore: \begin{align*} \left[ \frac{N^2}{R_{\rm mH}} \right] = \frac{1}{1/{\rm H}} = {\rm H} \end{align*}
The same argument applies to the mutual inductance: \begin{align*} \left[ \frac{N_1N_2}{R_{\rm mH}} \right] = {\rm H} \end{align*}
Two coils are wound on the same magnetic core. The shared main magnetic path has the reluctance
\begin{align*} R_{\rm mH}=1.6\cdot 10^6~\frac{1}{\rm H}. \end{align*}
The numbers of turns are
\begin{align*} N_1=400, \qquad N_2=100. \end{align*}
The leakage inductances are
\begin{align*} L_{1\sigma}=4.0~{\rm mH}, \qquad L_{2\sigma}=0.30~{\rm mH}. \end{align*}
1. Calculate $L_{1{\rm H}}$.
The main-flux self-inductance of coil 1 is: \begin{align*} L_{1{\rm H}} = \frac{N_1^2}{R_{\rm mH}} \end{align*}
Insert the values: \begin{align*} L_{1{\rm H}} &= \frac{400^2}{1.6\cdot 10^6~1/{\rm H}} \\ &= 0.100~{\rm H} \end{align*}
2. Calculate $L_{2{\rm H}}$.
The main-flux self-inductance of coil 2 is: \begin{align*} L_{2{\rm H}} = \frac{N_2^2}{R_{\rm mH}} \end{align*}
Insert the values: \begin{align*} L_{2{\rm H}} &= \frac{100^2}{1.6\cdot 10^6~1/{\rm H}} \\ &= 0.00625~{\rm H} \\ &= 6.25~{\rm mH} \end{align*}
3. Calculate $M$.
The mutual inductance is: \begin{align*} M = \frac{N_1N_2}{R_{\rm mH}} \end{align*}
Insert the values: \begin{align*} M &= \frac{400\cdot 100}{1.6\cdot 10^6~1/{\rm H}} \\ &= 0.025~{\rm H} \\ &= 25~{\rm mH} \end{align*}
4. Calculate the total self-inductances $L_1$ and $L_2$.
The total self-inductance is the sum of main-flux inductance and leakage inductance.
For coil 1: \begin{align*} L_1 &= L_{1{\rm H}}+L_{1\sigma} \\ &= 100~{\rm mH}+4.0~{\rm mH} \\ &= 104~{\rm mH} \end{align*}
For coil 2: \begin{align*} L_2 &= L_{2{\rm H}}+L_{2\sigma} \\ &= 6.25~{\rm mH}+0.30~{\rm mH} \\ &= 6.55~{\rm mH} \end{align*}
5. Calculate the coupling coefficient $k=\frac{M}{\sqrt{L_1L_2}}$.
The coupling coefficient is: \begin{align*} k = \frac{M}{\sqrt{L_1L_2}} \end{align*}
Insert the values in henry: \begin{align*} k &= \frac{0.025~{\rm H}}{\sqrt{0.104~{\rm H}\cdot 0.00655~{\rm H}}} \\ &\approx 0.96 \end{align*}
The coupling is strong, but not ideal, because leakage inductances are present.
The coupling is strong, but not ideal.
A transformer has $n=5$. The secondary winding resistance is $R_2=0.20~\Omega$ and the secondary leakage reactance is $X_{2\sigma}=0.35~\Omega$.
Calculate the values $R'_2$ and $X'_{2\sigma}$ referred to the primary side.
