   * **Mixing peak values and RMS values:** In AC power and transformer ratings, \(U\) and \(I\) usually mean RMS values. Time functions are written \(u(t)\), \(i(t)\). Instantaneous short-circuit peaks are written here as \(i_{\rm p}\).   * **Mixing peak values and RMS values:** In AC power and transformer ratings, \(U\) and \(I\) usually mean RMS values. Time functions are written \(u(t)\), \(i(t)\). Instantaneous short-circuit peaks are written here as \(i_{\rm p}\).
   * **Confusing reluctance and resistance:** Magnetic reluctance \(R_{\rm m}\) has the unit \(1/{\rm H}\), not \(\Omega\).   * **Confusing reluctance and resistance:** Magnetic reluctance \(R_{\rm m}\) has the unit \(1/{\rm H}\), not \(\Omega\).
-  * **Confusing \(n\) and the technical no-load voltage ratio \(\ddot{u}\):** The ideal ratio is \(n=\frac{N_1}{N_2}\). The measured no-load voltage ratio is close to \(n\), but not exactly equal for a real transformer.+  * **Confusing \(n\) and the technical no-load voltage ratio \(\ddot{\rm u}\):** The ideal ratio is \(n=\frac{N_1}{N_2}\). The measured no-load voltage ratio is close to \(n\), but not exactly equal for a real transformer.
   * **Forgetting the square when referring impedances:** Voltages transform with \(n\), currents with \(\frac{1}{n}\), but impedances transform with \(n^2\).   * **Forgetting the square when referring impedances:** Voltages transform with \(n\), currents with \(\frac{1}{n}\), but impedances transform with \(n^2\).
   * **Ignoring leakage reactance:** Leakage reactance is often the dominant part of short-circuit impedance. It strongly affects fault current and voltage drop.   * **Ignoring leakage reactance:** Leakage reactance is often the dominant part of short-circuit impedance. It strongly affects fault current and voltage drop.