1. Calculate $R'_2$.
When a resistance is referred from the secondary side to the primary side, it is multiplied by $n^2$: \begin{align*} R'_2 = n^2R_2 \end{align*}
Insert the values: \begin{align*} R'_2 &= 5^2\cdot 0.20~\Omega \\ &= 25\cdot 0.20~\Omega \\ &= 5.0~\Omega \end{align*}
2. Calculate $X'_{2\sigma}$.
The secondary leakage reactance is also referred to the primary side by multiplying with $n^2$: \begin{align*} X'_{2\sigma} = n^2X_{2\sigma} \end{align*}
Insert the values: \begin{align*} X'_{2\sigma} &= 5^2\cdot 0.35~\Omega \\ &= 25\cdot 0.35~\Omega \\ &= 8.75~\Omega \end{align*}
3. Check the unit.
The turns ratio $n$ is dimensionless: \begin{align*} [n]=1 \end{align*}
Therefore, multiplying by $n^2$ does not change the unit: \begin{align*} [R'_2] &= \Omega \\ [X'_{2\sigma}] &= \Omega \end{align*}
A transformer has a rated primary current $I_{1{\rm N}}=10~{\rm A}$ and a short-circuit voltage ${\rm u_k}=5~\%$.
1. Calculate the continuous short-circuit current $I_{1{\rm k}}$ when rated primary voltage is applied.
The short-circuit current can be estimated from the rated current and the relative short-circuit voltage: \begin{align*} I_{1{\rm k}} = I_{1{\rm N}}\cdot \frac{100~\%}{\rm u_k} \end{align*}
Insert the values: \begin{align*} I_{1{\rm k}} &= 10~{\rm A}\cdot \frac{100~\%}{5~\%} \\ &= 200~{\rm A} \end{align*}
2. Estimate the initial peak short-circuit current $i_{\rm p}$ using $i_{\rm p}\approx 2.54 I_{1{\rm k}}$.
The initial peak current is estimated by: \begin{align*} i_{\rm p} \approx 2.54\cdot I_{1{\rm k}} \end{align*}
Insert the continuous short-circuit current: \begin{align*} i_{\rm p} &\approx 2.54\cdot 200~{\rm A} \\ &= 508~{\rm A} \end{align*}
The short-circuit current is much larger than the rated current. Protection devices must be selected accordingly.
Protection devices must be selected accordingly.
A single-phase transformer supplies an actuator driver. Rated data and equivalent circuit data are:
\begin{align*} U_{1{\rm N}}&=230~{\rm V}, & U_{2{\rm N}}&=23~{\rm V}, & I_{2{\rm N}}&=5.0~{\rm A}, \\ R_1&=1.2~\Omega, & X_{1\sigma}&=1.8~\Omega, \\ R_2&=0.012~\Omega, & X_{2\sigma}&=0.018~\Omega. \end{align*}
Assume $n=\frac{U_{1{\rm N}}}{U_{2{\rm N}}}$. The magnetizing branch is neglected for the loaded operating point.
1. Calculate $n$.
The turns ratio is estimated from the rated voltages: \begin{align*} n = \frac{U_{1{\rm N}}}{U_{2{\rm N}}} \end{align*}
Insert the values: \begin{align*} n &= \frac{230~{\rm V}}{23~{\rm V}} \\ &= 10 \end{align*}
2. Refer $R_2$ and $X_{2\sigma}$ to the primary side.
Secondary quantities are referred to the primary side by multiplying them with $n^2$: \begin{align*} R'_2 &= n^2R_2 \\ X'_{2\sigma} &= n^2X_{2\sigma} \end{align*}
With $n=10$: \begin{align*} R'_2 &= 10^2\cdot 0.012~\Omega \\ &= 1.2~\Omega \\[4pt] X'_{2\sigma} &= 10^2\cdot 0.018~\Omega \\ &= 1.8~\Omega \end{align*}
3. Calculate $R_{\rm k}$ and $X_{\rm k}$.
The short-circuit equivalent values are the sums of the primary quantities and the referred secondary quantities: \begin{align*} R_{\rm k} &= R_1+R'_2 \\ X_{\rm k} &= X_{1\sigma}+X'_{2\sigma} \end{align*}
Insert the values: \begin{align*} R_{\rm k} &= 1.2~\Omega+1.2~\Omega \\ &= 2.4~\Omega \\[4pt] X_{\rm k} &= 1.8~\Omega+1.8~\Omega \\ &= 3.6~\Omega \end{align*}
4. Calculate the primary rated current magnitude $I_{1{\rm N}}$ using the ideal current ratio.
For an ideal transformer, the primary current magnitude is: \begin{align*} I_{1{\rm N}} = \frac{I_{2{\rm N}}}{n} \end{align*}
Insert the values: \begin{align*} I_{1{\rm N}} &= \frac{5.0~{\rm A}}{10} \\ &= 0.50~{\rm A} \end{align*}
5. Estimate the magnitude of the internal voltage drop $U_{\rm k}\approx |\underline{Z}_{\rm k}|I_{1{\rm N}}$.
First calculate the magnitude of the short-circuit impedance: \begin{align*} |\underline{Z}_{\rm k}| = \sqrt{R_{\rm k}^2+X_{\rm k}^2} \end{align*}
Insert the values: \begin{align*} |\underline{Z}_{\rm k}| &= \sqrt{(2.4~\Omega)^2+(3.6~\Omega)^2} \\ &= 4.33~\Omega \end{align*}
Now calculate the internal voltage drop: \begin{align*} U_{\rm k} &\approx |\underline{Z}_{\rm k}|I_{1{\rm N}} \\ &= 4.33~\Omega\cdot 0.50~{\rm A} \\ &= 2.17~{\rm V} \end{align*}
This is a primary-side voltage drop. On the secondary side: \begin{align*} \frac{2.17~{\rm V}}{10} = 0.217~{\rm V} \end{align*}
For a $23~{\rm V}$ actuator supply this is small but not zero.
Secondary-side equivalent: \begin{align*} U_{\rm k,2}\approx 0.217~{\rm V} \end{align*}
A transformer has the rated primary data
\begin{align*} U_{1{\rm N}}=230~{\rm V}, \qquad I_{1{\rm N}}=2.0~{\rm A}. \end{align*}
The short-circuit equivalent impedance referred to the primary side is
\begin{align*} R_{\rm k}=1.5~\Omega, \qquad X_{\rm k}=4.0~\Omega. \end{align*}
1. Calculate $|\underline{Z}_{\rm k}|$.
The short-circuit impedance magnitude is: \begin{align*} |\underline{Z}_{\rm k}| = \sqrt{R_{\rm k}^2+X_{\rm k}^2} \end{align*}
Insert the values: \begin{align*} |\underline{Z}_{\rm k}| &= \sqrt{(1.5~\Omega)^2+(4.0~\Omega)^2} \\ &= 4.27~\Omega \end{align*}
2. Calculate the rated short-circuit voltage $U_{1{\rm k}}$.
The primary voltage required to drive rated current through the short-circuited transformer is: \begin{align*} U_{1{\rm k}} = |\underline{Z}_{\rm k}|I_{1{\rm N}} \end{align*}
Insert the values: \begin{align*} U_{1{\rm k}} &= 4.27~\Omega\cdot 2.0~{\rm A} \\ &= 8.54~{\rm V} \end{align*}
3. Calculate the relative short-circuit voltage ${\rm u_k}$.
The relative short-circuit voltage is: \begin{align*} {\rm u_k} = \frac{U_{1{\rm k}}}{U_{1{\rm N}}}\cdot 100~\% \end{align*}
Insert the values: \begin{align*} {\rm u_k} &= \frac{8.54~{\rm V}}{230~{\rm V}}\cdot 100~\% \\ &= 3.71~\% \end{align*}
4. Calculate the prospective continuous short-circuit current $I_{1{\rm k}}$ for rated primary voltage.
The prospective continuous short-circuit current is: \begin{align*} I_{1{\rm k}} = I_{1{\rm N}}\cdot \frac{100~\%}{\rm u_k} \end{align*}
Insert the values: \begin{align*} I_{1{\rm k}} &= 2.0~{\rm A}\cdot \frac{100}{3.71} \\ &= 53.9~{\rm A} \end{align*}
5. Calculate the approximate first peak current $i_{\rm peak}\approx 2.54 I_{1{\rm k}}$.
The approximate first peak current is: \begin{align*} i_{\rm peak} \approx 2.54 I_{1{\rm k}} \end{align*}
Insert the short-circuit current: \begin{align*} i_{\rm peak} &\approx 2.54\cdot 53.9~{\rm A} \\ &= 137~{\rm A} \end{align*}
Even though the rated current is only $2.0~{\rm A}$, a short-circuit fault could lead to a much larger current until protection reacts.
A transformer has the turns ratio $n=10$.
The short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.4~\Omega$, $X_{\rm k}=3.6~\Omega$.
The secondary load current is $I_2=4.0~{\rm A}$. The load has the power factor $\cos\varphi=0.8$ and is inductive.
Estimate the voltage drop on the secondary side using
\begin{align*} \Delta U_1 \approx I_1\left(R_{\rm k}\cos\varphi+X_{\rm k}\sin\varphi\right) \end{align*}
and
\begin{align*} \Delta U_2\approx \frac{\Delta U_1}{n}. \end{align*}
1. Calculate the primary current magnitude $I_1$.
The primary current magnitude is approximately: \begin{align*} I_1 = \frac{I_2}{n} \end{align*}
Insert the values: \begin{align*} I_1 &= \frac{4.0~{\rm A}}{10} \\ &= 0.40~{\rm A} \end{align*}
2. Determine $\sin\varphi$ for the inductive load.
For an inductive load with $\cos\varphi=0.8$: \begin{align*} \sin\varphi = \sqrt{1-\cos^2\varphi} \end{align*}
Insert the value: \begin{align*} \sin\varphi &= \sqrt{1-0.8^2} \\ &= 0.6 \end{align*}
3. Estimate the primary-side voltage drop $\Delta U_1$.
Use the Kapp approximation: \begin{align*} \Delta U_1 &\approx I_1\left(R_{\rm k}\cos\varphi+X_{\rm k}\sin\varphi\right) \end{align*}
Insert the values: \begin{align*} \Delta U_1 &\approx 0.40~{\rm A} \left( 2.4~\Omega\cdot 0.8 + 3.6~\Omega\cdot 0.6 \right) \\ &= 0.40~{\rm A} \left( 1.92~\Omega+2.16~\Omega \right) \\ &= 1.63~{\rm V} \end{align*}
4. Estimate the secondary-side voltage drop $\Delta U_2$.
The secondary-side voltage drop is: \begin{align*} \Delta U_2 \approx \frac{\Delta U_1}{n} \end{align*}
Insert the values: \begin{align*} \Delta U_2 &\approx \frac{1.63~{\rm V}}{10} \\ &= 0.163~{\rm V} \end{align*}
The secondary voltage decreases by approximately $0.16~{\rm V}$ for this operating point.
The secondary voltage decreases by approximately $0.16~{\rm V}$.
A transformer has the rated primary voltage $U_{1{\rm N}}=230~{\rm V}$. Its rated primary current is $I_{1{\rm N}}=3.0~{\rm A}$.
At rated voltage and no-load operation, the magnetizing current is approximately $I_{\rm m,N}=0.12~{\rm A}$. The short-circuit voltage is ${\rm u_k}=6.0~\%$.
Assume that the magnetizing current is approximately proportional to the applied voltage.
1. Calculate the short-circuit test voltage $U_{1{\rm k}}$.
The short-circuit test voltage is: \begin{align*} U_{1{\rm k}} = \frac{\rm u_k}{100~\%}\cdot U_{1{\rm N}} \end{align*}
Insert the values: \begin{align*} U_{1{\rm k}} &= 0.06\cdot 230~{\rm V} \\ &= 13.8~{\rm V} \end{align*}
2. Estimate the magnetizing current $I_{\rm m,k}$ during the short-circuit test.
The magnetizing current is assumed to be proportional to the voltage: \begin{align*} I_{\rm m,k} = I_{\rm m,N}\cdot \frac{U_{1{\rm k}}}{U_{1{\rm N}}} \end{align*}
Insert the values: \begin{align*} I_{\rm m,k} &= 0.12~{\rm A}\cdot \frac{13.8~{\rm V}}{230~{\rm V}} \\ &= 0.0072~{\rm A} \\ &= 7.2~{\rm mA} \end{align*}
3. Compare $I_{\rm m,k}$ with $I_{1{\rm N}}$.
Compare the short-circuit magnetizing current with the rated current: \begin{align*} \frac{I_{\rm m,k}}{I_{1{\rm N}}} = \frac{0.0072~{\rm A}}{3.0~{\rm A}} \end{align*}
Calculate the ratio: \begin{align*} \frac{I_{\rm m,k}}{I_{1{\rm N}}} &= 0.0024 \\ &= 0.24~\% \end{align*}
4. Explain why the magnetizing branch can be neglected.
During the short-circuit test, the applied voltage is much smaller than the rated voltage: \begin{align*} U_{1{\rm k}} \ll U_{1{\rm N}} \end{align*}
Since the magnetizing current is assumed to be approximately proportional to the applied voltage, the magnetizing current is also very small: \begin{align*} I_{\rm m,k}=7.2~{\rm mA} \end{align*}
Compared with the rated current: \begin{align*} I_{1{\rm N}}=3.0~{\rm A} \end{align*}
the magnetizing current is only $0.24~\%$.
So during the short-circuit test, almost all current flows through the short-circuit path consisting of $R_{\rm k}$ and $X_{\rm k}$.
A transformer has the turns ratio $n=10$. The short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.0~\Omega$, $X_{\rm k}=4.0~\Omega$.
The secondary load current is $I_2=5.0~{\rm A}$. The load is ohmic-inductive with $\cos\varphi=0.8$.
The no-load current on the primary side is approximately $I_{10}=0.03~{\rm A}$.
1. Calculate the load-related primary current $I'_2$.
The load-related primary current is: \begin{align*} I'_2 = \frac{I_2}{n} \end{align*}
Insert the values: \begin{align*} I'_2 &= \frac{5.0~{\rm A}}{10} \\ &= 0.50~{\rm A} \end{align*}
2. Estimate the primary-side voltage drop.
The voltage drop is estimated with: \begin{align*} \Delta U_1 \approx I'_2 \left( R_{\rm k}\cos\varphi + X_{\rm k}\sin\varphi \right) \end{align*}
For $\cos\varphi=0.8$: \begin{align*} \sin\varphi &= \sqrt{1-\cos^2\varphi} \\ &= \sqrt{1-0.8^2} \\ &= 0.6 \end{align*}
Insert the values: \begin{align*} \Delta U_1 &\approx 0.50~{\rm A} \left( 2.0~\Omega\cdot 0.8 + 4.0~\Omega\cdot 0.6 \right) \\ &= 0.50~{\rm A} \left( 1.6~\Omega+2.4~\Omega \right) \\ &= 2.0~{\rm V} \end{align*}
3. Calculate the secondary-side voltage drop $\Delta U_2\approx \frac{\Delta U_1}{n}$.
The secondary-side voltage drop is: \begin{align*} \Delta U_2 \approx \frac{\Delta U_1}{n} \end{align*}
Insert the values: \begin{align*} \Delta U_2 &\approx \frac{2.0~{\rm V}}{10} \\ &= 0.20~{\rm V} \end{align*}
4. Estimate an upper bound for the neglected voltage drop caused by $I_{10}$.
First calculate the magnitude of the short-circuit impedance: \begin{align*} |\underline{Z}_{\rm k}| = \sqrt{R_{\rm k}^2+X_{\rm k}^2} \end{align*}
Insert the values: \begin{align*} |\underline{Z}_{\rm k}| &= \sqrt{(2.0~\Omega)^2+(4.0~\Omega)^2} \\ &= 4.47~\Omega \end{align*}
The upper bound for the voltage drop caused by the no-load current is: \begin{align*} \Delta U_{1,10} &\leq |\underline{Z}_{\rm k}|I_{10} \\ &= 4.47~\Omega\cdot 0.03~{\rm A} \\ &= 0.134~{\rm V} \end{align*}
On the secondary side: \begin{align*} \Delta U_{2,10} &\leq \frac{0.134~{\rm V}}{10} \\ &= 0.0134~{\rm V} \end{align*}
5. Decide whether the short-circuit equivalent circuit is sufficient for this load estimate.
The load-related secondary-side voltage drop is: \begin{align*} \Delta U_2\approx 0.20~{\rm V} \end{align*}
The estimated neglected secondary-side voltage drop caused by the no-load current is at most: \begin{align*} \Delta U_{2,10}\leq 0.0134~{\rm V} \end{align*}
This is small compared with the load-related drop of $0.20~{\rm V}$.
A transformer has the rated primary voltage of $U_1=230~{\rm V}$ and and the turns ratio $n=10$. A resistive load draws $I_2=4.0~{\rm A}$.
For the real transformer, the short-circuit equivalent parameters referred to the primary side are $R_{\rm k}=2.4~\Omega$, $X_{\rm k}=3.2~\Omega$.
The iron loss is approximately $P_{\rm Fe}=1.5~{\rm W}$.
Assume a resistive load with $\cos\varphi=1$.
1. Calculate the ideal secondary voltage $U_{2,\rm ideal}$.
For the ideal transformer: \begin{align*} U_{2,\rm ideal} = \frac{U_1}{n} \end{align*}
Insert the values: \begin{align*} U_{2,\rm ideal} &= \frac{230~{\rm V}}{10} \\ &= 23.0~{\rm V} \end{align*}
2. Calculate the load-related primary current $I'_2$.
The load-related primary current is: \begin{align*} I'_2 = \frac{I_2}{n} \end{align*}
Insert the values: \begin{align*} I'_2 &= \frac{4.0~{\rm A}}{10} \\ &= 0.40~{\rm A} \end{align*}
3. Estimate the real secondary voltage.
For a resistive load, the approximate primary-side voltage drop is: \begin{align*} \Delta U_1 \approx I'_2R_{\rm k} \end{align*}
Insert the values: \begin{align*} \Delta U_1 &\approx 0.40~{\rm A}\cdot 2.4~\Omega \\ &= 0.96~{\rm V} \end{align*}
The corresponding secondary-side voltage drop is: \begin{align*} \Delta U_2 &\approx \frac{\Delta U_1}{n} \\ &= \frac{0.96~{\rm V}}{10} \\ &= 0.096~{\rm V} \end{align*}
Thus the real secondary voltage is approximately: \begin{align*} U_{2,\rm real} &\approx 23.0~{\rm V}-0.096~{\rm V} \\ &= 22.90~{\rm V} \end{align*}
4. Estimate the copper losses.
The copper losses are: \begin{align*} P_{\rm Cu} \approx R_{\rm k}(I'_2)^2 \end{align*}
Insert the values: \begin{align*} P_{\rm Cu} &\approx 2.4~\Omega\cdot (0.40~{\rm A})^2 \\ &= 0.384~{\rm W} \end{align*}
The real transformer also has iron losses: \begin{align*} P_{\rm Fe}=1.5~{\rm W} \end{align*}
Additionally: \begin{align*} P_{\rm Fe}=1.5~{\rm W} \end{align*}
5. Compare ideal and real transformer behavior.
For the ideal transformer: \begin{align*} U_{2,\rm ideal}=23.0~{\rm V} \end{align*}
For the real transformer: \begin{align*} U_{2,\rm real}\approx 22.90~{\rm V} \end{align*}
The real transformer has copper losses and iron losses: \begin{align*} P_{\rm Cu}&\approx 0.384~{\rm W} \\ P_{\rm Fe}&=1.5~{\rm W} \end{align*}
So the main differences are:
For this operating point the transformer is close to ideal, but not exactly ideal.
For this operating point it is close to ideal, but not exactly ideal.